K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
F

Failure to Address Sprinkler System Deficiency After Failed Inspection

Autumnwood Of DeckervilleDeckerville, Michigan Survey Completed on 03-05-2025

Summary

The facility failed to provide required maintenance and testing for its automatic sprinkler system in accordance with NFPA 25. During a record review, it was found that the annual fire sprinkler inspection report from November 21, 2024, documented a failure of the dry fire sprinkler system accelerator, which resulted in a failed flow test. As of the time of the survey on March 5, 2025, the deficiencies identified in the inspection report had not been addressed. These findings were confirmed through an interview with the maintenance director during the record review. No information about specific residents or their medical conditions was included in the report.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0353 citations
Failure to Perform and Document Required 20-Year Sprinkler Head Testing
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to perform and/or document the required 20-year testing of quick-response sprinkler heads throughout all smoke compartments, as required by NFPA 25. During review of Life Safety records with the Director of Environmental Services, no documentation of a 20-year sprinkler test was available, despite the sprinklers being original to the building. Spare sprinkler heads in stock showed manufacturing dates from the late 1990s, and the outside testing company could not provide historical records to confirm that the mandated 20-year testing had ever been completed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiency in Sprinkler System Compliance
D
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the Main Lobby had mixed sprinkler coverage, with two quick response and two standard sprinklers, which does not comply with NFPA requirements. The Regional Maintenance Director acknowledged the issue during the inspection, and the deficiency was documented with photographic evidence.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Document Sprinkler System Inspections and Maintenance
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

The facility did not provide documentation for required sprinkler system inspections and allowed sprinkler heads to become covered in dust and corrosion. Staff confirmed missing inspection records and overdue maintenance, and the facility was unable to complete necessary repairs due to a payment hold with the vendor. The deficiencies remained uncorrected during follow-up surveys, resulting in a continuous fire watch.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler Heads Not Maintained Free of Debris in Main Kitchen
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that sprinkler heads in the Main Kitchen were covered with debris, particularly around vents, and this was confirmed by facility leadership during interviews. The deficiency affected one of nine smoke zones.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Not Maintained Free of Extraneous Weight
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to keep the automatic sprinkler system free of extraneous weight, with multiple wires and flex conduit observed attached to or laying across sprinkler piping in several areas above the ceiling. Facility leadership confirmed these items were present and supported by the sprinkler system.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Not Maintained Free of Extraneous Weight
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors observed that the facility's automatic sprinkler system was not maintained free of extraneous weight, with multiple wires and flex conduit supported by sprinkler piping and brackets in two smoke compartments. Facility leadership confirmed these findings during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release May 27, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙