K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
F

Incomplete Fire Damper Testing Documentation in HVAC System

King Nursing & Rehabilitation CommunityHoughton Lake, Michigan Survey Completed on 04-14-2025

Summary

The facility failed to ensure that its heating, ventilation, and air conditioning (HVAC) systems were in compliance with National Fire Protection Association (NFPA) standards. During a review of facility records, it was found that documentation for the required 4-year testing of fire dampers, as specified by NFPA 80, was incomplete. A vendor report dated March 14, 2025, showed that only 15 out of 30 fire dampers had been inspected or tested. An additional vendor report from August 9, 2022, indicated that only 8 fire dampers were inspected and all passed. These findings were confirmed through an interview with the Maintenance Assistant during the record review.

Plan Of Correction

K521 #1 The missing report was obtained and placed in the Life Safety Manual to ensure all 30 items were tested. #2 All residents have the potential to be affected by this deficiency. Any deficiencies identified will be corrected by Summit Fire Protection on 5/22/25. #3 The Maintenance Director was educated on providing all paperwork as proof that the heating, ventilation and air conditioning is in compliance with NFPA and paperwork will be kept in the Life Safety Manual. #4 Any further heating, ventilation and air conditioning shall continue to stay in compliance with NFPA and paperwork will be provided and put in Life Safety Manual. #5 It will be the responsibility of the Maintenance Director and Administrator to insure sustained compliance.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0521 citations
Lack of Required Inspection and Testing Documentation for Fire Dampers
F
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

Surveyors determined that the facility did not maintain required documentation showing that fire dampers had been inspected and tested in accordance with NFPA 101, NFPA 90A, and NFPA 80 standards. During record review, no inspection or testing records were produced despite multiple requests, even though fire dampers were observed throughout the building. The Maintenance Director confirmed that the documentation was not available, and this deficiency had the potential to affect all 69 residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Address Fire Damper Deficiencies in HVAC System
E
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

Surveyors identified that the facility did not maintain required inspections or corrective actions for fourteen fire and smoke dampers in the HVAC system, with issues such as non-functioning motors, missing dampers, and inadequate fire wall protection remaining unaddressed at the time of survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Address Failed Fire Dampers in HVAC System
E
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

The facility did not maintain its HVAC system as required, as two failed fire dampers were identified in an inspection report and there was no evidence of corrective action taken at the time of the survey. This was confirmed by facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Venting of Portable Air Conditioning Unit
E
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

A portable air conditioning unit in a large common area near the Nurses' Station was observed to be vented directly into the ceiling's interstitial space instead of to the outside, contrary to NFPA 101 and manufacturer requirements. This was confirmed by facility leadership during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Exercise Fire Dampers at Required Intervals
F
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

Surveyors determined that the facility did not provide documentation showing fire dampers were exercised within the required four-year interval, as confirmed by the Maintenance Director during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Documentation and Final Inspection for Newly Installed Boiler
F
K0521 K521: Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Short Summary

A newly installed boiler heating unit was found to lack manufacturer information and proof of state inspection. The facility could not provide documentation that required corrections identified by a state boiler inspector had been completed, and a final inspection had not been requested.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Michigan

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Michigan — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙