K0351 K351: Install an approved automatic sprinkler system.
D

Sprinkler System Installation Deficiency

Transitions Healthcare Washington PaWashington, Pennsylvania Survey Completed on 03-19-2025

Summary

The facility failed to maintain automatic sprinkler system installation requirements as evidenced by the presence of mixed standard response and quick response sprinkler heads in the basement hallway. This deficiency was identified during an observation conducted on March 19, 2025, between 10:35 a.m. and 10:55 a.m. The issue was confirmed through an interview with the Facility Administrator, Maintenance Personnel, and the Plant Operations Director on the same day at 12:30 p.m.

Plan Of Correction

1. Sprinkler heads were converted so that all sprinkler heads were standardized to the quick response sprinkler head. 2. No other variant sprinkler heads were identified within the facility. 3. The Director of Plant operations or designee will audit sprinkler heads to ensure that they are all the quick response sprinkler heads monthly x 3 months. 4. Audits will be taken to the safety committee and submitted to the QAPI committee for review of findings and further interventions are warranted.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0351 citations
Incomplete Sprinkler Coverage for Built-In Dining Room Cabinetry
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that floor-to-ceiling built-in millwork cabinetry with doors in the first floor dining room was installed and in use without interior sprinkler coverage or other required fire protection measures, and this cabinetry was not shown on the approved DOH renovation and sprinkler plans, preventing verification of proper sprinkler coverage; on revisit, the same lack of fire protection within the closed-door storage cabinetry remained uncorrected, as confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiency in Sprinkler System Installation
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A deficiency was cited due to the facility not being fully protected by an approved automatic sprinkler system as required by the 2012 standards for existing nursing homes and hospitals.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Obstructions and Missing Ceiling Tiles
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that shower curtains in multiple resident rooms were within 18 inches of sprinkler heads, violating NFPA 13 requirements, and also noted missing ceiling tiles in two utility areas. These issues were confirmed by the Facilities Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Sprinkler Pipe for Mechanical Support
E
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A hot water pipe was observed being supported and hanging from a sprinkler pipe in the 300 wing mechanical room, contrary to NFPA 13 requirements for sprinkler system installation. This was confirmed by the Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler System Installation in Electrical Room
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

The facility failed to install an automatic sprinkler system in the Main electrical (switchgear) Room in the basement, affecting one of three levels. This deficiency was confirmed during an exit interview with the Administrator, Maintenance Director, and Regional VP of Operations, indicating incomplete sprinkler protection as per NFPA standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Deficiency in Elevator Pit
E
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

The facility failed to maintain sprinkler system requirements as the hydraulic elevator pit lacked a sidewall sprinkler installed within two feet of the floor. This deficiency was confirmed by the maintenance director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙