F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
E

Non-Operational Bathroom Ventilation Systems

Emerald Nursing & Rehab LakeviewGrand Island, Nebraska Survey Completed on 01-29-2026

Summary

The facility failed to ensure the ventilation system was in working order in 12 resident bathrooms in rooms 501, 502, 503, 504, 505, 506, 508, 510, 511, 512, 513, and 514 out of 24 sampled resident rooms. During an observation with the Facility Administrator, Maintenance Supervisor, and Housekeeping Supervisor, the bathroom ventilation system in room 500-hall did not pull when a 1-ply tissue was pressed against it, confirming the vent was non-operational, and staff confirmed there was no window in the bathroom. The Maintenance Supervisor stated that no one checks the ventilation system and that it is not part of the maintenance program, and also said he was unaware the system was not working and that no one had alerted him. The Facility Administrator also stated being unaware that the ventilation system was not working, and did not deny that the listed bathrooms were not operational. The Regional Director of Operation stated the facility did not have a policy on ventilation monitoring.

Penalty

Inspection fine: $13,42615 days payment denial
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0923 citations
Bathroom Exhaust Ventilation Not Functioning
E
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Bathroom exhaust vents were not functioning in multiple resident rooms on the 100 and 200 halls, with surveyors observing no air movement at the ceiling vents in both occupied and unoccupied bathrooms. An MTC confirmed the ventilation problem and stated the vents were usually checked weekly, but there was no documentation to verify those checks.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Inadequate Ventilation in Resident Rooms and Hallways
E
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Inadequate ventilation was identified throughout the facility when surveyors observed resident room windows on multiple floors screwed shut and unable to open, with no screens present. Hallway HVAC was present but not functioning in some areas, and only some resident rooms had AC units. Staff stated the building was not fully equipped with AC, that the windows were kept shut due to security concerns, and that repair recommendations for non-functioning AC units had been pending corporate approval.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Airflow in Soiled Laundry Rooms
D
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Improper Airflow in Soiled Laundry Rooms: During the annual survey, a strong odor was noted in the soiled laundry rooms because the mechanically operated ventilation systems serving the two soiled laundry rooms did not have negative pressure airflow. On a follow-up tour, a window in one soiled laundry room was open to provide air circulation, and the Maintenance Director stated the roof exhaust fans would be reassessed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Inadequate Ventilation Above Dish Machine Caused Ceiling Damage
F
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Inadequate ventilation above the dish machine allowed steam to rise and hit the ceiling tiles over the dishwashing area. Staff observed bowed, peeling ceiling tiles, exposed yellow foam insulation, and a disrepair area around the ventilation duct, and the Maintenance Director stated the damage was caused by steam from the dish machine and had required repeated tile repairs.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Nonworking Bathroom Ventilation in 10 Resident Rooms
E
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Nonworking Bathroom Ventilation in 10 Resident Rooms: Surveyors observed that the bathroom vents in 10 resident rooms did not function when tested with toilet paper. Maintenance staff later confirmed the vents were not working and was unaware of the problem, and could not provide bathroom vent check logs. Record review showed the facility policy required ventilation system audits to be maintained.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Nonfunctional Bathroom Ventilation in Multiple Resident Rooms
F
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Bathroom ventilation was not functioning in eight sampled resident rooms, including rooms 102, 105, 107, 114, 119, 121, 204, and 206. Surveyors verified the issue with a one-ply tissue during screening and the environmental tour, and the FM confirmed the problem. The facility also lacked an HVAC policy and a preventative maintenance program, and its HVAC checklist only addressed filter checks.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Nebraska

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Nebraska — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release August 26, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.