K0241 K241: Have correct number of accessible exits for each story.
B

Failure to Provide Required Number of Exits in Basement

Kadima Rehabilitation & Nursing At PalmyraPalmyra, Pennsylvania Survey Completed on 07-29-2025

Summary

During an observation conducted on July 29, 2025, at 11:50 AM, it was found that the basement of the facility had only a single exit. This was confirmed in an interview with the Administrator at the same time, who acknowledged that the basement did not have at least two exits remote from each other. The deficiency affects one of two smoke compartments within the component, as the facility failed to provide not less than two exits, remote from one another, for each floor as required by NFPA 101 standards.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0241 citations
Failure to Provide Required Number of Basement Exits
E
K0241 K241: Have correct number of accessible exits for each story.
Short Summary

Surveyors found that the facility basement, which houses the laundry, employee break room, maintenance office, boiler room, storage, electrical room, and employee bathroom/locker room, had only one exit instead of the two required by NFPA 101. This deficiency was confirmed by interviews with facility leadership and could affect about 10 occupants in an emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Insufficient Exits in Basement Maintenance and Mechanical Areas
D
K0241 K241: Have correct number of accessible exits for each story.
Short Summary

A deficiency was identified when it was observed that the basement maintenance shop and mechanical room had only one exit, failing to meet the requirement for at least two remote and accessible exits from every part of every story and smoke compartment. This was confirmed by the Maintenance Director and could affect three occupants in the event of a fire.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Facility Lacks Two Acceptable Exits in Basement
B
K0241 K241: Have correct number of accessible exits for each story.
Short Summary

The facility was found to lack two acceptable emergency exits in the basement, as the north exit is a communicating stair that does not lead to an exterior exit discharge. This deficiency was confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-Compliance with NFPA 101 Exit Requirements
B
K0241 K241: Have correct number of accessible exits for each story.
Short Summary

The facility failed to comply with NFPA 101 requirements by not providing at least two remote exits for two of its smoke compartments. Observations revealed that the 2nd floor Annex and the basement lacked the necessary exits. This was confirmed by the Maintenance Manager.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiency in Fire Exit Compliance
C
K0241 K241: Have correct number of accessible exits for each story.
Short Summary

The facility was found non-compliant with NFPA 101 requirements for exits, lacking two approved exits remote from each other for each floor. The existing exit strategy relied on a central stairway, confirmed during interviews with the Administrator and Maintenance Director. A follow-up visit confirmed the issue remained unresolved, with the facility working towards obtaining an FSES.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Facility Lacks Second Acceptable Exit from Center Building
C
K0241 K241: Have correct number of accessible exits for each story.
Short Summary

The facility failed to provide two acceptable exits from each floor of the Center Building, affecting the entire building component. All three floors lacked a second acceptable means of exiting, with existing routes consisting exclusively of horizontal exits into adjacent healthcare buildings, not meeting NFPA 101 standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙