K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
D

Failure to Maintain Fire Alarm System in Proper Working Order

Crystal River Health And Rehabilitation CenterCrystal River, Florida Survey Completed on 04-26-2026

Summary

Surveyors found that the facility failed to maintain its fire alarm system in accordance with NFPA 72 requirements. During an observation at 3:30 PM, the fire alarm control panel was noted to be displaying a trouble signal. Upon concurrent interview, the Maintenance Director acknowledged the trouble condition and stated it was due to a faulty heat detector. This unresolved trouble signal on the fire alarm control panel constituted a failure to ensure the fire alarm system was maintained and functioning as designed for the entire facility. No residents or specific patient conditions were mentioned in the report, and no additional clinical details were provided.

Plan Of Correction

This Plan of Correction constitutes written compliance for the deficiencies cited. However, submission of this Plan of Correction is not an admission that a deficiency exists or that one was cited correctly. This plan of correction is submitted to meet requirements established by State and Federal Law. To comply with K0345 and assure continued compliance, the following plan has been put in place. K0345 - Fire Alarm System Maintenance Immediate Correction: A fire alarm provider diagnosed and repaired the trouble signal, restoring the system to a "System Normal" state. Residents in the affected zone were monitored for safety during the repair. Identification of Others: A 100% audit of the Fire Alarm Control Panel (FACP) was conducted to ensure no other trouble or supervisory signals were present facility-wide. Systemic Changes: Maintenance and administrative staff were re-educated on responding to trouble signals within 24 hours and documenting all actions in the maintenance log. Monitoring (QA): The Maintenance Supervisor will conduct daily visual inspections of the FACP. The Safety Committee will review all service reports monthly, reporting findings to the QAPI Committee.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0345 citations in Ohio
Failure to Perform and Document Semi-Annual Fire Alarm System Inspections
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors determined that the facility did not comply with NFPA 101 and NFPA 72 requirements for fire alarm system maintenance when record review showed incomplete fire alarm inspection reports and no documentation of required semi-annual visual inspections of fire detection components. The Director of Maintenance confirmed that these six-month inspections had not been documented and reported being unaware of the requirement, creating a deficiency that had the potential to affect all four residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Document Fire Alarm System per NFPA Requirements
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to maintain and document its fire alarm system in accordance with NFPA 101 and NFPA 72, potentially affecting all residents. The only annual fire alarm record provided was a single page without a device list, and there was no documentation of required semi-annual visual inspections or sensitivity testing of devices. During the tour, surveyors observed multiple fire alarm breakers in various electrical panels that were not marked in red, not secured from unauthorized access, and in one case left in the off position, with panel labeling insufficient to identify the presence of a fire alarm breaker. These findings were confirmed with the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

65.1% of Ohio facilities received at least one citation during their inspection in the last 12 months.Will yours be survey-ready?

Surveyors issued 55 serious citations across Ohio in the last 12 months. See exactly what they're citing.

Get ready for your next survey

See what surveyors are citing in Ohio and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release May 27, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙