K0241 K241: Have correct number of accessible exits for each story.
C

Deficiency in Required Exits for Smoke Compartment

Nottingham VillageNorthumberland, Pennsylvania Survey Completed on 12-16-2024

Summary

The facility was found to be non-compliant with the National Fire Protection Association (NFPA) 101 standards regarding the number of exits required for each story and smoke compartment. Specifically, the deficiency was identified in one of the ten smoke compartments within the facility. During an observation conducted on December 16, 2024, at 10:00 a.m., it was noted that the basement level of the facility did not have two acceptable means of egress as required. This finding was confirmed during an exit interview with the Facility Administrator on the same day at 12:00 p.m.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0241 citations
Failure to Provide Required Number of Exits in Basement
B
K0241 K241: Have correct number of accessible exits for each story.
Short Summary

A surveyor observed that the basement had only a single exit, and the Administrator confirmed the lack of at least two remote exits, resulting in noncompliance with NFPA 101 requirements for exit accessibility in smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Provide Required Number of Basement Exits
E
K0241 K241: Have correct number of accessible exits for each story.
Short Summary

Surveyors found that the facility basement, which houses the laundry, employee break room, maintenance office, boiler room, storage, electrical room, and employee bathroom/locker room, had only one exit instead of the two required by NFPA 101. This deficiency was confirmed by interviews with facility leadership and could affect about 10 occupants in an emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Insufficient Exits in Basement Maintenance and Mechanical Areas
D
K0241 K241: Have correct number of accessible exits for each story.
Short Summary

A deficiency was identified when it was observed that the basement maintenance shop and mechanical room had only one exit, failing to meet the requirement for at least two remote and accessible exits from every part of every story and smoke compartment. This was confirmed by the Maintenance Director and could affect three occupants in the event of a fire.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Facility Lacks Two Acceptable Exits in Basement
B
K0241 K241: Have correct number of accessible exits for each story.
Short Summary

The facility was found to lack two acceptable emergency exits in the basement, as the north exit is a communicating stair that does not lead to an exterior exit discharge. This deficiency was confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-Compliance with NFPA 101 Exit Requirements
B
K0241 K241: Have correct number of accessible exits for each story.
Short Summary

The facility failed to comply with NFPA 101 requirements by not providing at least two remote exits for two of its smoke compartments. Observations revealed that the 2nd floor Annex and the basement lacked the necessary exits. This was confirmed by the Maintenance Manager.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiency in Fire Exit Compliance
C
K0241 K241: Have correct number of accessible exits for each story.
Short Summary

The facility was found non-compliant with NFPA 101 requirements for exits, lacking two approved exits remote from each other for each floor. The existing exit strategy relied on a central stairway, confirmed during interviews with the Administrator and Maintenance Director. A follow-up visit confirmed the issue remained unresolved, with the facility working towards obtaining an FSES.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

65.1% of Ohio facilities received at least one citation during their inspection in the last 12 months.Will yours be survey-ready?

Surveyors issued 55 serious citations across Ohio in the last 12 months. See exactly what they're citing.

Get ready for your next survey

See what surveyors are citing in Ohio and spot your risk areas before they do.

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release May 27, 2026) and official state health department websites — never guesswork.

Find your facility

Search by name to see its inspection history, citations and penalties — and how to prepare for the next survey.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙