F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
E

Inadequate Ventilation in Resident Rooms and Hallways

Trinity Hill Care CenterHartford, Connecticut Survey Completed on 06-03-2026

Summary

The facility failed to ensure adequate ventilation by opened windows, mechanical ventilation, or a combination of the two throughout the building. Survey observations on multiple days found that all resident room windows on the 1st, 2nd, and 3rd floors had screws in them that prevented them from being opened, and there were no screens in the resident room windows. Internal temperatures on one observation day ranged from 77 degrees to 81 degrees while the outside temperature reached 85 degrees. The building had HVAC ventilation in the hallways, but not in resident rooms, and only some resident rooms had air conditioners. The vents on the 2nd floor hallway serving Rooms 201 through 215 were not blowing air, and a window air conditioner at the end of the hallway was in use. Interviews confirmed that the resident room windows were intentionally kept from opening. An LPN stated the windows had been screwed shut after someone may have tried to jump out of one, and that the 2nd floor gets hot, with fans provided if residents complain. The Director of Maintenance stated the building was not fully equipped with air conditioning, that only some rooms had AC because the electrical load could not handle units in every room, and that management directed him to keep the windows from opening because of concerns about people jumping the back fence and selling drugs at the windows. He also stated he had been told by BFSI to remove the screws, but his supervisor and corporate person told him the screws were to remain. He further identified two non-functional hallway AC units and said repairs had been delayed because all work required corporate approval. A mechanical service representative stated the facility had received repair recommendations for the non-functioning AC units since 4/9/26 and had not approved the repairs to date.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0923 citations
Bathroom Exhaust Ventilation Not Functioning
E
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Bathroom exhaust vents were not functioning in multiple resident rooms on the 100 and 200 halls, with surveyors observing no air movement at the ceiling vents in both occupied and unoccupied bathrooms. An MTC confirmed the ventilation problem and stated the vents were usually checked weekly, but there was no documentation to verify those checks.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Airflow in Soiled Laundry Rooms
D
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Improper Airflow in Soiled Laundry Rooms: During the annual survey, a strong odor was noted in the soiled laundry rooms because the mechanically operated ventilation systems serving the two soiled laundry rooms did not have negative pressure airflow. On a follow-up tour, a window in one soiled laundry room was open to provide air circulation, and the Maintenance Director stated the roof exhaust fans would be reassessed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Inadequate Ventilation Above Dish Machine Caused Ceiling Damage
F
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Inadequate ventilation above the dish machine allowed steam to rise and hit the ceiling tiles over the dishwashing area. Staff observed bowed, peeling ceiling tiles, exposed yellow foam insulation, and a disrepair area around the ventilation duct, and the Maintenance Director stated the damage was caused by steam from the dish machine and had required repeated tile repairs.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Nonworking Bathroom Ventilation in 10 Resident Rooms
E
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Nonworking Bathroom Ventilation in 10 Resident Rooms: Surveyors observed that the bathroom vents in 10 resident rooms did not function when tested with toilet paper. Maintenance staff later confirmed the vents were not working and was unaware of the problem, and could not provide bathroom vent check logs. Record review showed the facility policy required ventilation system audits to be maintained.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Nonfunctional Bathroom Ventilation in Multiple Resident Rooms
F
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Bathroom ventilation was not functioning in eight sampled resident rooms, including rooms 102, 105, 107, 114, 119, 121, 204, and 206. Surveyors verified the issue with a one-ply tissue during screening and the environmental tour, and the FM confirmed the problem. The facility also lacked an HVAC policy and a preventative maintenance program, and its HVAC checklist only addressed filter checks.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Functional Mechanical Ventilation in Soiled Utility Room and Resident Bathrooms
E
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Surveyors found that mechanical ventilation in a soiled utility room and in resident bathrooms on two halls was not functioning. A strong, pungent odor was present in the soiled utility room, and testing of the ceiling vents with tissue paper showed no suction. The maintenance supervisor confirmed the vents were non-functional and reported that a single unit controlled ventilation for the soiled utility room and both halls’ bathrooms, suggesting a possible belt issue. This failure had the potential to affect all residents on those halls.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Connecticut

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Connecticut — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release August 26, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.