F0908 F908: Keep all essential equipment working safely.
E

Incomplete Fire Watch During Fire Alarm System Impairment

La Bella Of DanvilleDanville, Illinois Survey Completed on 06-23-2026

Summary

The facility failed to ensure fire system equipment was functioning properly and failed to complete a thorough fire watch for 10 residents living in Zone 2 of the North Building Dementia Unit. On 6/18/26, the fire alarm annunciator panel behind the front nurses' station displayed "Trouble Fire - Zone 2 Open Fault." Staff began fire watch because Zone 2 was offline and included rooms 4 through 17, but the fire watch did not include rooms 5 through 13. Later observations on 6/23/26 showed a CNA walking the hallway and looking only into rooms with open doors, without touching closed resident room doors for heat, opening closed doors to inspect rooms, or entering the closed hallway beyond the fire doors to inspect rooms 5 through 13, even though those rooms were within the affected fire alarm zone. The Maintenance Director stated water damage beginning on 6/6/26 damaged a fire sensor on 6/10/26 and that a disconnected wire also affected the fire alarm panel. The fire system service coordinator stated the alarm panel showed a Zone 2 open fault and an internal ground fault, and that the panel needed replacement before further troubleshooting could occur; the coordinator also stated the facility should remain on continuous fire watch until the panel was replaced and deficiencies corrected. The facility's fire watch policy required that whenever a significant portion of the fire alarm or sprinkler system is not functioning, the fire watch team observe and inspect every room. The facility's records documented 10 residents in Zone 2, and the fire alarm system remained impaired during the period reviewed.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0908 citations
Expired Supplies Found in Crash Carts
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Expired supplies were found in two crash carts on nursing units 1B and 2B. An opened Ambu bag in the 2B cart was expired, and the 1B cart contained two expired Ambu bags and expired Assure Prism glucometer strips. RN staff confirmed the items were expired and should not have been in the carts.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Stove Burner Not Functioning
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

A gas stove in the kitchen had a back center burner that would not ignite when turned on, and staff reported it had been not working for about 1 to 2 months. Interviews showed cooks were expected to report equipment problems to the DM, who would notify Maintenance, but the issue was not promptly communicated to Maintenance. No gas odor or hissing was observed, and the burner was later taken out of service until repaired.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Elevator Malfunctioned and Remained in Need of Repair
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

The facility failed to keep one of its elevators in safe operating condition. Records showed elevator two malfunctioned multiple times and needed a replacement part, and residents and staff were aware of the repeated malfunctions. The Administrator confirmed the elevator was malfunctioning and needed repair.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Dryer Lint Traps
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Failure to Maintain Dryer Lint Traps: Surveyors observed heavy lint buildup in both dryer lint traps, with lint hanging from each trap and covering the full trap surface. The sign-off log showed no entries after the prior shift, and staff interviews confirmed the required two-hour checks and documentation were not consistently completed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Glucometer Calibration and Quality Control Not Documented
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Glucometer calibration and QC were not documented for one glucometer on Medication Cart D, and the QC log was blank for the scheduled check. LVN and DON verified that the 11-7 shift was responsible for nightly/daily calibration and QC to support accurate blood sugar readings.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Thermostats Not Powered On or Working
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Thermostats Not Powered On or Working: Two of five sampled thermostats were observed turned off with black screens and no visible power. A resident’s RP said it was always hot in the resident’s room and a fan was provided because there was no working AC. The MS stated the thermostats should be on and working to regulate room temperatures, but he was unsure how often they should be checked.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Illinois

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Illinois — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release October 8, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.