K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
E

Hazardous Area Door Gap Deficiency

Gardens At York Terrace, ThePottsville, Pennsylvania Survey Completed on 12-18-2024

Summary

The facility failed to maintain the hazardous area doors within the allowed gap margins in one of the four smoke zones. Specifically, during an observation on December 18, 2024, at 12:10 PM, it was noted that the Kitchen Storage Room door had a gap at the top that exceeded the minimum allowed margin by 3/16-inch. This deficiency was confirmed during an interview at the exit conference with the Administrator and Director of Maintenance on the same day at 1:15 PM.

Plan Of Correction

The facility to correct the kitchen door by utilizing a door adjustor to meet the gap requirement. An audit of all hazardous doors will be audited to ensure compliance. The facility will complete a random audit of the hazardous doors quarterly. Education provided to maintenance staff regarding hazardous door requirements. The findings from the audits will be reported to QAPI for 6 months.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0321 citations
Failure to Maintain Self-Closing Doors for Multiple Hazardous Storage Areas
F
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

Surveyors found that multiple hazardous storage areas, including a closet near medical records, a beauty salon used to store chemical cases, a supply room in one nursing station, a room leading to a smoking area, a housekeeping room near therapy, and a lobby storage room, lacked required self-closing or automatic-closing doors. These conditions did not comply with NFPA 101 requirements for hazardous area enclosure and had the potential to affect all residents and staff in an emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Soiled Linen Room Door Failed to Latch in Hazardous Area
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

Surveyors found that the common area soiled linen room on the second floor, classified as a hazardous area in a sprinklered location, had a door that failed to positively latch when tested. This door is required to self-close and latch to maintain proper separation for hazardous areas. The issue was confirmed with the Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Fire Barrier Door Closure in Hazardous Area
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

A faulty door closure was observed on the South Nurses' Station and Food Storage Room, resulting in the door failing to automatically close and latch as required for hazardous area enclosures. This deficiency was confirmed by the DON and Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Self-Closing and Latching Door in Hazardous Area
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

Surveyors found that the door to a third-floor trash room, classified as a hazardous area, did not self-close or positively latch as required. This issue was confirmed by facility staff during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Hazardous Area Door Failed to Self-Close and Latch
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

A deficiency was found when the A Hall Resident Care Supply room door did not self-close to a positive latch as required by LSC 8.7.1.3, leaving a hazardous area inadequately protected according to fire safety standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Hazardous Area Door Deficiencies and Improper Hold-Open Devices
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

Surveyors identified that hazardous area doors, including the Sprinkler Tank Room and 1st floor Dietary Storage Room, were not maintained within required gap margins and were held open with unauthorized devices, as confirmed by the Director of Facilities.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙