K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
F

Failure to Maintain Required Sprinkler System Inspection Documentation

Adams County ManorWest Union, Ohio Survey Completed on 03-25-2026

Summary

The facility failed to properly maintain its automatic sprinkler system in accordance with NFPA 101 (2012) and NFPA 25 (2010), affecting all 67 residents in the building. During record review on 03/25/26 beginning at 8:45 A.M., surveyors found only one documented sprinkler inspection within the previous 12 months, dated 04/23/25. Additional documentation of required inspections was requested at the entrance conference at 8:40 A.M., and again at 9:35 A.M. and 10:10 A.M., but no further records were provided by the time of exit. An interview with the Maintenance Director confirmed that there were no other sprinkler inspection records available, verifying the lack of documented ongoing inspection and maintenance of the sprinkler system. No specific resident medical histories or conditions at the time of the deficiency were described in the report.

Plan Of Correction

1.Based on record review, observation and interview, no residents experienced negative outcomes related to sprinkler system deficiencies. The facility failed to ensure sprinkler system inspection, testing, and maintenance were completed and documented in accordance with NFPA 25. Findings included lack of complete inspection documentation within the required timeframe and identified physical deficiencies (including missing escutcheon plates). 2.The Medical Director was notified by LNHA on 03/26/2026 that the facility failed to ensure sprinkler system inspections, testing, and maintenance were completed and documented in accordance with NFPA 101 and NFPA 25 requirements. 3.Sprinkler system inspection, testing, and maintenance will be completed by a contracted fire protection vendor on or before 04/30/2026. This will include implementation of a full Inspection, Testing, and Maintenance (ITM) program in accordance with NFPA 25 (2010 Edition), including but not limited to:  Completion of a full annual sprinkler system inspection in accordance with NFPA 25 §13.6.2.1.  Quarterly testing of waterflow alarm devices and supervisory signals.  Monthly and/or weekly inspection of control valves, gauges, and system condition as applicable.  Five-year internal pipe inspection (obstruction investigation) if due.  Inspection of all sprinkler heads to ensure no damage, corrosion, paint, loading, obstruction, or missing escutcheon plates.  Verification that all components are installed correctly and maintained in reliable operating condition. All identified physical deficiencies (including missing escutcheon plates and any additional deficiencies discovered during inspection) will be corrected on or before 04/30/2026. A comprehensive facility-wide sprinkler system inspection will be completed to ensure no additional deficiencies exist. All inspection, testing, and maintenance activities will be placed on an automatically recurring schedule by Administrator/designee to ensure ongoing compliance. 4.Documentation of all sprinkler system inspection, testing, and maintenance activities will be maintained onsite and readily available at the time of survey. The Maintenance Director/designee will conduct routine audits to verify completion of required inspection, testing, and maintenance (ITM) activities. Compliance will be reviewed in QAPI every quarter and as needed to ensure ongoing systemic compliance. 5.LNHA educated Maintenance Director on 03/26/2026 regarding the requirements for maintaining the facility's fire suppression equipment, as well as ensuring required completion of backflow device testing; and required escutcheon plates to sprinkler heads.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0353 citations
Missing Documentation for Required Sprinkler System Inspections
C
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for its fire sprinkler system. During review and interview, the facility could not provide records of semi-annual inspections for valve supervisory switches or annual inspections for control valves. The maintenance supervisor confirmed that these sprinkler system inspection records were not available when requested by surveyors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Sprinkler System Testing and Fire Drill Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for multiple fire protection system tests and inspections, including the annual fire hydrant flow test, the five-year GPM test of the hydrant, the five-year internal inspection of the fire riser, and the five-year hydrostatic test of the FDC, as required by NFPA 101 and NFPA 25. In addition, the facility lacked records of required fire drills for each shift per quarter, with missing drills for one quarter’s third shift and for the second and third shifts of the last quarter of the prior year. The Maintenance Director acknowledged that these records were not available.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing 5-Year Internal Sprinkler System Inspection Report
D
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors determined that the facility did not maintain required documentation for its automatic sprinkler system. Record review showed the sprinkler system was past due for the mandated 5-year internal inspection, and the facility could not produce the most recent 5-year inspection report. During interview, the Maintenance Director confirmed that this inspection report was missing, and the deficiency was cited as affecting the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler Inspection Records and Obstructed Exterior Sprinkler Head
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that required sprinkler system inspection documentation was incomplete, with only three quarterly reports available and the 2nd quarter annual sprinkler report missing. During observation of the exterior car port, one of six sprinkler heads was obstructed by underside aluminum paneling. The Administrator and Maintenance Director confirmed both the missing documentation and the obstruction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Support of Sprinkler Piping by Electrical Conduit in Two Smoke Compartments
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility did not maintain its automatic sprinkler system in accordance with NFPA standards when electrical MC wire conduit was found resting directly on sprinkler piping above ceiling tiles in the elevator lobby areas on two separate floors, affecting two of fifteen smoke compartments. The Facility Administrator and Director of Maintenance acknowledged these sprinkler system deficiencies during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Required 20-Year Sprinkler Head Testing
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to perform and/or document the required 20-year testing of quick-response sprinkler heads throughout all smoke compartments, as required by NFPA 25. During review of Life Safety records with the Director of Environmental Services, no documentation of a 20-year sprinkler test was available, despite the sprinklers being original to the building. Spare sprinkler heads in stock showed manufacturing dates from the late 1990s, and the outside testing company could not provide historical records to confirm that the mandated 20-year testing had ever been completed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

65.1% of Ohio facilities received at least one citation during their inspection in the last 12 months.Will yours be survey-ready?

Surveyors issued 55 serious citations across Ohio in the last 12 months. See exactly what they're citing.

Get ready for your next survey

See what surveyors are citing in Ohio and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release May 27, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙