K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
E

Automatic Sprinkler System Deficiency Due to Unsealed Ceiling Penetrations

Fulton County Medical CenterMcconnellsburg, Pennsylvania Survey Completed on 04-22-2025

Summary

The facility failed to maintain the automatic sprinkler system, as evidenced by an observation on April 22, 2025, at 12:25 p.m. During this observation, two unsealed penetrations were found in the ceiling tiles of the LTC Gym, specifically on the left side of the gym. This deficiency could potentially affect the operation of the automatic sprinkler system in one of the four smoke compartments. An interview with the Facility Administrator and Plant Operations Manager later confirmed the presence of this automatic sprinkler system deficiency.

Plan Of Correction

1. The facility replaced 2 ceiling tiles and corrected unsealed penetrations in the LTC gym on April 23, 2025. 2. Facility maintenance staff will complete visual inspection of ceiling tiles each quarter during their regular penetration inspections. The LTC Quarterly Penetration Inspection form was updated on 5/6/2025 to reflect documentation of the visual inspection. 3. Completion of visual inspection of ceiling tiles and documentation of such will be audited during the monthly Building and Safety meeting which is attended by Plant Operations Manager, Director of Environmental Services, FCMC Safety Officer, Nursing Home Administrator and Chief Operations Officer for twelve months.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0353 citations
Missing Documentation for Required Sprinkler System Inspections
C
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for its fire sprinkler system. During review and interview, the facility could not provide records of semi-annual inspections for valve supervisory switches or annual inspections for control valves. The maintenance supervisor confirmed that these sprinkler system inspection records were not available when requested by surveyors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Sprinkler System Testing and Fire Drill Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for multiple fire protection system tests and inspections, including the annual fire hydrant flow test, the five-year GPM test of the hydrant, the five-year internal inspection of the fire riser, and the five-year hydrostatic test of the FDC, as required by NFPA 101 and NFPA 25. In addition, the facility lacked records of required fire drills for each shift per quarter, with missing drills for one quarter’s third shift and for the second and third shifts of the last quarter of the prior year. The Maintenance Director acknowledged that these records were not available.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing 5-Year Internal Sprinkler System Inspection Report
D
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors determined that the facility did not maintain required documentation for its automatic sprinkler system. Record review showed the sprinkler system was past due for the mandated 5-year internal inspection, and the facility could not produce the most recent 5-year inspection report. During interview, the Maintenance Director confirmed that this inspection report was missing, and the deficiency was cited as affecting the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler Inspection Records and Obstructed Exterior Sprinkler Head
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that required sprinkler system inspection documentation was incomplete, with only three quarterly reports available and the 2nd quarter annual sprinkler report missing. During observation of the exterior car port, one of six sprinkler heads was obstructed by underside aluminum paneling. The Administrator and Maintenance Director confirmed both the missing documentation and the obstruction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Support of Sprinkler Piping by Electrical Conduit in Two Smoke Compartments
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility did not maintain its automatic sprinkler system in accordance with NFPA standards when electrical MC wire conduit was found resting directly on sprinkler piping above ceiling tiles in the elevator lobby areas on two separate floors, affecting two of fifteen smoke compartments. The Facility Administrator and Director of Maintenance acknowledged these sprinkler system deficiencies during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Sprinkler System Inspection Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility failed to maintain required inspection and testing of its automatic sprinkler system in accordance with NFPA standards. Record review showed only one documented sprinkler inspection within the prior year, and no additional inspection records were produced despite multiple requests during the survey. The Maintenance Director confirmed that no other sprinkler inspection documentation was available, indicating that ongoing required inspections were not documented for all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙