K0341 K341: Install a fire alarm system that can be heard throughout the facility.
E

Improper Installation of Fire Alarm Initiating Devices

St Monica Center For Rehabilitation & HealthcarePhiladelphia, Pennsylvania Survey Completed on 01-23-2025

Summary

The facility failed to properly install fire alarm initiating devices, specifically affecting one of the three levels in the building. During an observation on January 23, 2025, at 10:45 a.m., it was noted that the manual pull station for the double exit doors in the Kitchen on the first floor was not mounted within 5 feet of the exit doors as required. This deficiency was confirmed during an exit interview with the Administrator and Maintenance Director at 11:45 a.m. on the same day.

Plan Of Correction

1. The manual pull station in the kitchen is scheduled to be moved to be within 5 ft of exit door. 2. NHA/Designee will educate the maintenance director on the requirements of having pull stations within 5 feet of exit doors. 3. NHA/Designee will conduct an audit of exit doors to ensure there is a pull station within 5 feet. 4. Audit report will be submitted to QA.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0341 citations
Fire Alarm System Altered Without Required Plan Approval or Inspection
E
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

The facility installed carbon monoxide detectors on its fire alarm system and placed the system into service without obtaining prior plan approval or completing an occupancy inspection, as confirmed by interviews with the DON and Director of Maintenance. No documentation of approval or completion was provided.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Smoke Detector Protection in Open Dining Room
E
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

The 1st floor Dining Room had its doors removed, leaving the room open to the corridor without any smoke detector protection. This was confirmed by the Director of Facilities, resulting in a failure to provide required fire alarm protection in that smoke compartment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Installation and Obstruction of Fire Alarm System Components
F
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

Surveyors observed that a smoke detector head was not properly mounted to the ceiling at the North Smoke Doors exit into the administration hall, and another smoke detector head in the North Mechanical closet was covered with a plastic bag. These issues were confirmed by the Facility Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Smoke Detector Placement Near Airflow Source
E
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

A smoke detector was found installed within three feet of direct airflow from an air return or supply near an exit door, contrary to NFPA 70 and NFPA 72 requirements. This installation issue was confirmed by Facility Maintenance and could impact 30 occupants during a fire emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Installation of Fire Detection Devices
F
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

The facility failed to maintain smoke and heat detectors according to NFPA standards, as observed in the elevator equipment room where the devices were hanging from wires and not securely attached. This issue had the potential to affect 120 residents, and the responsible individual was unaware of the deficiency.

Inspection fine: $25,635
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙