F0908 F908: Keep all essential equipment working safely.
L

Failure to Maintain Boiler System Results in Inadequate Heating

Grand Manor Nursing & Rehabilitation CenterBronx, New York Survey Completed on 12-19-2024

Summary

The facility failed to maintain all mechanical, electrical, and patient care equipment in safe operating condition, specifically neglecting routine maintenance of the boiler system. The annual service contract for the boilers had expired, and the facility did not have a current contract in place. Multiple proposals and quotes from vendors to address identified boiler deficiencies and to provide ongoing maintenance were not acted upon by the facility. Invoices and service records showed repeated reports of insufficient heat and hot water, with only a fraction of the boilers functioning at any given time. The lack of maintenance led to the heating system malfunctioning, resulting in inadequate heating throughout the building. Observations during the survey revealed that temperatures in resident rooms, corridors, and stairwells were below the required state and federal ranges, with some areas measured as low as 40 degrees Fahrenheit. Resident rooms closest to the stairwells had the lowest temperatures. There was no documented evidence that the facility staff were inspecting or maintaining the heating system equipment, including the boilers and Packaged Terminal Air Conditioner (PTAC) units. The Director of Maintenance confirmed that the PTAC units were not blowing hot air due to incorrect connections and that the Administrator had been made aware of the issue. Interviews with the Director of Maintenance, the Administrator, and the boiler vendor revealed that the vendor had stopped servicing the facility due to unpaid bills, and that the Director of Maintenance was not permitted to order services or materials without prior approval from the Administrator. The Administrator was unaware of the extent of the heating issues and the low temperatures in resident rooms. The vendor reported that the boilers were operating at only about 40% capacity due to lack of maintenance, which contributed to the insufficient heat and hot water throughout the building.

Removal Plan

  • Packaged Terminal Air Conditioner units were deployed to all affected areas. Residents were relocated to warmer areas of the facility and temperature checks of all residents' rooms were conducted by the facility. A review of the temperature logs revealed temperatures within acceptable ranges.
  • Extra blankets and clothing were distributed to the residents by Housekeeping and Activities staff, hot beverages were provided, and residents had the option of staying in the warmer common areas.
  • The Administrator provided a vendor contract for annual boiler maintenance and the maintenance of Packaged Terminal Air Conditioner units.
  • The facility completed staff training on identifying and addressing temperature-related issues, procedures for reporting problems, deploying emergency measures, and ensuring resident comfort. 100% of staff received the in-service.
  • A Quality Assurance meeting was held to discuss the findings of the Immediate Jeopardy. Wall thermometers have been installed in residents' rooms and staff were given in-service education on reading the thermometers.
  • The Emergency Preparedness plan for Loss of Heat was revised to include immediate deployment of portable units and proactive monitoring and escalation processes for heating issues.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0908 citations
Inoperable Commercial Washer in Laundry Department
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

In the laundry department, 1 of 2 commercial washers was out of service for more than 8 months, leaving only 1 washer available for resident laundry. Laundry Aides stated they used the working washer for all residents and that keeping up with timely laundry services was sometimes challenging with only 1 machine.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Hoyer Lift Batteries Not Maintained in Safe Operating Condition
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

A resident who required a mechanical lift for transfers experienced repeated Hoyer lift battery failures during transfers, including one observed transfer where the lift stopped working while he was being lowered. Staff reported that lift batteries were often not charged, that overnight staff were responsible for charging them, and that they sometimes used the emergency release to lower the resident when the battery died. The DON and other staff confirmed the batteries were not consistently checked or maintained, and the maintenance supervisor said batteries were only replaced occasionally.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Flooring Renovation Started Before Construction Review Approval
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

Flooring Renovation Started Before Construction Review Approval: The facility removed carpet and installed laminate flooring in resident areas before receiving DOH Construction Review Services approval. The Administrator said the second-floor west unit remodeling had already been completed and residents were moved to another unit during the work. Notices to residents described planned flooring replacement, observation confirmed new wood flooring in the hallway and resident rooms, and a resident said they were relocated for at least two weeks. The Regional Plant Operations Director stated the approval was still pending and that they were unsure of the approval process.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Laundry Equipment Not Maintained in Safe Operating Condition
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

Laundry equipment was not maintained in safe operating condition. A resident with ESRD on dialysis reported that clothes came back stinking, while the Laundry Supervisor said the industrial washer kept breaking down, hot water was not getting hot, the wrong soap was being used for resident clothing, and the department lacked a hopper for washing soiled linens. Observation showed a small washer overfilled with sheets, and staff gave mixed reports about washer breakdowns and linen shortages.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Mechanical Lift Found With Exposed Charging Cord
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Mechanical lift equipment on the 3rd floor was observed with exposed black and red inner cords from the grey charging cord hanging out. An RN said the lift should not be used if the cords are exposed, and the DON stated such equipment should be reported to maintenance and removed from the floor for safety precautions. The Maintenance Director confirmed the outer grey cord protects the inner cords, and the maintenance log showed no repair report for the lift.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Expired Ambu Bags Found on Two Crash Carts
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

Expired Ambu Bags Found on Two Crash Carts: The facility failed to ensure two crash carts were in safe operating condition when an Ambu bag on the First Floor Crash Cart and an Ambu bag on the Second Floor Crash Cart were both found expired. RN staff confirmed the expired equipment and acknowledged the carts were not maintained as required by the facility's crash cart management process.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across New York

Get a heads-up on the newest immediate-jeopardy (J–L) citations in New York — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙