F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
F

Ventilation Systems Not Functioning Properly

Autumn Lake Healthcare At Chesapeake WoodsCambridge, Maryland Survey Completed on 12-19-2025

Summary

The facility failed to maintain clean and effective ventilation systems, and survey observations found that 13 of 16 ventilation systems reviewed during the annual survey were not functioning as intended. During kitchen observations, the surveyor used a smoke stick to assess airflow in the local exhaust ventilation systems and found that the Type 2 hood above the high-temperature mechanical dishwasher was inadequately designed and calibrated, with steam dissipating into the kitchen instead of being captured by the hood. The Type 1 canopy hood over the commercial convection oven and steamer was also positioned so the appliance extended beyond the hood overhang, allowing grease, steam, heat, condensation, and vapors to escape into the kitchen. Further physical verification of exhaust fan function was completed with the Regional Maintenance Director by placing tissue paper on exhaust fan covers. Multiple areas were found inoperable, including the dirty laundry room, clean laundry room, Choptank janitor's closet, soiled utility closet, one spa room, the B-wing soiled utility room, the B-wing janitor's closet, and several resident bathrooms. Some areas were noted as sufficient, including the E hallway bathroom, one spa room, and the oxygen tank storage room was noted as positive pressure. The Administrator was informed of the findings, and the Regional Maintenance Director had also shared the information.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0923 citations
Non-Functional Mechanical Ventilation
F
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Non-Functional Mechanical Ventilation: The facility failed to maintain mechanical ventilation in good working order. A shower room on the 1st floor South had humid, heavy air and no suction at the ceiling vent, and the Maintenance Supervisor I stated the vent was not drawing air and may have needed belt checks. Soiled utility room vents on the North and South Halls and bathroom ceiling vents for listed rooms were also found non-functional, with broken belts cited as the cause.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Bathroom Exhaust Ventilation Not Functioning
E
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Bathroom exhaust vents were not functioning in multiple resident rooms on the 100 and 200 halls, with surveyors observing no air movement at the ceiling vents in both occupied and unoccupied bathrooms. An MTC confirmed the ventilation problem and stated the vents were usually checked weekly, but there was no documentation to verify those checks.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Inadequate Ventilation in Resident Rooms and Hallways
E
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Inadequate ventilation was identified throughout the facility when surveyors observed resident room windows on multiple floors screwed shut and unable to open, with no screens present. Hallway HVAC was present but not functioning in some areas, and only some resident rooms had AC units. Staff stated the building was not fully equipped with AC, that the windows were kept shut due to security concerns, and that repair recommendations for non-functioning AC units had been pending corporate approval.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Airflow in Soiled Laundry Rooms
D
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Improper Airflow in Soiled Laundry Rooms: During the annual survey, a strong odor was noted in the soiled laundry rooms because the mechanically operated ventilation systems serving the two soiled laundry rooms did not have negative pressure airflow. On a follow-up tour, a window in one soiled laundry room was open to provide air circulation, and the Maintenance Director stated the roof exhaust fans would be reassessed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Inadequate Ventilation Above Dish Machine Caused Ceiling Damage
F
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Inadequate ventilation above the dish machine allowed steam to rise and hit the ceiling tiles over the dishwashing area. Staff observed bowed, peeling ceiling tiles, exposed yellow foam insulation, and a disrepair area around the ventilation duct, and the Maintenance Director stated the damage was caused by steam from the dish machine and had required repeated tile repairs.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Nonworking Bathroom Ventilation in 10 Resident Rooms
E
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Nonworking Bathroom Ventilation in 10 Resident Rooms: Surveyors observed that the bathroom vents in 10 resident rooms did not function when tested with toilet paper. Maintenance staff later confirmed the vents were not working and was unaware of the problem, and could not provide bathroom vent check logs. Record review showed the facility policy required ventilation system audits to be maintained.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Maryland

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Maryland — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release October 8, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.