K0351 K351: Install an approved automatic sprinkler system.
F

Deficiency in Sprinkler System Installation

Hampton Nursing And RehabilitationBay City, Michigan Survey Completed on 06-24-2025

Summary

A deficiency was identified regarding the installation of the sprinkler system. The report notes that nursing homes and hospitals, where required by construction type, must be protected throughout by an approved automatic sprinkler system. The facility did not meet this requirement, as the necessary sprinkler system installation was not in place as specified by the 2012 standards for existing buildings.

Plan Of Correction

Element 1: No residents were identified in this concern. The light fixture in the lobby was moved to accommodate the required distance from the sprinkler head. Completed by 7/24/2025

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0351 citations
Incomplete Sprinkler Coverage for Built-In Dining Room Cabinetry
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that floor-to-ceiling built-in millwork cabinetry with doors in the first floor dining room was installed and in use without interior sprinkler coverage or other required fire protection measures, and this cabinetry was not shown on the approved DOH renovation and sprinkler plans, preventing verification of proper sprinkler coverage; on revisit, the same lack of fire protection within the closed-door storage cabinetry remained uncorrected, as confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Obstructions and Missing Ceiling Tiles
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that shower curtains in multiple resident rooms were within 18 inches of sprinkler heads, violating NFPA 13 requirements, and also noted missing ceiling tiles in two utility areas. These issues were confirmed by the Facilities Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Sprinkler Pipe for Mechanical Support
E
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A hot water pipe was observed being supported and hanging from a sprinkler pipe in the 300 wing mechanical room, contrary to NFPA 13 requirements for sprinkler system installation. This was confirmed by the Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler System Installation in Electrical Room
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

The facility failed to install an automatic sprinkler system in the Main electrical (switchgear) Room in the basement, affecting one of three levels. This deficiency was confirmed during an exit interview with the Administrator, Maintenance Director, and Regional VP of Operations, indicating incomplete sprinkler protection as per NFPA standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Deficiency in Elevator Pit
E
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

The facility failed to maintain sprinkler system requirements as the hydraulic elevator pit lacked a sidewall sprinkler installed within two feet of the floor. This deficiency was confirmed by the maintenance director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Attic Sprinkler System Not Installed per NFPA 13
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A review of facility records revealed that the dry sprinkler system in the attic had been capped off, leaving the attic without full sprinkler protection as required by NFPA 13. This was confirmed by the Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Michigan

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Michigan — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙