F0908 F908: Keep all essential equipment working safely.
L

Failure to Maintain Boiler System Results in Inadequate Heating

Grand Manor Nursing & Rehabilitation CenterBronx, New York Survey Completed on 12-19-2024

Summary

The facility failed to maintain all mechanical, electrical, and patient care equipment in safe operating condition, specifically neglecting routine maintenance of the boiler system. The annual service contract for the boilers had expired, and the facility did not have a current contract in place. Multiple proposals and quotes from vendors to address identified boiler deficiencies and to provide ongoing maintenance were not acted upon by the facility. Invoices and service records showed repeated reports of insufficient heat and hot water, with only a fraction of the boilers functioning at any given time. The lack of maintenance led to the heating system malfunctioning, resulting in inadequate heating throughout the building. Observations during the survey revealed that temperatures in resident rooms, corridors, and stairwells were below the required state and federal ranges, with some areas measured as low as 40 degrees Fahrenheit. Resident rooms closest to the stairwells had the lowest temperatures. There was no documented evidence that the facility staff were inspecting or maintaining the heating system equipment, including the boilers and Packaged Terminal Air Conditioner (PTAC) units. The Director of Maintenance confirmed that the PTAC units were not blowing hot air due to incorrect connections and that the Administrator had been made aware of the issue. Interviews with the Director of Maintenance, the Administrator, and the boiler vendor revealed that the vendor had stopped servicing the facility due to unpaid bills, and that the Director of Maintenance was not permitted to order services or materials without prior approval from the Administrator. The Administrator was unaware of the extent of the heating issues and the low temperatures in resident rooms. The vendor reported that the boilers were operating at only about 40% capacity due to lack of maintenance, which contributed to the insufficient heat and hot water throughout the building.

Removal Plan

  • Packaged Terminal Air Conditioner units were deployed to all affected areas. Residents were relocated to warmer areas of the facility and temperature checks of all residents' rooms were conducted by the facility. A review of the temperature logs revealed temperatures within acceptable ranges.
  • Extra blankets and clothing were distributed to the residents by Housekeeping and Activities staff, hot beverages were provided, and residents had the option of staying in the warmer common areas.
  • The Administrator provided a vendor contract for annual boiler maintenance and the maintenance of Packaged Terminal Air Conditioner units.
  • The facility completed staff training on identifying and addressing temperature-related issues, procedures for reporting problems, deploying emergency measures, and ensuring resident comfort. 100% of staff received the in-service.
  • A Quality Assurance meeting was held to discuss the findings of the Immediate Jeopardy. Wall thermometers have been installed in residents' rooms and staff were given in-service education on reading the thermometers.
  • The Emergency Preparedness plan for Loss of Heat was revised to include immediate deployment of portable units and proactive monitoring and escalation processes for heating issues.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0908 citations
Kitchen Dishwashing System Leak Not Maintained
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

The facility failed to keep a kitchen dishwashing system in good working order when surveyors observed water flowing from a metal device under the counter, with buckled tile and peeled-back wall trim nearby. A kitchen staff member said maintenance had known about the leak for about a month, and maintenance later confirmed the issue had not been reported through the TELS system and that the damage was not new.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lint Buildup in Dryer Lint Trap
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Lint Buildup in Dryer Lint Trap: One of two dryers was observed running with lint buildup in the lint trap after the lint door was opened during a laundry tour. The MSS stated the lint trap should be cleaned every 2 hours for fire safety, and an LA stated she forgot to clean Dryer 2's lint trap. Facility policy required laundry equipment to be maintained per manufacturer instructions and kept in a safe, operable condition.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Refrigeration Not Maintained in Working Condition
F
F0908 F908: Keep all essential equipment working safely.
Short Summary

Essential kitchen equipment was not kept in good working condition. A large kitchen refrigerator had standing water on the bottom shelf and water dripping from the top onto covered food, and a resident refrigerator freezer had heavy ice buildup with a splintered gasket that did not attach well. The ADON and Maintenance Director both verified the equipment problems, and the MD stated the refrigerator was not working properly and needed repaired.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Dishwasher Thermometer Inaccurate and Temperatures Below Required Level
F
F0908 F908: Keep all essential equipment working safely.
Short Summary

Dishwasher Thermometer Inaccurate and Temps Below Required Level: The low-temp dishwasher was observed with wash and rinse temps below the facility's required 120F minimum, and the DS stated staff had to handwash dishes while the machine was out of order. The MS later found the machine's thermometer was not reading accurately, with the manual thermometer showing 135.1F while the machine read 118F, and the DS said the length of time the thermometer had been inaccurate was unknown.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Equipment Not Maintained in Safe Operating Condition
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

Kitchen equipment was not maintained in safe operating condition. A plate warmer was plugged in but only held room-temperature plates, and staff said it had not warmed plates since the prior week or earlier. A dishwasher temperature gauge was also faulty, reading 110F while a separate gauge showed the water was 122F during operation. The Maintenance Director said he had not been notified of either issue and found no June maintenance entries for the plate warmer or dishwasher gauge.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Equipment Not Maintained in Working Order
F
F0908 F908: Keep all essential equipment working safely.
Short Summary

Kitchen equipment was not maintained in proper working order, affecting nearly all residents who received meals from the kitchen. Surveyors observed significant ice buildup in two reach-in freezers, including on food products, and found the garbage disposal covered. Dietary staff said the disposal had been broken for about a year, and the DM reported the freezers were constantly in defrost with possible door seal problems. Maintenance confirmed the disposal needed replacement and said approval was delayed because the facility was being sold.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across New York

Get a heads-up on the newest immediate-jeopardy (J–L) citations in New York — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release August 26, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.