F0908 F908: Keep all essential equipment working safely.
F

Failure to Report Facility-Wide Sprinkler System Outage to IDPH

Thryve Of South HollandSouth Holland, Illinois Survey Completed on 04-03-2025

Summary

The facility failed to follow its fire watch policy by not reporting to the Illinois Department of Public Health (IDPH) that the sprinkler system was non-functional in all four units of the building. The facility's fire watch policy requires notification of the fire department and other authorities having jurisdiction when the fire protection system is impaired. Although the fire department was notified and fire watch procedures were implemented, the facility did not ensure that IDPH was informed about the full extent and duration of the sprinkler system impairment affecting all units. Multiple incident reports document a series of sprinkler system failures, beginning with a broken pipe that initially affected a vacant unit, followed by additional pipe failures impacting units with residents. The maintenance director confirmed that after a series of leaks and repairs, the entire sprinkler system, including all resident-occupied units, was drained and left non-operational while awaiting parts. Throughout this period, the facility remained on fire watch, with staff conducting building rounds every 30 minutes and logging their activities. The administrator acknowledged responsibility for reporting such incidents to IDPH but could not recall if the most recent report included the critical detail that all four units were without a working sprinkler system or the duration of the outage. The failure to provide this information to IDPH represents a deficiency in following the facility's own fire safety and reporting policies, potentially affecting all 117 residents present at the time.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0908 citations in Ohio
Nonfunctional Phone System on Secured Behavioral Units
F
F0908 F908: Keep all essential equipment working safely.
Short Summary

The facility failed to maintain a functional phone system on its secured behavioral units. On the women’s secured behavioral unit, the nurse’s station phone was not working and a second unit phone was unplugged, leaving staff without a working line for incoming calls from families. On the men’s secured behavioral unit, the unit phone was also unplugged and not operational, and staff reported frequent problems with phones not working. The receptionist stated that after her work hours, calls are routed to nurse’s stations, but acknowledged there had been recent periods when phones were not working. The administrator did not view families’ inability to call in as a problem, noted that staff sometimes shared personal phone numbers with families, and confirmed there was no specific phone policy.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Dishwasher in Working Order
F
F0908 F908: Keep all essential equipment working safely.
Short Summary

The facility did not maintain its dishwasher in working order over multiple extended periods, as documented in temperature logs and confirmed by staff interviews and surveyor observations. Due to recurring mechanical and chemical-dispensing problems, the dishwasher was frequently out of service, and technicians were repeatedly called for repairs. As a result, all meals were served in disposable Styrofoam containers with plastic utensils, and a resident reported difficulty cutting food and cutting through the container while eating. These conditions were inconsistent with the facility’s sanitization policy requiring equipment to be kept in good repair.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Safe, Functional Kitchen Equipment
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

Surveyors found that essential kitchen equipment was not kept in safe, working order. A high-temperature dishwasher was observed leaking significantly, with water running down a wall near electrical outlets and pooling on the floor where staff stood while operating it, despite multiple critical work orders being marked as completed and staff reporting the leak had persisted for weeks. In addition, a commercial food processor used for pureed foods was missing a key cover component, leading staff to improvise with aluminum foil, which allowed soup to spray onto surrounding surfaces and dishes; staff reported the part had been missing for several weeks while corporate dietary staff were still in the process of obtaining replacement parts.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Safe, Functional Kitchen Refrigeration and Ovens
F
F0908 F908: Keep all essential equipment working safely.
Short Summary

Surveyors found that essential kitchen equipment, including a walk-in refrigerator and both ovens, was not maintained in safe operating condition, potentially affecting all 38 residents. The walk-in refrigerator had documented temperatures above safe cold-holding levels over multiple days, with missing temperature entries and no documented food temperature checks or discarding of potentially affected food, despite staff awareness that the unit was in the 50s. The Administrator and Maintenance staff reported delayed notification of the refrigerator problem. Additionally, both kitchen ovens were nonfunctional for an extended period, one having suffered internal fire damage and the other experiencing recurrent failures since purchase, with ongoing electrical and equipment issues despite prior repair attempts.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Inadequate Handwashing Facilities in Kitchen
F
F0908 F908: Keep all essential equipment working safely.
Short Summary

Surveyors found that kitchen staff did not have access to adequate handwashing facilities while food was being prepared for most residents. One dietary staff member was observed cooking while the front kitchen handwashing sink had no running water, and the back sink lacked soap. The staff member suggested using a pot-filling spigot for handwashing and obtained paper towels from a food preparation area because none were stocked at the front sink. The dietary manager later reported he was unaware the front sink was not working, despite facility policy requiring accessible sinks, soap, and towels.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Safe and Functional Heating in Common Areas
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

The facility did not maintain its boiler in working condition, resulting in low temperatures throughout common areas such as hallways, dining rooms, and lounges. Residents were observed bundled in coats and blankets, and auxiliary heaters were used but were often ineffective. While PTAC units were installed in resident rooms, common areas remained inadequately heated, and staff confirmed ongoing temperature issues and equipment malfunctions.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

65.1% of Ohio facilities received at least one citation during their inspection in the last 12 months.Will yours be survey-ready?

Surveyors issued 55 serious citations across Ohio in the last 12 months. See exactly what they're citing.

Get ready for your next survey

See what surveyors are citing in Ohio and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release May 27, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙