K0341 K341: Install a fire alarm system that can be heard throughout the facility.
E

Lack of Smoke Detector Protection in Open Dining Room

Concordia At Spiritrust GettysburgGettysburg, Pennsylvania Survey Completed on 06-25-2025

Summary

Surveyors observed that the 1st floor Dining Room had its doors (1C10 and 1C11) removed, resulting in the room being open to the corridor. Despite this change, there was no smoke detector protection installed in the area. This deficiency was confirmed during an interview with the Director of Facilities, who acknowledged the absence of smoke detection in the room. The lack of smoke detector protection in a room open to the corridor constitutes a failure to provide required fire alarm protection in one of ten smoke compartments within the facility.

Plan Of Correction

Two battery-operated, ten-year smoke detectors will be installed in the Personal Care Dining Room to alert team members of a possible fire event. A procedure will be developed to explain the steps to follow in the event that detectors sound during a fire event. Current team members associated with Personal Care will be educated initially upon installation and then annually on the procedures. New hired team members will be educated and trained during their orientation. A recurring work order will be created to test these detectors monthly for proper operation and audible levels to the end of the Personal Care corridors. Completed documentation will be presented to QAPI for evaluation.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0341 citations
Fire Alarm System Altered Without Required Plan Approval or Inspection
E
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

The facility installed carbon monoxide detectors on its fire alarm system and placed the system into service without obtaining prior plan approval or completing an occupancy inspection, as confirmed by interviews with the DON and Director of Maintenance. No documentation of approval or completion was provided.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Installation and Obstruction of Fire Alarm System Components
F
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

Surveyors observed that a smoke detector head was not properly mounted to the ceiling at the North Smoke Doors exit into the administration hall, and another smoke detector head in the North Mechanical closet was covered with a plastic bag. These issues were confirmed by the Facility Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Smoke Detector Placement Near Airflow Source
E
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

A smoke detector was found installed within three feet of direct airflow from an air return or supply near an exit door, contrary to NFPA 70 and NFPA 72 requirements. This installation issue was confirmed by Facility Maintenance and could impact 30 occupants during a fire emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Installation of Fire Alarm Initiating Devices
E
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

The facility did not properly install fire alarm initiating devices, affecting one level of the building. The manual pull station for the double exit doors in the Kitchen on the first floor was not mounted within 5 feet of the exit doors, as observed and confirmed during an interview with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Installation of Fire Detection Devices
F
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

The facility failed to maintain smoke and heat detectors according to NFPA standards, as observed in the elevator equipment room where the devices were hanging from wires and not securely attached. This issue had the potential to affect 120 residents, and the responsible individual was unaware of the deficiency.

Inspection fine: $25,635
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙