Hazardous Area Door Deficiencies and Improper Hold-Open Devices
Penalty
Summary
The facility failed to maintain hazardous area doors in accordance with required safety standards in two of ten smoke zones. Specifically, during an observation, the Sprinkler Tank Room door (1A29D) was found to have gaps greater than 3/16 inch, which exceeds the allowed gap margins for such doors. This was confirmed by the Director of Facilities at the time of observation. Additionally, the 1st floor Dietary Storage Room rated doors (1B20) were observed being held open with manual hold-open drop downs, which are unauthorized devices. The Director of Facilities confirmed that these doors were being held open in this manner. These findings indicate that the facility did not ensure hazardous area doors were properly maintained to meet fire safety requirements.
Plan Of Correction
1. A rated door system will be installed on door 1A29D to maintain proper gap margins to less than 3/16". A recurring work order will be created to inspect the door for proper gap margins quarterly for one year. Completed work order documentation will be presented to QAPI for evaluation. 2. Manual hold open devices will be removed from doors 1B20. A recurring work order will be created to inspect doors for proper operation and positive latching quarterly for one year. Completed work order documentation will be presented to QAPI for evaluation.