K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
E

Failure to Maintain Hazardous Area Enclosure in Laundry Room

Quakertown CenterQuakertown, Pennsylvania Survey Completed on 02-10-2025

Summary

The facility failed to maintain a hazardous area enclosure, specifically in the laundry room, which affected one of the five smoke compartments in the facility. During an observation on February 10, 2025, at 11:00 a.m., it was noted that both doors of the laundry room were propped open with door wedges, preventing them from closing and latching as required. This deficiency was confirmed during an exit interview with the Administrator and Maintenance Director on the same day at 1:15 p.m.

Plan Of Correction

1) Laundry doors were closed and door wedges were removed. 2) Staff were educated that door wedges are not to be used in the facility. 3) Laundry rooms will be audited three times a week for 8 weeks, then monthly for two months. Results of the audit will be presented at the monthly QAPI meetings for review and or recommendations.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0321 citations
Failure to Maintain Self-Closing Doors for Multiple Hazardous Storage Areas
F
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

Surveyors found that multiple hazardous storage areas, including a closet near medical records, a beauty salon used to store chemical cases, a supply room in one nursing station, a room leading to a smoking area, a housekeeping room near therapy, and a lobby storage room, lacked required self-closing or automatic-closing doors. These conditions did not comply with NFPA 101 requirements for hazardous area enclosure and had the potential to affect all residents and staff in an emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Soiled Linen Room Door Failed to Latch in Hazardous Area
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

Surveyors found that the common area soiled linen room on the second floor, classified as a hazardous area in a sprinklered location, had a door that failed to positively latch when tested. This door is required to self-close and latch to maintain proper separation for hazardous areas. The issue was confirmed with the Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Fire Barrier Door Closure in Hazardous Area
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

A faulty door closure was observed on the South Nurses' Station and Food Storage Room, resulting in the door failing to automatically close and latch as required for hazardous area enclosures. This deficiency was confirmed by the DON and Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Self-Closing and Latching Door in Hazardous Area
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

Surveyors found that the door to a third-floor trash room, classified as a hazardous area, did not self-close or positively latch as required. This issue was confirmed by facility staff during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Hazardous Area Door Failed to Self-Close and Latch
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

A deficiency was found when the A Hall Resident Care Supply room door did not self-close to a positive latch as required by LSC 8.7.1.3, leaving a hazardous area inadequately protected according to fire safety standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Hazardous Area Door Deficiencies and Improper Hold-Open Devices
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

Surveyors identified that hazardous area doors, including the Sprinkler Tank Room and 1st floor Dietary Storage Room, were not maintained within required gap margins and were held open with unauthorized devices, as confirmed by the Director of Facilities.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙