Improper Use of Power Strip as Permanent Power Source in Electrical Room
Penalty
Summary
Surveyors identified a deficiency related to improper use of relocatable power taps (RPTs) and power strips in violation of NFPA 99, NFPA 70, and NFPA 1 requirements. During a facility tour conducted between 10:00 a.m. and 12:00 p.m. with the Maintenance Director, surveyors observed one power strip in the electrical room being used as a source of permanent power instead of being connected to a dedicated receptacle. The report notes that this use did not comply with standards that require extension cords and power strips not be used as a substitute for fixed wiring and that they be used only under specified conditions. The deficiency specifically concerns the facility’s failure to ensure that RPTs are maintained and used in accordance with NFPA 99 (2012 Edition) sections 10.2.3.6 and 10.2.4, and NFPA 70 (2011 and 2020 Editions) provisions governing flexible cords and temporary wiring, as well as NFPA 1 (2021 Edition) sections 11.1.2.2, 11.1.4.1, and 1.4.1. The report states that this condition could lead to electric hazards for residents and staff. No individual resident cases, medical histories, or specific clinical conditions are described in connection with this deficiency.
Plan Of Correction
What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice? No residents were affected by this deficient practice. How you will identify other residents having potential to be affected by the same practice and what corrective actions will be taken; Facility wide audit of electrical rooms was conducted to identify improper use of power strips. No additional concerns were identified. What measures will be put into place or what systematic changes you will make to ensure that the practice does not recur; The facility completed education reinforcing compliance with electrical safety requirements in accordance with National Fire Protection Association. How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put in place: The maintenance director/designee will complete random electrical safety audits 2 times per week for 4 weeks, then monthly to ensure compliance with electrical safety standards. The findings will be reported to the Quality Assurance Performance Improvement Committee for ongoing compliance. What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice? No residents were affected by this deficient practice. How you will identify other residents having potential to be affected by the same practice and what corrective actions will be taken; Facility wide audit of electrical rooms was conducted to identify improper use of power strips. No additional concerns were identified. What measures will be put into place or what systematic changes you will make to ensure that the practice does not recur; The facility completed education reinforcing compliance with electrical safety requirements in accordance with National Fire Protection Association. How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put in place; The maintenance director/designee will complete random electrical safety audits 2 times per week for 4 weeks, then monthly to ensure compliance with electrical safety standards. The findings will be reported to the Quality Assurance Performance Improvement Committee for ongoing compliance.