K0311 K311: Have an enclosure around a vertical opening shaft.
B

Failure to Maintain Self-Closing Mechanism on Laundry Chute Door

Concordia Lutheran Health And Human CareCabot, Pennsylvania Survey Completed on 07-30-2025

Summary

The facility failed to maintain proper self-closing mechanisms on a vertical opening door, specifically the basement laundry chute door. During an observation, it was found that the chute door did not have the required number of fusible links on its hold-open springs, with only one of the two necessary fusible links installed. This deficiency prevented the chute door from closing as required. The issue was confirmed in an interview with the administrator and maintenance supervisor.

Plan Of Correction

Fusible link replaced immediately at time of survey. Weekly audits to ensure fusible link is installed will be completed by Maintenance or designee weekly for four weeks. After four weeks, audits will continue monthly. The results of these audits will be reviewed quarterly by the Quality Assurance and Quality Improvement committee for further analysis and recommendation.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0311 citations
Failure to Maintain Fire Resistance Rating for Vertical Openings
B
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

The facility failed to maintain the required fire resistance rating for vertical openings, affecting two levels. The stairway between the Lower Level Kitchen and the First Floor lacked one-hour fire resistive construction. Additionally, the north side exit from the Basement had a staircase with unsheathed walls, lacking the required fire resistance. These deficiencies were confirmed during interviews with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Vertical Opening Enclosures
E
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

The facility failed to maintain proper vertical opening enclosures, as unsealed openings were found in a bathroom pipe chase wall on two unoccupied floors. This was due to ongoing work to replace a leaking drain pipe, affecting two smoke compartments. The issue was confirmed by the Facility Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Resistance Rating on Tenth Floor
E
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

The facility did not maintain the fire resistance rating of vertical openings on the tenth floor. An observation revealed that the rated access ceiling door in the Electrical Closet next to room 1020 failed to self-close and latch, as confirmed by the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Vertical Opening Enclosure Deficiency
D
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

The facility did not maintain the required fire resistance rating for vertical opening enclosures, affecting one smoke compartment. Observations revealed multiple wires passing through a large open hole in Room U 115, confirmed by the Facility Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Inadequate Fire Resistance in Vertical Enclosures
C
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

The facility failed to maintain the required fire resistance rating for vertical enclosures, affecting all six floors. Observations revealed that HVAC shafts adjacent to exit stair towers lacked the necessary two-hour fire resistance. Additionally, the Clay Street exit stair tower on the fourth and fifth floors had inadequate construction, with insufficient drywall and unprotected steel beams. This deficiency was confirmed during an exit interview with the Facility Administrator and Facilities Manager.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Vertical Opening Fire Safety Deficiency
E
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

The facility failed to maintain fire safety for a vertical opening between two floors. The self-closing devices were removed from the Private Dining Room's double doors, which are part of a one-hour, two-story vertical opening. This deficiency was confirmed during an interview with the Facility Administrator and Facilities Manager.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙