Clermont Health And Rehabilitation Center
Inspection history, citations, penalties and survey trends for this long-term care facility in Clermont, Florida.
- Location
- 151 E Minnehaha Ave, Clermont, Florida 34711
- CMS Provider Number
- 105512
- Inspections on file
- 20
- Latest survey
- August 7, 2025
- Citations (last 12 mo.)
- 7
Citation history
Health deficiencies cited at Clermont Health And Rehabilitation Center during CMS and state inspections, most recent first.
Several residents did not receive their prescribed long-acting insulin or hypotensive medications as ordered, with LPNs documenting that doses were held or not required without physician parameters or proper documentation. Staff interviews revealed confusion about medication administration protocols, and nursing progress notes lacked explanations for withheld medications. The DON confirmed that staff did not follow physician orders, and medical records did not justify the omissions.
A resident receiving tube feeding was observed lying flat in bed while the feeding pump was running, despite physician orders and the care plan requiring head of bed elevation during feeding. Nursing staff confirmed the need for at least a 30-degree elevation, and the DON reported the facility lacked a formal tube feeding policy.
A physician did not document the rationale for disagreeing with a pharmacist's recommendation to discontinue several PRN medications for a resident, leaving the rationale section blank on the pharmacy review form. The DON and physician confirmed that while rationales are usually provided, time constraints led to the omission in this case.
A resident with diabetes had multiple elevated blood sugar readings requiring PRN glipizide, but the MAR lacked documentation of administration or refusal on numerous occasions. Nursing staff reported confusion about where to document PRN medication, and the DON confirmed this issue. The facility's policy required immediate and accurate documentation, which was not consistently followed.
A resident with MRSA receiving IV antibiotics was not placed on contact precautions, and staff failed to use appropriate PPE or perform hand hygiene during care. Staff entered the room, provided direct care, and performed invasive procedures without donning gowns or gloves, and there was no isolation signage posted, despite facility policy and physician orders requiring these precautions.
The facility failed to ensure the accuracy of the MDS for two residents who were discharged. One resident's discharge was incorrectly documented as to a short-term general hospital instead of the community, and another resident's discharge was incorrectly documented as unplanned instead of planned.
The facility failed to ensure two residents received oxygen as per physician orders. One resident received oxygen at 3 LPM instead of the ordered 2 LPM, and another received oxygen at 4 LPM instead of the ordered 2 LPM. Both residents relied on nurses to manage their oxygen levels, and the DON confirmed the discrepancies.
The facility failed to ensure a safe and homelike environment in two residential units, with issues such as separated baseboard molding, broken floor strips, and a broken windowsill tile. Additionally, a spill in a resident hallway was not immediately addressed by staff, posing safety risks. Interviews confirmed the urgency of these repairs and the expectation for staff to address safety concerns promptly.
The facility failed to provide appropriate urinary catheter care for a resident with a suprapubic catheter. Observations revealed that the catheter tubing was looped and resting on the floor, preventing urine from draining into the catheter bag, which was also found resting in a basin with fluid. Staff members acknowledged improper handling of the catheter tubing and drainage bag, and the facility lacked a specific policy for catheter care.
The facility failed to store foods safely and sanitarily in the main kitchen. Unlabeled and undated food items, including 2.5-gallon buckets of yellowish liquid, a steam pan with a purple jelly-like substance, and an opened bag of plant-based chicken nuggets, were found in the walk-in cooler. The Certified Dietary Manager confirmed these items should have been labeled and dated according to facility policy.
The facility failed to ensure staff performed hand hygiene during medication administration and did not follow infection control standards for administering subcutaneous medications. An RN prepared and administered oral medications to a resident without performing hand hygiene and administered an insulin injection to another resident without cleaning the skin with an alcohol wipe. The DON confirmed that staff should wash their hands before and after every patient interaction.
Failure to Administer Medications as Ordered and Inadequate Documentation
Penalty
Summary
The facility failed to ensure that insulin and hypotensive medications were administered according to physician orders for multiple residents. For several residents with diabetes mellitus, long-acting insulin was not administered as ordered, with staff documenting codes indicating the medication was not required or was held, despite the absence of physician parameters allowing for such actions. Medication Administration Records (MARs) showed repeated instances where insulin doses were omitted, and nursing progress notes lacked documentation explaining the rationale for withholding the medication. Interviews with LPNs revealed a misunderstanding of when to hold long-acting insulin, with some staff stating they used their own judgment or believed parameters existed when they did not. The Director of Nursing confirmed that there were no orders to hold the long-acting insulin, and the expectation was for staff to follow physician orders. In addition to the insulin administration issues, the facility failed to administer midodrine, a medication for hypotension, as ordered for a resident with low systolic blood pressure. Despite multiple documented instances of systolic blood pressure readings below the physician-ordered threshold, the medication was not given. Staff interviews indicated confusion regarding the parameters for administering midodrine, with one LPN stating they focused on diastolic rather than systolic blood pressure and referencing facility in-service training that may have contributed to the misunderstanding. The DON acknowledged that the nurse involved was confused about the correct parameters and that staff are expected to follow provider orders. Across all cases, there was a lack of appropriate documentation in the medical records to justify withholding medications, and staff interviews consistently revealed gaps in knowledge or misinterpretation of physician orders. The deficiencies were identified through review of physician orders, MARs, nursing progress notes, and staff and physician interviews, all of which confirmed that medications were not administered as prescribed and that documentation and communication with providers were insufficient.
Failure to Maintain Proper Positioning During Tube Feeding
Penalty
Summary
A deficiency was identified when a resident receiving enteral nutrition via a PEG tube was observed lying flat in bed with the tube feeding pump running, contrary to physician orders and the resident's care plan, which required the head of bed to be elevated during feeding and medication administration. The resident's physician order specified that the head of bed should be elevated while feeding to prevent complications, and the care plan included the same intervention. During interviews, nursing staff confirmed that the head of bed should be at least at a 30-degree angle during tube feeding. Additionally, when asked, the Director of Nursing stated that the facility did not have a formal policy on tube feeding, only a standard practice.
Physician Failed to Document Rationale for Disagreement with Pharmacist Recommendations
Penalty
Summary
The facility failed to ensure that the physician documented the rationale for disagreeing with the pharmacist's recommendations regarding the discontinuation of several PRN medications for one resident. During a monthly drug regimen review, the pharmacist recommended discontinuing multiple PRN medications due to non-use, but the physician responded with 'Disagree' and left the rationale section blank. The document was signed by the physician without any explanation for the disagreement. Interviews with the Director of Nursing and the physician confirmed that pharmacy reviews are conducted monthly, and while the physician typically writes a rationale for disagreements, in this instance, no rationale was provided due to time constraints.
Incomplete Documentation of PRN Antidiabetic Medication Administration
Penalty
Summary
The facility failed to ensure that medical records for a resident receiving antidiabetic medication were complete and accurate. Physician orders required blood sugar monitoring every 12 hours and administration of glipizide as needed when blood sugar exceeded 180. Review of the resident's Medication Administration Records (MAR) for two consecutive months showed multiple instances where blood sugar readings were above the threshold, but there was no documentation of glipizide administration or refusal. Interviews with nursing staff revealed confusion regarding where to document the administration of PRN glipizide, with some staff indicating they may have documented in the wrong area or could not recall specific events. The Director of Nursing acknowledged this confusion among staff regarding documentation procedures for PRN medications. The resident in question had a history of diabetes mellitus and was described as frequently non-compliant with her antidiabetic medication, often refusing both oral and injectable treatments. Despite this, the facility's policy required immediate and accurate documentation of all medication administrations, including PRN medications, specifying the need to record the date, time, dose, and route. The lack of documentation on the MAR for multiple dates where blood sugar was elevated and glipizide should have been administered or refused constituted a failure to maintain complete and accurate medical records in accordance with professional standards.
Failure to Implement Contact Precautions and PPE Use for Resident with MRSA
Penalty
Summary
The facility failed to implement appropriate infection prevention and control measures for a resident diagnosed with MRSA who was receiving IV antibiotics. Despite physician orders and care plan interventions specifying contact precautions and enhanced barrier precautions, staff did not consistently use required personal protective equipment (PPE) such as gowns and gloves, nor did they perform hand hygiene when entering the resident's room or providing care. Observations revealed that staff entered the resident's room, delivered meals, assisted with positioning, took vital signs, administered medications, and performed dressing changes without donning PPE or performing hand hygiene. There was also no contact isolation signage on the resident's door, and staff were unaware or misinformed about the resident's isolation status. The resident, who had a history of COPD, asthma, respiratory failure, and was on oxygen and fluid restriction, reported to surveyors that staff did not wear gowns or other protective equipment when assisting her. Staff interviews confirmed a lack of understanding regarding the need for contact precautions. Facility policy required gloves and gowns for contact precaution rooms, but this was not followed in practice, as evidenced by multiple staff failing to use PPE and perform hand hygiene during direct care activities, including invasive procedures such as IV site dressing changes and line flushing.
Inaccurate MDS Documentation for Discharged Residents
Penalty
Summary
The facility failed to ensure the accuracy of the Minimum Data Set (MDS) for two residents who were discharged. For Resident #174, the records indicated a discharge to a short-term general hospital, but the MDS Director confirmed that the discharge should have been documented as to the community. Similarly, for Resident #175, the records showed an unplanned discharge, but the MDS Director stated that it should have been documented as a planned discharge. These inaccuracies were identified during interviews with the MDS Director and through a review of the residents' records.
Failure to Administer Oxygen Per Physician Orders
Penalty
Summary
The facility failed to ensure residents received oxygen as per physician orders for two residents. Resident #139 was observed receiving oxygen at 3 liters per minute (LPM) on two separate occasions, despite a physician order specifying oxygen at 2 LPM as needed for shortness of breath. The resident confirmed that the nurse adjusts the oxygen, and the Director of Nursing (DON) verified the discrepancy between the physician order and the administered oxygen level. Similarly, Resident #154 was observed receiving oxygen at 4 LPM on two separate occasions, contrary to a physician order for oxygen at 2 LPM as needed for shortness of breath. The resident was unaware of the correct oxygen level and relied on the nurses to manage it. The DON confirmed the oxygen concentrator was set incorrectly and verified the physician order. The facility's policy on oxygen therapy, which mandates verifying physician orders and applying the correct liter flow, was not followed.
Failure to Maintain Safe and Homelike Environment
Penalty
Summary
The facility failed to ensure a safe and homelike environment for residents in two of the three residential units, specifically the 200 and 300 Units. Observations revealed several maintenance issues, including separated rubber baseboard molding, broken rubber transition floor strips, and a broken stone tile on a windowsill. These issues were noted in the rooms of multiple residents, including one resident whose bed was improperly positioned against a wall with a broken windowsill tile, posing a safety hazard. Interviews with the Maintenance Director and a Registered Nurse confirmed the urgency of these repairs, highlighting the potential risks to residents' safety. Additionally, a puddle of brown liquid was observed on the floor in a resident hallway near the elevator, with two residents in wheelchairs nearby. A Dietary Aide noticed the spill but did not take immediate action to address it, instead planning to report it later. The Assistant Administrator emphasized that staff are expected to address such safety concerns immediately. The facility's Physical Plant Resource Guide outlines procedures for reporting and prioritizing maintenance issues, but the observed deficiencies indicate a failure to adhere to these protocols, compromising resident safety and the homelike environment.
Failure to Provide Appropriate Urinary Catheter Care
Penalty
Summary
The facility failed to ensure appropriate urinary catheter care for Resident #165, who was admitted with diagnoses including urinary tract infection, type 2 diabetes mellitus, hydronephrosis, and neuromuscular dysfunction of the bladder. The resident's care plan specified that the suprapubic catheter should be kept free of kinks and the drainage bag should be kept below the level of the bladder. However, multiple observations revealed that the urinary catheter tubing was looped and resting on the floor, preventing urine from draining into the catheter bag. Additionally, the catheter bag was found resting in a basin with fluid, indicating improper handling and potential contamination risk. During interviews, staff members, including a Registered Nurse (RN) and the Director of Nursing (DON), acknowledged the improper handling of the catheter tubing and drainage bag. The RN admitted to lifting the catheter tubing above the resident's bladder to facilitate drainage, which is against standard practice. The DON also lifted the drainage bag above the resident's bladder to inspect it, further confirming the improper handling. The DON admitted that the facility did not have a specific policy and procedure for catheter care, relying instead on standard practice guidelines. These actions and inactions led to the deficiency in providing appropriate catheter care for Resident #165.
Failure to Store Food Safely and Sanitarily
Penalty
Summary
The facility failed to ensure foods were stored in a safe and sanitary manner in the main kitchen. During a tour of the main kitchen, two unlabeled and undated 2.5-gallon buckets of yellowish liquid were found on the second shelf of the main walk-in cooler. Additionally, a 4-inch steam pan with a purple jelly-like substance, which had no label and an expiration date of 4/23/2024, was observed on the same shelf. An opened and undated bag of plant-based chicken nuggets was also found on the third shelf of the walk-in cooler. The Certified Dietary Manager (CDM) confirmed the presence of these unlabeled and undated food items and acknowledged that all items should have labels and expiration date stickers before storage. The facility's policy, effective January 2023, mandates labeling all leftovers with the recipe name, date of storage, and use-by date, and discarding refrigerated leftovers after 72 hours.
Failure to Perform Hand Hygiene and Follow Infection Control Standards
Penalty
Summary
The facility failed to ensure staff performed hand hygiene during medication administration and did not follow infection control standards for administering subcutaneous medications. During an observation, a Registered Nurse (RN) prepared and administered oral medications to a resident without performing hand hygiene. The RN acknowledged the lapse in hand hygiene during an interview. Additionally, the same RN administered an insulin injection to another resident without performing hand hygiene before donning gloves and without cleaning the skin with an alcohol wipe prior to the injection. The RN admitted to not using an alcohol wipe and not performing hand hygiene before administering the medication. The Director of Nursing (DON) confirmed that staff should wash their hands before and after every patient interaction, either with soap and water or hand sanitizer. The facility's policies on medication administration and hand hygiene, last reviewed on 1/5/2024, emphasize the importance of hand hygiene and the use of antimicrobial agents for both medication products and residents' skin. The policies outline specific steps for hand hygiene and the administration of subcutaneous medications, which were not followed by the RN in the observed instances.
Latest citations in Florida
Surveyors found that the facility’s only commercial cooking hood was not maintained in accordance with NFPA 101 and NFPA 96 requirements. During a kitchen tour with the Maintenance Director, the hood was observed to be not grease tight due to missing fire-resistant caulk, and the Maintenance Director acknowledged this condition at the time of the survey.
Surveyors found that the facility failed to comply with NFPA 99, NFPA 70, and NFPA 1 requirements for electrical equipment when, during a tour with the Maintenance Director, a power strip in the electrical room was observed being used as a permanent power source instead of a dedicated receptacle. The report states that this improper use of a relocatable power tap could lead to electrical hazards for residents and staff, and notes that extension cords and power strips are not to be used as substitutes for fixed wiring under the cited codes.
Surveyors found that the facility did not have documentation showing completion of the required annual 90‑minute test of emergency lighting. During record review and interview, the Director of Facilities confirmed that records of this annual test, required under NFPA 101 sections 19.2.9.1 and 7.9, were not available. This deficiency was cited as affecting all occupants in the event of a fire or other emergency.
Surveyors found that the facility failed to perform and/or document the required annual Duct Detector Differential testing for the fire alarm system in accordance with NFPA 101, NFPA 70, and NFPA 72. During record review and interviews with the Director of Facilities, no documentation could be produced to show that this annual testing had been completed, and the Director acknowledged the lack of records. This deficiency was cited as potentially affecting all occupants in the event of a fire or other emergency.
Surveyors found that the facility failed to perform and/or document required annual testing and exercising of main and feeder circuit breakers in accordance with NFPA 99 and manufacturer recommendations. During record review, no documentation could be produced to show that the annual breaker exercises had been completed, and the Director of Facilities acknowledged this lack of records. This deficiency relates to the essential electrical system that supports life safety and critical branches during emergencies.
Surveyors observed that an adapter was used to power a refrigerator in the kitchen and a refrigerator in the dining room manager's office was plugged into a power strip. The Director of Facilities confirmed both uses, which did not comply with NFPA 99 and NFPA 70 requirements prohibiting adapters and power strips from being used as substitutes for permanent wiring.
Surveyors found that food service operations failed to meet professional food safety standards in both the main and satellite kitchens. In the main kitchen, a cook’s facial hair was not fully covered, the handwashing sink did not initially provide warm water, wet-nested pans and dirty plate domes were stored for use, ice buckets were stained with mold-like discoloration, and the high-temp dishwasher failed to reach the required sanitizing temperature. In the satellite pantry, the dishwasher did not reach required wash temperatures, vents and cabinets above serving dishes had mold-like buildup and residue, floors were damaged and soiled, the dishwasher chemical cabinet was rusted, the AC filter was heavily soiled, the juice dispenser had debris near clean cups, and tray carts contained dirty sheet trays. During tray line observation, salad items were held above 41°F, and a pureed vegetable listed on the menu extension was not available on the line.
Two residents on physician-ordered modified diets (pureed and mechanical soft with nectar-thick liquids) were given Regular Menus listing items such as fresh fruit, salad greens, and grilled cheese that were not compatible with their diet orders. Both residents selected items from these Regular Menus, but the facility either could not provide the chosen foods due to diet restrictions or substituted different items (e.g., canned peach halves instead of fresh fruit), despite the residents’ expressed preferences. The RD and dietetic technician confirmed that Regular Menus were routinely provided to all residents, including those on mechanically altered diets, leading to menu choices that did not align with ordered diet consistencies.
Surveyors found that the facility did not follow physician-ordered therapeutic diets or provide prescribed Magic Cup nutritional supplements for several cognitively impaired residents. A resident on a pureed diet with honey-thick liquids was served a lunch without the ordered pureed vegetable, and tray line review on another day showed no pureed vegetables available despite the menu specifying them. Multiple residents with orders for Magic Cup supplements had these listed on their meal tickets but were instead served other desserts or received no supplement at all, while documentation on the MAR indicated full consumption. Dietary staff acknowledged responsibility for providing Magic Cups but could not explain why residents in the dining room did not receive them.
A resident with intact cognition and multiple cardiac and pulmonary diagnoses had clearly documented DNR orders, including signed advance directive forms and care plan entries confirming her wish to avoid resuscitation. During a cardiac emergency, a CNA found the resident unresponsive and notified an RN, who initiated a code blue response. Several RNs and LPNs transferred the resident to bed and began CPR without first verifying code status, despite one LPN asking and then leaving the room to check the record. Staff interviews and video review showed that chest compressions and use of a bag-valve mask continued for about 12 minutes until EMS arrived, even after staff learned the resident was DNR, and the physician confirmed the resident was already listed as DNR in the system, leading to an Immediate Jeopardy finding for failure to honor advance directives.
Commercial Cooking Hood Not Maintained Grease Tight per NFPA Standards
Penalty
Summary
Surveyors identified a deficiency involving the facility’s commercial cooking facilities. During a tour of the kitchen between 1:00 p.m. and 3:00 p.m. with the Maintenance Director, surveyors observed that the one commercial cooking hood in use was not grease tight. Specifically, the hood was missing required fire-resistant caulk, which is necessary for maintaining a grease-tight seal in accordance with NFPA 96 and NFPA 101 standards. The Maintenance Director acknowledged these findings at the time of observation. The deficiency was cited under NFPA 101 and NFPA 96 requirements for commercial cooking operations, which mandate that cooking equipment and associated hoods be protected and maintained in compliance with these fire and life safety codes.
Plan Of Correction
Preparation and/or execution of this plan does not constitute admission or agreement by the provider of the truth of the facts alleged or conclusions set forth on the statement of deficiencies. This plan of correction is prepared and/or executed solely because required. What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice? No residents were affected by this deficient practice. How you will identify other residents having potential to be affected by the same practice and what corrective actions will be taken; Commercial cooking hood system inspected; no additional deficient areas were identified. What measures will be put into place or what systematic changes will you make to ensure that the practice does not recur:Maintenance staff and Dietary staff education on proper use and reporting of issues related to cooking hood system.Verification of scheduled inspections and cleaning of cooking hood system by licensed vendor.How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put in place:The maintenance director/designee will complete weekly audits of cooking hood system for 4 weeks, then monthly for 2 months to ensure compliance. The findings will be reported to the Quality Assurance Performance Improvement Committee for ongoing compliance. Preparation and/or execution of this plan does not constitute admission or agreement by the provider of the truth of the facts alleged or conclusions set forth on the statement of deficiencies. This plan of correction is prepared and/or executed solely because required. What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice? No residents were affected by this deficient practice. How you will identify other residents having potential to be affected by the same practice and what corrective actions will be taken; Commercial cooking hood system inspected; no additional deficient areas were identified. What measures will be put into place or what systematic changes will you make to ensure that the practice does not recur; Maintenance staff and Dietary staff education on proper use and reporting of issues related to cooking hood system. Verification of scheduled inspections and cleaning of cooking hood system by licensed vendor. How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put in place; The maintenance director/designee will complete weekly audits of cooking hood system for 4 weeks, then monthly for 2 months to ensure compliance. The findings will be reported to the Quality Assurance Performance Improvement Committee for ongoing compliance.
Improper Use of Power Strip as Permanent Power Source in Electrical Room
Penalty
Summary
Surveyors identified a deficiency related to improper use of relocatable power taps (RPTs) and power strips in violation of NFPA 99, NFPA 70, and NFPA 1 requirements. During a facility tour conducted between 10:00 a.m. and 12:00 p.m. with the Maintenance Director, surveyors observed one power strip in the electrical room being used as a source of permanent power instead of being connected to a dedicated receptacle. The report notes that this use did not comply with standards that require extension cords and power strips not be used as a substitute for fixed wiring and that they be used only under specified conditions. The deficiency specifically concerns the facility’s failure to ensure that RPTs are maintained and used in accordance with NFPA 99 (2012 Edition) sections 10.2.3.6 and 10.2.4, and NFPA 70 (2011 and 2020 Editions) provisions governing flexible cords and temporary wiring, as well as NFPA 1 (2021 Edition) sections 11.1.2.2, 11.1.4.1, and 1.4.1. The report states that this condition could lead to electric hazards for residents and staff. No individual resident cases, medical histories, or specific clinical conditions are described in connection with this deficiency.
Plan Of Correction
What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice? No residents were affected by this deficient practice. How you will identify other residents having potential to be affected by the same practice and what corrective actions will be taken; Facility wide audit of electrical rooms was conducted to identify improper use of power strips. No additional concerns were identified. What measures will be put into place or what systematic changes you will make to ensure that the practice does not recur; The facility completed education reinforcing compliance with electrical safety requirements in accordance with National Fire Protection Association. How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put in place: The maintenance director/designee will complete random electrical safety audits 2 times per week for 4 weeks, then monthly to ensure compliance with electrical safety standards. The findings will be reported to the Quality Assurance Performance Improvement Committee for ongoing compliance. What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice? No residents were affected by this deficient practice. How you will identify other residents having potential to be affected by the same practice and what corrective actions will be taken; Facility wide audit of electrical rooms was conducted to identify improper use of power strips. No additional concerns were identified. What measures will be put into place or what systematic changes you will make to ensure that the practice does not recur; The facility completed education reinforcing compliance with electrical safety requirements in accordance with National Fire Protection Association. How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put in place; The maintenance director/designee will complete random electrical safety audits 2 times per week for 4 weeks, then monthly to ensure compliance with electrical safety standards. The findings will be reported to the Quality Assurance Performance Improvement Committee for ongoing compliance.
Failure to Document Required Annual 90‑Minute Emergency Lighting Test
Penalty
Summary
Surveyors identified a deficiency related to emergency lighting when, during record review and staff interview between 11:30 AM and 3:00 PM with the Director of Facilities, the facility was unable to provide documentation that the required annual 90‑minute testing of emergency lighting had been performed. The Director of Facilities acknowledged that there was no documentation available to show completion of this annual 90‑minute emergency lighting test, as required by NFPA 101 (2012 and 2021 editions), sections 19.2.9.1 and 7.9. This failure to document the annual emergency lighting test was cited as a noncompliance that could affect all occupants of the facility in the event of a fire or other emergency. No specific residents, medical histories, or clinical conditions were mentioned in the report; the deficiency pertains to facility-wide life safety systems and their required testing and documentation.
Plan Of Correction
Emergency Lighting CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Emergency Lighting K0291 The facility immediately conducted a comprehensive inspection of all emergency lighting systems. On The Director of Facilities performed the required 90-minute annual testing of all emergency lighting units. Documentation of testing has been completed and is maintained on-site. 2. All areas of the facility were considered at risk due to lack of documented annual testing. A full facility-wide audit of all emergency lighting units was completed on by the Director of Facilities to ensure compliance. 3. The facility implemented a preventative maintenance schedule to ensure annual 90-minute emergency lighting testing is completed in accordance with NFPA 101 (2012), Section 7.9. A log tracking system has been developed to document all required testing. The Director of Facilities/designee will receive re-education on Life Safety Code requirements and documentation standards. 4. The Director of Facilities will review fire alarm testing records quarterly for 12 months, will present the findings for 12 months at Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the twelve months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required. Emergency Lighting CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Emergency Lighting K0291 The facility immediately conducted a comprehensive inspection of all emergency lighting systems. On The Director of Facilities performed the required 90-minute annual testing of all emergency lighting units. Documentation of testing has been completed and is maintained on-site. 2. All areas of the facility were considered at risk due to lack of documented annual testing. A full facility-wide audit of all emergency lighting units was completed on by the Director of Facilities to ensure compliance. 3. The facility implemented a preventative maintenance schedule to ensure annual 90-minute emergency lighting testing is completed in accordance with NFPA 101 (2012), Section 7.9. A log tracking system has been developed to document all required testing. The Director of Facilities/designee will receive re-education on Life Safety Code requirements and documentation standards. 4. The Director of Facilities will review fire alarm testing records quarterly for 12 months, will present the findings for 12 months at Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the twelve months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required.
Failure to Perform and Document Annual Duct Detector Differential Testing
Penalty
Summary
Surveyors identified a deficiency related to the facility’s fire alarm system testing and maintenance, specifically the required annual Duct Detector Differential testing. During record review conducted between 11:30 AM and 3:00 PM, surveyors requested documentation demonstrating that this annual testing had been completed in accordance with NFPA 101 (2012 and 2021 editions), NFPA 70, and NFPA 72. The facility was unable to produce records showing that the Duct Detector Differential testing had been performed as required. In an interview conducted during the same time frame, the Director of Facilities acknowledged that the facility failed to provide documentation of the annual Duct Detector Differential testing. The deficiency was cited under NFPA 101 2012 (19.2.9.1, 7.9) and NFPA 101 2021 (19.2.9.1, 7.9), indicating noncompliance with the standards that require fire alarm detection systems, including duct detectors, to be tested and maintained annually. The report notes that this deficiency could affect all occupants of the facility in the event of a fire or other emergency.
Plan Of Correction
Fire Alarm System - Testing and Maintenance CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Fire Alarm System - Testing and Maintenance K0345 1. On The facility a certified fire alarm vendor to perform annual duct detector differential testing. All required testing has now been completed and documented. 2. All residents and staff were considered at risk due to lack of documented testing. A facility-wide review of all fire alarm components was conducted on 3. The facility established a service agreement to ensure all fire alarm testing (including duct detectors) is completed annually per NFPA 72 and NFPA 101 requirements. A compliance calendar has been implemented with alerts for required inspections and testing. The Director of Facilities/designee has been re-educated on required testing intervals and documentation. 4. The Director of Facilities or designee will audit for 3 months all documentation for the annual testing and inspection of the duct detector pressure differential test. The Director of Facilities will present the findings of site inspections for 3 months at Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required Fire Alarm System - Testing and Maintenance CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Fire Alarm System - Testing and Maintenance K0345 1. On The facility a certified fire alarm vendor to perform annual duct detector differential testing. All required testing has now been completed and documented. 2. All residents and staff were considered at risk due to lack of documented testing. A facility-wide review of all fire alarm components was conducted on. 3. The facility established a service agreement to ensure all fire alarm testing (including duct detectors) is completed annually per NFPA 72 and NFPA 101 requirements. A compliance calendar has been implemented with alerts for required inspections and testing. The Director of Facilities/designee has been re-educated on required testing intervals and documentation. 4. The Director of Facilities or designee will audit for 3 months all documentation for the annual testing and inspection of the duct detector pressure differential test. The Director of Facilities will present the findings of site inspections for 3 months at Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required
Failure to Perform and Document Annual Main and Feeder Breaker Testing
Penalty
Summary
The deficiency involves the facility’s failure to perform and document required annual maintenance and testing of the main and feeder circuit breakers in accordance with NFPA 99 and manufacturer recommendations. During a record review conducted between 11:30 AM and 3:00 PM, surveyors requested documentation of the annual main and feeder breaker exercise. The facility was unable to provide records demonstrating that this testing and exercising had been completed as required. In interviews conducted during the same time frame, the Director of Facilities acknowledged that the facility did not have documentation showing that the annual main and feeder breaker exercise was performed according to manufacturer recommendations. The report notes that this failure to comply with NFPA 99 (2012 and 2021 editions, Sections 6.4.4 and 6.5.4) could affect all occupants of the facility in the event of a fire or other emergency, and that written records of maintenance and testing are required to be maintained and readily available.
Plan Of Correction
Electrical Systems - Essential Electric System CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Electrical Systems - Essential Electric System Maintenance and Testing K0918 1. On A licensed electrical contractor performed the annual main and feeder breaker testing/exercising in accordance with manufacturer recommendations. Documentation has been completed and is maintained on-site. 2. All residents were considered at risk due to lack of documented testing. A full review of the essential electrical system was conducted on 3. A preventative maintenance program has been implemented to ensure that annual breaker testing is completed per NFPA 99 (2012). The facility has incorporated electrical system testing into its environmental compliance tracking system. The Director of Facilities/designee received re-education on NFPA requirements. 4. The Director of Facilities will audit electrical system maintenance logs quarterly for 12 months. Inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required. Electrical Systems - Essential Electric System CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Electrical Systems - Essential Electric System Maintenance and Testing K0918 1. On A licensed electrical contractor performed the annual main and feeder breaker testing/exercising in accordance with manufacturer recommendations. Documentation has been completed and is maintained on-site. 2. All residents were considered at risk due to lack of documented testing. A full review of the essential electrical system was conducted on . 3. A preventative maintenance program has been implemented to ensure that annual breaker testing is completed per NFPA 99 (2012). The facility has incorporated electrical system testing into its environmental compliance tracking system. The Director of Facilities/designee received re-education on NFPA requirements. 4. The Director of Facilities will audit electrical system maintenance logs quarterly for 12 months. Inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, , and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required.
Improper Use of Adapters and Power Strips for Refrigerators
Penalty
Summary
The deficiency involves improper use of electrical adapters and power strips as substitutes for permanent wiring, in violation of NFPA 99 and NFPA 70 requirements. During an observation with the Director of Facilities, surveyors found that an adapter was being used to power a refrigerator in the kitchen. The Director of Facilities acknowledged that an adapter was in use for this refrigerator, contrary to the standards that prohibit adapters from being used in place of fixed wiring. In a separate observation with the Director of Facilities, surveyors identified that a refrigerator in the dining room manager's office was plugged into a power strip. The Director of Facilities acknowledged that a power strip was being used for this refrigerator. These findings showed that the facility was not complying with NFPA 99 provisions that require power strips and adapters not be used as substitutes for permanent wiring for such equipment.
Plan Of Correction
Formatted text (without <text> tags or quotes): Electrical Equipment - Power and Extension Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Electrical Equipment - Power and Extension K0920 1. On The adapter in the kitchen refrigerator and the power strip in the dining room manager's office were immediately removed. All equipment was plugged directly into approved wall outlets. 2. On A facility-wide inspection was conducted by The Director of Facilities to identify improper use of power strips and adapters. Any non-compliant items were removed immediately. 3. On Staff were educated on proper electrical safety practices, including prohibited use of extension and adapters. Routine environmental rounds now include electrical safety checks. 4. The Director of Facilities/designee will conduct monthly environmental rounds for 3 months, then quarterly thereafter. Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that Continued from page occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required. Electrical Equipment - Power and Extension CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Electrical Equipment - Power and Extension K0920 1. On The adapter in the kitchen refrigerator and the power strip in the dining room manager's office were immediately removed. All equipment was plugged directly into approved wall outlets. 2. On A facility-wide inspection was conducted by The Director of Facilities to identify improper use of power strips and adapters. Any non-compliant items were removed immediately. 3. On Staff were educated on proper electrical safety practices, including prohibited use of extension and adapters. Routine environmental rounds now include electrical safety checks. 4. The Director of Facilities/designee will conduct monthly environmental rounds for 3 months, then quarterly thereafter. Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required.
Food Safety and Sanitation Deficiencies in Main and Satellite Kitchens
Penalty
Summary
Surveyors identified multiple failures to store, prepare, distribute, and serve food in accordance with professional standards for food service safety in both the main kitchen and a satellite pantry kitchen. In the main kitchen, a cook’s beard cover did not fully cover all facial hair, and the handwashing sink initially did not provide warm water until the Executive Director manually adjusted a valve under the sink. In the pot washing area, full-sized steam table pans were stacked while still wet, and more than five plate domes with stuck-on food particles were found piled in the tray line area ready for use, indicating they had not been properly washed. Two large ice buckets were stained with black and grey mold-like discoloration and white wear marks. The high-temperature dishwashing machine in the main kitchen was run three times but failed to reach the required 180°F rinse temperature, only reaching 172°F, meaning dishes were not properly sanitized. In the second-floor satellite pantry kitchen, the high-temperature dishwashing machine was also run three times and failed to meet required wash temperatures, reaching only 139°F instead of the required 150–165°F, so dishes were not properly cleaned and sanitized. Additional sanitation and maintenance issues were observed, including a vent above serving dishes with a mold-like accumulation, broken and soiled cabinets above serving dishes with residue on the handles, and pantry floors with cracked, broken, and missing tiles with debris or residue buildup. The dishwasher chemical cabinet lock was rust-laden, the AC filter was covered with dark grey soot and dust, the juice dispenser with clean cups nearby had debris on top, and tray delivery carts contained large sheet trays with residue and stuck-on food debris. During a tray line observation, chopped tomatoes and sliced avocados on the salad line were held at 44°F and 45°F respectively, above the required 41°F or less, and the menu extension listed pureed peas for a pureed diet, but no pureed vegetable was present on the line.
Plan Of Correction
Food Procurement, Store/Prepare/Serve-Sanitary CFR(s): 483.60(i)(1)(2) §483.60(i) Food safety requirements. Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required F0812 1. All identified sanitation issues were corrected on Hot water valve was fixed immediately by maintenance team Steam table pan wet nesting was corrected The 5 plate domes that were dirty were taken to the dishwasher to be washed Stained ice buckets were replaced with new ones Dishwashing machine not reaching temperature for rinse cycle was fixed by Eco lab the same day Team member was provided education and in-service on proper use of beard guard. Corrected on [R] 2.Identified issues from satellite Kitchen were corrected on [R] Dishwashing machine not reaching temperature for rinse cycle was fixed by Eco lab the same day The vent located above the serving dishes was cleaned by maintenance team The cabinets were cleaned immediately The floors of the pantry area were observed with broken, cracked, missing tiles, with buildup residue and debris. Maintenance director made aware in the process of getting replaced. The locking mechanism of the dishwasher chemical cabinet is rust laden. Laden removed and in the process of being replaced. The AC filter was cleaned by maintenance team Th juice dispenser was cleaned by dietary aide The large delivery trays with residue and food debris were discarded 3. Issues identified during Tray line observation were corrected: The chopped tomatoes and sliced avocados were discarded Pureed vegetable was added to the line. Inservice on serving all food groups, starches, protein and vegetables to residents on texture modified diet order. Inservice provided to all dietary aides Inservice on maintaining and holding temperatures for ready to eat foods. Inservice provided to all cooks and dietary aides Daily sanitation rounds will be conducted by the Certified Dietary manager /designee for one week. Weekly for 2 months. 4. The Certified Dietary Manager/Executive Chef/designee will report the findings of the above observations and audits to the monthly QAPI Committee. The Administrator is responsible for confirming implementation and compliance of this POC and and resolving any variances that may occur.
Failure to Honor Diet-Appropriate Menu Choices for Residents on Modified Diets
Penalty
Summary
The facility failed to provide residents with menu choices that matched their physician-ordered diet textures and liquid consistencies. One resident with severe cognitive impairment had a physician order for a controlled diet with pureed texture and honey-thick liquids. During a noon meal observation, this resident’s meal ticket was stapled to a Regular Menu listing items such as lettuce and tomato salad, stir-fried vegetables, and a grilled cheese sandwich, none of which were appropriate for the resident’s ordered diet. The Registered Dietitian and the Dietetic Technician confirmed that Daily Menu printouts with Regular Menu options were provided to all residents, including those on mechanically altered diets, resulting in residents being offered choices that could not be honored due to diet restrictions. Another resident with moderate cognitive impairment had a physician order for a mechanical soft diet with nectar-thick liquids. This resident’s lunch tray ticket was also stapled to a Regular Menu that included salad greens, which are not allowed on a mechanical soft diet. On a separate breakfast observation, the same resident’s Regular Menu included fresh fruit as a choice, which the resident circled, but the tray contained canned peach halves instead. The resident stated she wanted her chosen fresh fruit rather than the peaches and reiterated her food preferences during the interview. Photographic evidence was obtained to document these discrepancies between ordered diets, menu offerings, and the food actually provided.
Plan Of Correction
Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is requiredF05501. Resident #54 and Resident #56 were immediately assessed by the Registered Dietitian (RD) & CDM (Certified Dietary Manager) for food preferences on Residents #54 and #56 were offered meal choices consistent with the prescribed diet. No adverse outcomes were identified. 2. 100% audit of all residents with therapeutic diets was completed on [R] by CDM to ensure menus and meal selections consistent with physician-ordered diets.On [R] , CDM provided in-service provided to dietary aides, certified nursing assistants, nurses, managers on new selective menu processes. 3. The facility implemented a diet-specific menu system and pre-meal diet verification process by reviewing the diet in tray ticket program IMPAC and PCC. Copies of the menus to be provided as part of the audits.Diet Menu was revised to include a mechanically altered diet to be consistent with physician orders. Therapeutic diets menus are available and offered to each resident according to physician orders. The Dietary Manager or designee will conduct weekly audits of 4 residents on therapeutic diets x 4 weeks then monthly x 2months, to verify the correct menu is offered and served. 4. The Dietary Manager or designee will report findings at the monthly QAPI meeting. The Administrator is responsible for confirming implementation and compliance with this POC and [R] , and resolving any variances that occur.
Failure to Follow Therapeutic Diet Orders and Provide Prescribed Nutritional Supplements
Penalty
Summary
The deficiency involves the facility’s failure to follow physician-ordered therapeutic diets and prescribed nutritional supplements for multiple residents. One resident with severe cognitive impairment and a physician’s order for a controlled diet with pureed texture and honey-thick liquids was observed at lunch without the ordered pureed vegetable; her plate contained only pureed chicken, a pureed starch, and possibly a pureed bread, all covered in gravy. The pureed menu for that meal listed broccoli as the vegetable, and a subsequent tray line observation on another day showed no pureed vegetables available, despite the pureed menu specifying pureed peas. The dietary manager and registered dietitian were informed of the missing pureed vegetables, and photographic evidence was obtained. The facility also failed to provide ordered Magic Cup nutritional supplements as prescribed. One resident with severe cognitive impairment and a care plan addressing risk for compromised nutritional status had a physician’s order for a 4 oz Magic Cup on day and evening shifts with lunch and dinner; during a breakfast observation, the meal ticket listed Magic Cup, but none was provided. Another resident with moderate cognitive impairment had a physician’s order for a 4 oz Magic Cup with lunch; during lunch observation, the meal ticket indicated Magic Cup, but the resident was served chocolate ice cream and ate coconut cream pie for dessert instead. The MAR documented 100% consumption of a Magic Cup on two consecutive days, despite the observed failure to provide it. During interviews, the RD and dietary manager explained that Magic Cups were to be provided by dietary staff either on trays or via the dessert/ice cream cart, but they could not explain why residents in the dining room did not receive the ordered supplements. Photographic evidence was obtained of these occurrences.
Plan Of Correction
Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required F0803 1. Upon identification, resident #54 was given pureed vegetables. Residents #23, #39, and #54 were given Magic Cup supplements as ordered. On [R] CDM re-educated team members on supplement delivery including proper documentation and confirming that pureed diet being served matches what is listed on spread sheet. Dietary aides' morning and evening shifts are accountable for serving all food groups including vegetables when serving puree meals to residents. 2. A 100% audit of all residents with therapeutic diets and/or supplements was completed on [R] by Certified Dietary Manager. 3. A tray line checklist and diet/supplement reconciliation process between dietary and nursing were implemented by [R]. RD oversight of menu compliance was initiated. The Certified Dietary Manager or designee will audit food tray weekly x 4 weeks then weekly x 2 months. 4. The Certified Dietary Manager/Designee will report on the findings at the monthly QAPI meeting. The Administrator is responsible for confirming implementation and compliance with this POC and [R], and resolving any variances that may occur.
Failure to Verify and Honor DNR Order Before Initiating CPR
Penalty
Summary
The deficiency involves the facility’s failure to honor a resident’s clearly established Do Not Resuscitate (DNR) status during a cardiac emergency. The resident had multiple medical diagnoses, including cerebral infarction, COPD, cardiomyopathy, atherosclerotic heart disease, a nonrheumatic mitral valve disorder, cognitive communication deficit, and immunodeficiency. The medical record contained DNR orders created on two separate dates with no end dates, a DNR document signed by the resident and a nurse practitioner, and a 3008 form listing the resident’s advance directive as DNR. The resident’s MDS showed a Brief Interview for Mental Status score of 15, indicating intact cognition, and progress notes documented that the difference between DNR/no CPR and full code had been explained over 30 minutes, after which the resident chose DNR and reiterated to social services that she did not want to be resuscitated or undergo chest compressions. On the day of the incident, a CNA assigned to the resident checked on her and found her sitting in a wheelchair and unresponsive despite multiple verbal attempts to rouse her. The CNA notified the RN, who obtained a blood pressure machine, entered the room, then ran out to the nurses’ station, after which a code blue was paged over the intercom. The RN returned with a crash cart, and additional nursing staff, including RNs and LPNs, entered the room. Staff described transferring the unresponsive resident from the wheelchair to the bed and beginning chest compressions. Multiple staff members reported that when one LPN asked about the resident’s code status, no one in the room knew it at that time, and that this LPN left the room to verify the code status while CPR was already in progress. Interviews and video review confirmed that CPR was initiated and continued for approximately 12 minutes before EMS arrived, despite the resident’s existing DNR orders. Several nurses, including those who arrived after CPR had started, acknowledged that they did not check the resident’s code status before assisting with chest compressions or using a bag-valve mask. Staff later reported that the LPN who checked the record returned and announced that the resident was a DNR, yet compressions continued until EMS arrived. The physician stated that the resident was already in the system as a DNR and that staff were expected to check code status before performing CPR. The DON and regional nurse consultant confirmed, based on interviews and camera review, that staff failed to confirm the resident’s code status prior to initiating CPR and that CPR was performed against the resident’s wishes, leading surveyors to determine that this failure resulted in Immediate Jeopardy.
Removal Plan
- Implemented a revised admission/readmission process requiring an Advance Directive discussion form to be completed by the licensed nurse upon admission or with change in advance directives, with follow-up by Social Services.
- Reviewed Advance Directive discussion forms in the daily clinical meeting with the Interdisciplinary Team.
- Conducted a huddle on units after the clinical meeting to discuss any changes in advance directives/code status.
- Placed signage on each crash cart stating: "Stop check physician order prior to starting Cardiopulmonary Resuscitation."
- Implemented the "It Takes Two" process requiring two licensed nurses to verify code status/advance directives prior to initiation of CPR.
- Initiated an internal investigation including resident record review, staff interviews, and notification to the physician and resident representative.
- Suspended and terminated the assigned nurse and reported the nurse’s license to the licensing board.
- Suspended and terminated an additional nurse who responded and participated in initiation of CPR and reported the nurse’s license to the licensing board.
- Suspended two additional nurses pending investigation and returned them to work with disciplinary action, education on ANE/honoring advance directives, and participation in a code blue drill.
- Conducted a 100% audit of all current residents’ code status and care plans.
- Conducted a 100% audit of crash carts to ensure all required items were present.
- Reviewed CPR cards for identified nurses to confirm validity and inclusion of in-person skills competencies.
- Held an ad hoc QAPI meeting with Administrator, DON, Medical Director, and department heads.
- Completed an audit of residents discharged, transferred to the hospital, or expired to verify advance directives were honored.
- Provided staff education for licensed/certified staff on medical emergency response and communication of advance directives and code status, following physician orders related to advance directives, the "It Takes Two" verification process, and CNA roles during code blue.
- Provided all-staff education on Abuse, Neglect and Exploitation/Resident Rights with focus on honoring advance directives.
- Completed honoring advance directives attestation with licensed nursing staff.
- Completed physician orders education for licensed nursing staff.
- Completed medical emergency response and communication of code status education for licensed nursing staff.
- Completed ANE/Resident Rights education for all staff.
- Completed advance directives posttest for licensed staff.
- Completed ANE/Resident Rights posttest for all staff.
- Completed code blue process/"It Takes Two" education for licensed nursing staff.
- Began code blue drills every shift and required licensed nurses to attend a mock code blue quality assurance drill prior to working.
- Completed CNA roles-in-code-blue training.
- Completed quality reviews validating staff competencies for completed education.
- Completed quality reviews of newly admitted residents to verify completion of the advance directive discussion form.
- Implemented Director of Clinical Services chart review of residents who expire at the facility or are transferred to the hospital after a cardiac event to verify advance directives were followed.