K0341 K341: Install a fire alarm system that can be heard throughout the facility.
F

Improper Installation and Obstruction of Fire Alarm System Components

Pinnacle Care Of Battle CreekBattle Creek, Michigan Survey Completed on 05-08-2025

Summary

The facility failed to ensure that the fire alarm system was installed and maintained in accordance with NFPA 70 and NFPA 72 standards. During an observation, it was found that the smoke detector head at the North Smoke Doors exit into the administration hall was not properly mounted to the ceiling. Additionally, another smoke detector head located in the North Mechanical closet was discovered with a plastic bag taped over it. These deficiencies were confirmed through interviews with the Facility Maintenance Director at the time of the observations. No information regarding specific residents, their medical history, or their condition at the time of the deficiency was provided in the report.

Plan Of Correction

K3411. The Maintenance Director and/or designee will repair the smoke detector heads at the North smoke doors and North mechanical closet. The Administrator will review regulation K341 and provide education to the Maintenance team on the requirements. The Maintenance Director and/or designee will conduct a weekly community audit of smoke detectors to ensure appropriate function. Results of the audits will be brought to the Quality Assurance Performance Improvement meeting monthly for review. The Committee will be responsible for any changes to the auditing process. The Administrator is responsible to attain and maintain compliance. Completion date for compliance will be 06.20.25.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0341 citations
Fire Alarm System Altered Without Required Plan Approval or Inspection
E
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

The facility installed carbon monoxide detectors on its fire alarm system and placed the system into service without obtaining prior plan approval or completing an occupancy inspection, as confirmed by interviews with the DON and Director of Maintenance. No documentation of approval or completion was provided.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Smoke Detector Protection in Open Dining Room
E
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

The 1st floor Dining Room had its doors removed, leaving the room open to the corridor without any smoke detector protection. This was confirmed by the Director of Facilities, resulting in a failure to provide required fire alarm protection in that smoke compartment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Smoke Detector Placement Near Airflow Source
E
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

A smoke detector was found installed within three feet of direct airflow from an air return or supply near an exit door, contrary to NFPA 70 and NFPA 72 requirements. This installation issue was confirmed by Facility Maintenance and could impact 30 occupants during a fire emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Installation of Fire Alarm Initiating Devices
E
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

The facility did not properly install fire alarm initiating devices, affecting one level of the building. The manual pull station for the double exit doors in the Kitchen on the first floor was not mounted within 5 feet of the exit doors, as observed and confirmed during an interview with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Installation of Fire Detection Devices
F
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

The facility failed to maintain smoke and heat detectors according to NFPA standards, as observed in the elevator equipment room where the devices were hanging from wires and not securely attached. This issue had the potential to affect 120 residents, and the responsible individual was unaware of the deficiency.

Inspection fine: $25,635
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Michigan

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Michigan — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙