K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
F

Failure to Provide Required Emergency Lighting in Generator ATS Room

Corewell Health Rehabilitation & Nursing Center -Stevensville, Michigan Survey Completed on 03-04-2025

Summary

The facility failed to maintain its generator in accordance with NFPA 110 requirements. During an observation, it was found that there was no battery back-up light installed in the electrical room containing the generator Automatic Transfer Switch (ATS), as required by NFPA 110, section 7.3. This deficiency was identified through direct observation and confirmed in an interview with the Maintenance Technician at the time of discovery. The lack of a battery back-up light in the generator ATS room could potentially affect all occupants of the facility, as it would result in no emergency lighting in the event of a generator failure, leaving no lighted access to emergency equipment. The report does not mention any specific residents or staff affected at the time of the deficiency, nor does it provide details about their medical history or condition.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0918 citations
Failure to Perform and Document Annual Main and Feeder Breaker Testing
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors found that the facility failed to perform and/or document required annual testing and exercising of main and feeder circuit breakers in accordance with NFPA 99 and manufacturer recommendations. During record review, no documentation could be produced to show that the annual breaker exercises had been completed, and the Director of Facilities acknowledged this lack of records. This deficiency relates to the essential electrical system that supports life safety and critical branches during emergencies.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Document Essential Electrical System Testing
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors identified that the facility did not maintain required documentation for 1.5-hour load bank testing, monthly generator load testing, weekly voltage checks, or monthly conductance testing for generator batteries. These omissions were confirmed during a record review and acknowledged by facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Emergency Generator Control Board
E
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

A deficiency was identified when the facility did not provide documentation that the main control board of one emergency generator, flagged for replacement during annual maintenance, had been corrected. This issue was confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Emergency Generator Annunciator Panel
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

The facility did not maintain the emergency generator annunciator panel, which was found to be without power and nonfunctional during testing at the first floor Nurses Station. This deficiency was confirmed by the Administrator and Maintenance Director, impacting the facility's ability to monitor emergency power systems as required.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Emergency Generator Maintenance and Testing
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors found that the facility did not provide documentation verifying that required weekly inspections, monthly testing, and annual testing of the emergency generator were performed in the past year. The Administrator confirmed the absence of these records, affecting the entire emergency electrical system.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Four-Hour Emergency Generator Load Test
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors found that the facility did not have documentation showing its emergency generator had undergone a required four-hour continuous load test within the past 36 months. Administrative and maintenance staff were unable to provide evidence of compliance, and the only available service report showed a test duration of just over three hours, not meeting regulatory standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release May 27, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙