K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
E

Improper Repair of Smoke Barrier Penetrations in Multiple Smoke Compartments

Park Meadows Healthcare & Rehabilitation CenterGainesville, Florida Survey Completed on 06-02-2026

Summary

Surveyors identified a deficiency in the facility’s maintenance of smoke/fire-rated enclosures, specifically related to penetrations in smoke barriers in multiple smoke compartments. During an interview, the Maintenance Director reported that insulation was used to pack holes and then covered with fiberglass in general storage rooms in smoke compartments 1, 2, and 3, but was unable to confirm whether these materials were approved for use in fire-rated walls. Subsequent observation showed that the penetrations were indeed covered with fiberglass, and one general storage room in smoke compartment 2 had a hole in one of the fiberglass panels. The report states that this failure to properly maintain penetrations through smoke/fire-rated construction could allow smoke and flammable gases to spread to other areas and cause the smoke/fire-rated construction to fail to perform as designed.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0372 citations in Ohio
Unsealed Wire Penetrations in Smoke Barrier
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that two wires passed unsealed through a smoke barrier above the ceiling near a resident corridor, with the Maintenance Director confirming unawareness of the sealing requirement. This deficiency had the potential to affect five residents and did not comply with NFPA 101-2012 standards for smoke barrier construction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Smoke Barrier Integrity per NFPA 101
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found multiple penetrations in smoke barriers sealed with non-fire-rated materials and one unsealed pipe, compromising the required fire and smoke resistance in several corridors and the attic. Maintenance leadership confirmed uncertainty about the materials used, and these deficiencies had the potential to affect all 39 residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

65.1% of Ohio facilities received at least one citation during their inspection in the last 12 months.Will yours be survey-ready?

Surveyors issued 55 serious citations across Ohio in the last 12 months. See exactly what they're citing.

Get ready for your next survey

See what surveyors are citing in Ohio and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release May 27, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙