F0908 F908: Keep all essential equipment working safely.
F

Kitchen Water Heater Malfunction Leads to Inadequate Dish Machine Temperatures

Lanier Rehabilitation CenterJacksonville, Florida Survey Completed on 02-20-2025

Summary

The facility failed to maintain the kitchen's mechanical equipment in safe operating condition, specifically the water heater, which was not functioning. This resulted in the dish machine's wash and rinse temperatures not reaching the manufacturer's specified levels. During a kitchen tour, it was observed that the dish machine's temperature did not exceed 69 degrees Fahrenheit during both the wash and rinse cycles. The Certified Dietary Manager (CDM) explained that the facility had been using a low-temperature dish machine with chlorine bleach for sanitization, and they attempted to use hot water from a coffee machine to compensate for the lack of hot water from the water heater. Interviews with the CDM and the Maintenance Director revealed that the water heater had been out of order for several weeks to a couple of months. The facility had received the correct replacement water heater, but installation was delayed due to the unavailability of the contracted maintenance provider. The Maintenance Director noted that the previous water heater had rusted through, and there were multiple delays in receiving the correct replacement. The manufacturer's specifications for the dish machine required a minimum incoming temperature of 120 degrees Fahrenheit, which was not met due to the water heater's malfunction.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0908 citations
Kitchen Dishwashing System Leak Not Maintained
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

The facility failed to keep a kitchen dishwashing system in good working order when surveyors observed water flowing from a metal device under the counter, with buckled tile and peeled-back wall trim nearby. A kitchen staff member said maintenance had known about the leak for about a month, and maintenance later confirmed the issue had not been reported through the TELS system and that the damage was not new.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lint Buildup in Dryer Lint Trap
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Lint Buildup in Dryer Lint Trap: One of two dryers was observed running with lint buildup in the lint trap after the lint door was opened during a laundry tour. The MSS stated the lint trap should be cleaned every 2 hours for fire safety, and an LA stated she forgot to clean Dryer 2's lint trap. Facility policy required laundry equipment to be maintained per manufacturer instructions and kept in a safe, operable condition.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Refrigeration Not Maintained in Working Condition
F
F0908 F908: Keep all essential equipment working safely.
Short Summary

Essential kitchen equipment was not kept in good working condition. A large kitchen refrigerator had standing water on the bottom shelf and water dripping from the top onto covered food, and a resident refrigerator freezer had heavy ice buildup with a splintered gasket that did not attach well. The ADON and Maintenance Director both verified the equipment problems, and the MD stated the refrigerator was not working properly and needed repaired.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Dishwasher Thermometer Inaccurate and Temperatures Below Required Level
F
F0908 F908: Keep all essential equipment working safely.
Short Summary

Dishwasher Thermometer Inaccurate and Temps Below Required Level: The low-temp dishwasher was observed with wash and rinse temps below the facility's required 120F minimum, and the DS stated staff had to handwash dishes while the machine was out of order. The MS later found the machine's thermometer was not reading accurately, with the manual thermometer showing 135.1F while the machine read 118F, and the DS said the length of time the thermometer had been inaccurate was unknown.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Equipment Not Maintained in Safe Operating Condition
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

Kitchen equipment was not maintained in safe operating condition. A plate warmer was plugged in but only held room-temperature plates, and staff said it had not warmed plates since the prior week or earlier. A dishwasher temperature gauge was also faulty, reading 110F while a separate gauge showed the water was 122F during operation. The Maintenance Director said he had not been notified of either issue and found no June maintenance entries for the plate warmer or dishwasher gauge.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Equipment Not Maintained in Working Order
F
F0908 F908: Keep all essential equipment working safely.
Short Summary

Kitchen equipment was not maintained in proper working order, affecting nearly all residents who received meals from the kitchen. Surveyors observed significant ice buildup in two reach-in freezers, including on food products, and found the garbage disposal covered. Dietary staff said the disposal had been broken for about a year, and the DM reported the freezers were constantly in defrost with possible door seal problems. Maintenance confirmed the disposal needed replacement and said approval was delayed because the facility was being sold.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Florida

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Florida — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release August 26, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.