K0920 K920: Ensure proper usage of power strips and extension cords.
E

Improper Use of Power Strips and Extension Cords in Multiple Facility Areas

Ambassador Healthcare At College ParkFort Myers, Florida Survey Completed on 05-19-2026

Summary

Surveyors identified deficiencies related to the use and maintenance of relocatable power taps (RPTs) and extension cords that did not comply with NFPA 101, NFPA 99, and NFPA 70 requirements. During a facility tour conducted between 11:00 a.m. and 3:30 p.m. with the Maintenance Director, surveyors observed in the social services office an RPT plugged into another RPT, which was then plugged into a wall outlet, with the cord running across a walkway and taped to the floor. In the multipurpose room, a television was found plugged into an extension cord, contrary to standards that prohibit using extension cords as a substitute for fixed wiring and require temporary extensions to be removed immediately after use. Further observations included the MDS office, where an RPT was plugged into another RPT and an outlet adapter was in use. These configurations did not meet the NFPA 99 provisions governing the proper use of power strips and extension cords, including requirements that power strips be appropriately rated and used only as intended, and that extension cords not be used as permanent wiring. During concurrent interviews, the Maintenance Director acknowledged these findings as they were observed by the surveyors.

Plan Of Correction

The RPT observed plugged into an RPT plugged into an outlet in the Social Services Office was removed. The extension cord used to plug in the television in the multipurpose room was removed. The RPT plugged into an RPT and outlet adapter in the MDS office was removed. Additional offices and resident care areas will be reviewed for the improper use of plug adapters, power strips and extension. The Executive Director/designee will educate the Maintenance Director on the importance of NFPA 101 Electrical Equipment- Power and Extension specific to the improper use of plug adapters, power strips, and extension and will continue to monitor in accordance with NFPA standards. Any findings will be reported to the monthly QAPI Committee for further review. The RPT observed plugged into an RPT plugged into an outlet in the Social Services Office was removed. The extension cord used to plug in the television in the multipurpose room was removed. The RPT plugged into an RPT and outlet adapter in the MDS office was removed. Additional offices and resident care areas will be reviewed for the improper use of plug adapters, power strips and extension. The Executive Director/designee will educate the Maintenance Director on the importance of NFPA 101 Electrical Equipment - Power and Extension specific to the improper use of plug adapters, power strips, and extension and will continue to monitor in accordance with NFPA standards. Any findings will be reported to the monthly QAPI Committee for further review.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0920 citations
Improper Use of Power Strip as Permanent Power Source in Electrical Room
C
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found that the facility failed to comply with NFPA 99, NFPA 70, and NFPA 1 requirements for electrical equipment when, during a tour with the Maintenance Director, a power strip in the electrical room was observed being used as a permanent power source instead of a dedicated receptacle. The report states that this improper use of a relocatable power tap could lead to electrical hazards for residents and staff, and notes that extension cords and power strips are not to be used as substitutes for fixed wiring under the cited codes.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Adapters and Power Strips for Refrigerators
F
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors observed that an adapter was used to power a refrigerator in the kitchen and a refrigerator in the dining room manager's office was plugged into a power strip. The Director of Facilities confirmed both uses, which did not comply with NFPA 99 and NFPA 70 requirements prohibiting adapters and power strips from being used as substitutes for permanent wiring.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Outlet Multiplier in Salon
D
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

A three-to-one outlet multiplier was found in use in the first floor salon, with a hair dryer, hair straightener, and hair curler plugged into it, in violation of electrical equipment requirements. The maintenance director confirmed this setup during an interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unapproved Power Strip Causes Electrical Fire at Bedside
F
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

A power strip not meeting required UL standards was found in use at a bedside, resulting in an electrical fire. The device had been brought in by a family member for charging a phone, and the facility could not verify its compliance with safety standards. This deficiency affected multiple residents and a smoke compartment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Extension Cords and Power Strips for Window AC Units
F
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found that multiple window AC units throughout the facility were retrofitted by removing factory GFCI power cords and attaching extension cords, eliminating original electrical protections. One AC unit in the Dietary Director's office was also plugged into a power strip, contrary to regulations. Facility leadership confirmed these modifications, which violated electrical safety standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unauthorized Use of Extension Cords and Surge Protectors
E
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found that extension cords and surge protectors were being used in multiple rooms to power phone chargers and medical devices, in violation of NFPA 101 and related standards. Facility leadership confirmed these unauthorized devices were in use during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

65.1% of Ohio facilities received at least one citation during their inspection in the last 12 months.Will yours be survey-ready?

Surveyors issued 55 serious citations across Ohio in the last 12 months. See exactly what they're citing.

Get ready for your next survey

See what surveyors are citing in Ohio and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release May 27, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙