K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
F

Failure to Document Semiannual Fire Alarm System Inspections

Avista Nursing And RehabilitationSaginaw, Michigan Survey Completed on 05-13-2025

Summary

The facility failed to ensure that the fire alarm system was tested and maintained according to an approved program in compliance with NFPA 72. During a record review, it was found that there was no documentation available to show that the required semiannual visual inspection of the fire alarm initiating devices had been completed, as specified by NFPA 72, section 14.3. This lack of documentation was confirmed during interviews with both the Maintenance Director and the Regional Director at the time of the survey. No information regarding specific residents, their medical history, or their condition at the time of the deficiency was provided in the report.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0345 citations
Failure to Perform and Document Annual Duct Detector Differential Testing
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to perform and/or document the required annual Duct Detector Differential testing for the fire alarm system in accordance with NFPA 101, NFPA 70, and NFPA 72. During record review and interviews with the Director of Facilities, no documentation could be produced to show that this annual testing had been completed, and the Director acknowledged the lack of records. This deficiency was cited as potentially affecting all occupants in the event of a fire or other emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Complete Required Fire Alarm System Sensitivity Testing
D
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

The facility did not complete required sensitivity testing for all smoke and duct detectors as mandated by NFPA 101 and NFPA 72. Record review revealed that 11 smoke detectors and two duct detectors were not tested, and inspection reports lacked documentation of sensitivity testing results. The Regional Maintenance Director acknowledged these findings during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Operable Fire Alarm System Components
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility did not maintain its fire alarm system in operable condition, with issues such as failed battery load tests, a non-functioning buzzer at the FACP, improperly connected horn strobes, missing required signage at pull stations, and malfunctioning smoke and heat detectors. Facility leadership confirmed these deficiencies were not corrected at the time of review.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Alarm System in Accordance with NFPA Standards
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

The facility did not maintain its fire alarm system as required, with the fire alarm panel displaying fault and trouble indicators over multiple survey visits. The deficiencies were confirmed by the maintenance supervisor and remained uncorrected due to delays in vendor payment and scheduling.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Documentation for Fire Alarm System Testing
E
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that documentation for required semi-annual fire alarm system testing was not available during review. The Administrator and Maintenance Director confirmed the missing records, resulting in a deficiency related to fire alarm system maintenance requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Alarm System Documentation
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility did not have documentation of a required semi-annual visual inspection of the fire alarm system for all smoke compartments, as confirmed during interviews with facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release May 27, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙