K0920 K920: Ensure proper usage of power strips and extension cords.
C

Improper Use of Power Strip as Permanent Power Source in Electrical Room

Vero Beach Care CenterVero Beach, Florida Survey Completed on 05-08-2026

Summary

Surveyors identified a deficiency related to improper use of relocatable power taps (RPTs) and power strips in violation of NFPA 99, NFPA 70, and NFPA 1 requirements. During a facility tour conducted between 10:00 a.m. and 12:00 p.m. with the Maintenance Director, surveyors observed one power strip in the electrical room being used as a source of permanent power instead of being connected to a dedicated receptacle. The report notes that this use did not comply with standards that require extension cords and power strips not be used as a substitute for fixed wiring and that they be used only under specified conditions. The deficiency specifically concerns the facility’s failure to ensure that RPTs are maintained and used in accordance with NFPA 99 (2012 Edition) sections 10.2.3.6 and 10.2.4, and NFPA 70 (2011 and 2020 Editions) provisions governing flexible cords and temporary wiring, as well as NFPA 1 (2021 Edition) sections 11.1.2.2, 11.1.4.1, and 1.4.1. The report states that this condition could lead to electric hazards for residents and staff. No individual resident cases, medical histories, or specific clinical conditions are described in connection with this deficiency.

Plan Of Correction

What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice? No residents were affected by this deficient practice. How you will identify other residents having potential to be affected by the same practice and what corrective actions will be taken; Facility wide audit of electrical rooms was conducted to identify improper use of power strips. No additional concerns were identified. What measures will be put into place or what systematic changes you will make to ensure that the practice does not recur; The facility completed education reinforcing compliance with electrical safety requirements in accordance with National Fire Protection Association. How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put in place: The maintenance director/designee will complete random electrical safety audits 2 times per week for 4 weeks, then monthly to ensure compliance with electrical safety standards. The findings will be reported to the Quality Assurance Performance Improvement Committee for ongoing compliance. What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice? No residents were affected by this deficient practice. How you will identify other residents having potential to be affected by the same practice and what corrective actions will be taken; Facility wide audit of electrical rooms was conducted to identify improper use of power strips. No additional concerns were identified. What measures will be put into place or what systematic changes you will make to ensure that the practice does not recur; The facility completed education reinforcing compliance with electrical safety requirements in accordance with National Fire Protection Association. How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put in place; The maintenance director/designee will complete random electrical safety audits 2 times per week for 4 weeks, then monthly to ensure compliance with electrical safety standards. The findings will be reported to the Quality Assurance Performance Improvement Committee for ongoing compliance.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0920 citations
Improper Use of Power Strips and Extension Cords in Multiple Facility Areas
E
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found multiple instances of improper use of relocatable power taps (RPTs) and extension cords during a facility tour with the Maintenance Director. In the social services office, an RPT was plugged into another RPT connected to a wall outlet, with the cord running across a walkway and taped to the floor. In the multipurpose room, a television was plugged into an extension cord, and in the MDS office, an RPT was plugged into another RPT with an outlet adapter in use. These conditions did not comply with NFPA 101, NFPA 99, and NFPA 70 standards governing electrical equipment, power strips, and extension cords.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Adapters and Power Strips for Refrigerators
F
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors observed that an adapter was used to power a refrigerator in the kitchen and a refrigerator in the dining room manager's office was plugged into a power strip. The Director of Facilities confirmed both uses, which did not comply with NFPA 99 and NFPA 70 requirements prohibiting adapters and power strips from being used as substitutes for permanent wiring.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Outlet Multiplier in Salon
D
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

A three-to-one outlet multiplier was found in use in the first floor salon, with a hair dryer, hair straightener, and hair curler plugged into it, in violation of electrical equipment requirements. The maintenance director confirmed this setup during an interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unapproved Power Strip Causes Electrical Fire at Bedside
F
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

A power strip not meeting required UL standards was found in use at a bedside, resulting in an electrical fire. The device had been brought in by a family member for charging a phone, and the facility could not verify its compliance with safety standards. This deficiency affected multiple residents and a smoke compartment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Extension Cords and Power Strips for Window AC Units
F
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found that multiple window AC units throughout the facility were retrofitted by removing factory GFCI power cords and attaching extension cords, eliminating original electrical protections. One AC unit in the Dietary Director's office was also plugged into a power strip, contrary to regulations. Facility leadership confirmed these modifications, which violated electrical safety standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unauthorized Use of Extension Cords and Surge Protectors
E
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found that extension cords and surge protectors were being used in multiple rooms to power phone chargers and medical devices, in violation of NFPA 101 and related standards. Facility leadership confirmed these unauthorized devices were in use during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Florida

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Florida — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report