K0351 K351: Install an approved automatic sprinkler system.
D

Improper Sprinkler Installation in Loading Dock Corridor

New Gouverneur Hospital S N FNew York, New York Survey Completed on 12-31-2024

Summary

During a Life Safety Recertification Survey conducted on two consecutive days, it was observed that the facility did not comply with the 2010 NFPA 13 standards for sprinkler installation. Specifically, in the corridor leading to the secondary access of the Loading Dock, pendent-style sprinkler heads were installed approximately 56 inches below the ceiling, which exceeds the maximum allowable distance of 12 inches. This installation was at the same level as the lighting fixture. The Director of Maintenance acknowledged that the ceiling had been removed and stated it would be replaced, indicating a temporary alteration that led to the deficiency.

Plan Of Correction

Plan of Correction: Approved February 3, 2025 K 351 Sprinkler System - Installation 1. What Corrective Action(s) will be accomplished for those residents found to have been affected by the deficient practice: The ceiling, in the corridor of the secondary access to the loading dock, was reinstalled where the sprinkler heads were found to be greater than 12 in. from the ceiling. The ceiling in the corridor of the secondary access to the Loading Dock was reinstalled to its original position. The pendent-style sprinkler heads were adjusted to ensure the installation is in accordance with 2010 NFPA 13. 2. How will you identify other residents having the potential to be affected by the same deficient practice and what corrective action will be taken: The Director of Maintenance or Designee will conduct a thorough inspection of all sprinkler heads to confirm that installation is not greater than 12 in. from the ceiling. 3. What measures will be put in place or what systemic changes you will make to ensure that the deficient practice does not recur: The Fire Safety Team and the Maintenance team were in-serviced on NFPA Standard for the installation of Sprinkler Systems and highlighted their role in ensuring that pendant style sprinkler heads are not greater than 12 in. from the ceiling in accordance with NFPA 13. The Fire Safety Staff and Maintenance Staff will conduct weekly rounds confirming that Sprinkler Heads are not greater than 12 in from the ceiling. The Maintenance Staff will address any sprinkler heads that are not compliant with the standard. Regular maintenance checks will be conducted to ensure that all sprinkler heads are installed and maintained in accordance with 2010 NFPA 13. 4. How the Corrective Action(s) will be monitored to ensure the deficient practice will not recur, i.e., what quality assurance program will be put into practice: The Director of Maintenance/Designee will review 10% of all sprinkler heads to confirm that they are installed no greater than 12 in from the ceiling for a period of 3 months or until improvement is sustained that all sprinkler heads are no more than 12 in from the ceiling. The results from the monitoring will be reported to the QAPI Committee. 5. Responsible Individual: Director of Maintenance

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0351 citations
Incomplete Sprinkler Coverage for Built-In Dining Room Cabinetry
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that floor-to-ceiling built-in millwork cabinetry with doors in the first floor dining room was installed and in use without interior sprinkler coverage or other required fire protection measures, and this cabinetry was not shown on the approved DOH renovation and sprinkler plans, preventing verification of proper sprinkler coverage; on revisit, the same lack of fire protection within the closed-door storage cabinetry remained uncorrected, as confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiency in Sprinkler System Installation
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A deficiency was cited due to the facility not being fully protected by an approved automatic sprinkler system as required by the 2012 standards for existing nursing homes and hospitals.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Obstructions and Missing Ceiling Tiles
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that shower curtains in multiple resident rooms were within 18 inches of sprinkler heads, violating NFPA 13 requirements, and also noted missing ceiling tiles in two utility areas. These issues were confirmed by the Facilities Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Sprinkler Pipe for Mechanical Support
E
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A hot water pipe was observed being supported and hanging from a sprinkler pipe in the 300 wing mechanical room, contrary to NFPA 13 requirements for sprinkler system installation. This was confirmed by the Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler System Installation in Electrical Room
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

The facility failed to install an automatic sprinkler system in the Main electrical (switchgear) Room in the basement, affecting one of three levels. This deficiency was confirmed during an exit interview with the Administrator, Maintenance Director, and Regional VP of Operations, indicating incomplete sprinkler protection as per NFPA standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Deficiency in Elevator Pit
E
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

The facility failed to maintain sprinkler system requirements as the hydraulic elevator pit lacked a sidewall sprinkler installed within two feet of the floor. This deficiency was confirmed by the maintenance director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across New York

Get a heads-up on the newest immediate-jeopardy (J–L) citations in New York — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙