Stay Ahead of Compliance with Monthly Citation Updates


In your State Survey window and need a snapshot of your risks?

Survey Preparedness Report

One Time Fee
$79
  • Last 12 months of citation data in one tailored report
  • Pinpoint the tags driving penalties in facilities like yours
  • Jump to regulations and pathways used by surveyors
  • Access to your report within 2 hours of purchase
  • Easily share it with your team - no registration needed
Get Your Report Now →

Monthly citation updates straight to your inbox for ongoing preparation?

Monthly Citation Reports

$18.90 per month
  • Latest citation updates delivered monthly to your email
  • Citations organized by compliance areas
  • Shared automatically with your team, by area
  • Customizable for your state(s) of interest
  • Direct links to CMS documentation relevant parts
Learn more →

Save Hours of Work with AI-Powered Plan of Correction Writer


One-Time Fee

$49 per Plan of Correction
Volume discounts available – save up to 20%
  • Quickly search for approved POC from other facilities
  • Instant access
  • Intuitive interface
  • No recurring fees
  • Save hours of work
K0918
F

Failure to Document Required Generator Battery Testing

Fremont, Michigan Survey Completed on 04-09-2025

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Summary

The facility failed to document a required battery test during the monthly inspection of its generators. Specifically, the monthly test did not include either the specific gravity fluids or the cold crank amperage for maintenance-free batteries, as required to ensure the operational condition of the generator cells. This omission was identified during a record review conducted on April 9, 2025, and was confirmed through an interview with the facility Maintenance Director at the time of observation. The deficiency pertains to non-compliance with NFPA 110, which mandates that such battery tests be part of the monthly generator inspection. The lack of documentation and testing could potentially affect all occupants and staff in the event of a failed generator battery during a main utility power loss, as the operational readiness of the emergency power source could not be verified.

Plan Of Correction

K918 Electrical Systems Element 1: Facility purchased tester for generator battery. Battery tested and is in operational condition. Element 2: Residents that reside in the facility have the potential to be affected by this deficient practice. Element 3: The Maintenance Department was educated by the Nursing Home Administrator on monthly generator inspections to include a documented battery test. Element 4: Facility generator checks will be audited monthly for 4 months to ensure monthly generator inspections include a documented battery test. Variances will be corrected as indicated. Audit results will be forwarded to the facility's quality assurance committee for review and further recommendations. Additional education and monitoring will be initiated for any identified concerns. Facility Administrator will be responsible for sustained compliance.