Life Care Center Of Winter Haven
Inspection history, citations, penalties and survey trends for this long-term care facility in Winter Haven, Florida.
- Location
- 1510 Cypress Gardens Blvd, Winter Haven, Florida 33884
- CMS Provider Number
- 105792
- Inspections on file
- 16
- Latest survey
- February 20, 2025
- Citations (last 12 mo.)
- 0
Citation history
Health deficiencies cited at Life Care Center Of Winter Haven during CMS and state inspections, most recent first.
The facility failed to provide dignified care and dining services to residents, including improper meal assistance positioning, unauthorized use of clothing protectors, and staff speaking in different languages during care, causing discomfort to residents.
The facility failed to provide adequate foot care for three diabetic residents, leading to deficiencies in care. One resident experienced pain due to untrimmed toenails, despite having an active podiatry consult. Another resident had long, thickened toenails and a fungal infection, with delayed podiatry intervention. A third resident had long, thick, yellow toenails, with staff acknowledging the need for podiatry care but failing to provide timely intervention. The facility's policy on nail care for diabetic residents was not followed, contributing to the deficiencies.
A long-term care facility experienced a medication error rate of 42.42%, significantly exceeding the acceptable threshold of 5%. Errors included incorrect medication administration, failure to notify physicians of late medications, and improper documentation. Staff failed to follow facility policies, such as crushing enteric-coated tablets, not priming insulin pens, and administering medications without physician parameters. The Director of Nursing acknowledged these deficiencies, highlighting a need for adherence to established protocols.
The facility failed to assess two residents for self-administration of medications and did not obtain physician orders for medications observed in one resident's room. A resident was seen using a nebulizer without a physician order, and another had throat spray and ointment without orders. The facility's policy required assessments and documentation for self-administration, which were not followed.
A resident reported missing clothes to the facility, but no grievance was filed, violating the resident's right to voice grievances. The resident, with intact cognition, was not informed about the grievance process. The Director of Housekeeping was aware of the complaint but did not assist in filing a grievance, contrary to the facility's policy.
A facility failed to provide timely written notification to a resident and their representative before an emergency hospital transfer due to a medical condition. The required notice was not documented until after the transfer, contrary to facility policy, as confirmed by staff interviews.
The facility failed to accurately complete PASRR documentation for multiple residents, omitting diagnoses such as dementia and Alzheimer's disease. This resulted in incomplete Level I screenings and the absence of required Level II evaluations, contrary to facility policy and regulatory requirements.
A facility failed to provide wound care as ordered for a resident with diabetes and skin disorders. During an observation, a nurse found the resident's foot wounds uncovered, contrary to physician orders. The care plan required prompt treatment of skin breaks, and orders specified dressing procedures. Despite the resident's tendency to remove dressings, the facility did not adhere to its policy on treatment orders, resulting in a deficiency.
A facility failed to obtain timely physician-ordered lab tests for a resident with hypothyroidism. The resident was on Levothyroxine and had orders for TSH, Free T4, and PTH tests, which were not completed as required. Documentation showed partial administration and order clarification issues, with thyroid panel results only obtained 30 days after the order was discontinued. The DON stated labs should be done promptly, with the lab vendor visiting daily except Sundays.
An LPN failed to clean a blood pressure cuff between uses on two residents during medication administration, leading to a breach in infection control protocols.
Failure to Provide Dignified Care and Dining Services
Penalty
Summary
The facility failed to ensure residents were provided dining services and care with dignity, affecting four residents. Resident #63, who had hemiplegia and feeding difficulties, was observed being assisted with meals by a CNA who stood over her instead of sitting at eye level, as per facility policy. The CNA admitted to standing due to the need to assist multiple residents simultaneously, and there was a lack of clear communication among staff regarding the proper positioning during meal assistance. Resident #2 was observed being given a clothing protector without consent, and a napkin was tucked into the neckline without prior discussion or inclusion in the care plan. The resident had severe cognitive impairment, and the care plan did not reflect any choice regarding the use of clothing protectors. The facility's policy required staff to sit while assisting residents with meals, but this was not consistently followed. Residents #26 and #72 reported feeling uncomfortable when staff spoke in languages other than English during care. Resident #26, who had intact cognition, felt abused when staff switched languages upon realizing she understood French. Resident #72, also with intact cognition, reported similar incidents. The facility's mission statement emphasized dignity and resident-centered care, but these incidents contradicted those values, as residents felt their preferences and comfort were not prioritized.
Deficiency in Foot Care for Diabetic Residents
Penalty
Summary
The facility failed to provide proper foot care and treatment to maintain good foot health for three residents, leading to deficiencies in care. Resident #134, who has Type 2 Diabetes Mellitus and difficulty walking, repeatedly requested assistance with toenail care due to pain but was not attended to. Despite having an active podiatry consult, staff failed to ensure the resident received the necessary care. Observations revealed that the resident's toenails were protruding through his socks, and staff interviews indicated a lack of communication and follow-up regarding the resident's requests and needs. Resident #141, also with Type 2 Diabetes Mellitus, was observed with long, thickened toenails and a fungal infection on her fingernails. The resident expressed dissatisfaction with the lack of nail care since admission. Although a podiatry consult was eventually made, the staff failed to address the resident's nail care needs promptly. The resident's care records did not reflect the condition of her nails, and there was no documentation of appropriate interventions or assessments. Resident #140, another diabetic resident, was found with long, thick, and yellow toenails. The staff acknowledged the need for podiatry care but did not provide timely intervention. The facility's policy on nail care for residents with diabetes was not followed, as staff did not ensure the resident's toenails were maintained according to professional standards. The lack of proper foot care and communication among staff contributed to the deficiencies observed in the care of these residents.
High Medication Error Rate in LTC Facility
Penalty
Summary
The facility failed to maintain a medication error rate below 5%, with a reported rate of 42.42% based on observations of medication administration. During the survey, multiple instances of medication errors were identified involving six residents. These errors included incorrect medication administration, failure to administer medications as per physician orders, and improper documentation of medication administration. For instance, a Licensed Practical Nurse (LPN) crushed an enteric-coated aspirin instead of administering a chewable tablet as ordered for a resident with coronary artery disease. Additionally, the same LPN documented the administration of medications that were not given, such as Docusate Sodium and Hydralazine, without proper physician parameters for holding the medication. Another incident involved a Registered Nurse (RN) administering medications late without notifying the physician, as required by facility policy. The RN dispensed medications for a resident, including psychotropic and anticoagulant medications, which were scheduled for earlier administration. The facility's policy mandates that the physician be notified of late medication administration, but this was not done. Furthermore, the RN failed to administer a prescribed medication, Sertraline, after it was accidentally discarded, and did not document the incident appropriately. Additional errors were observed with other residents, including the improper disposal of medications, failure to prime insulin pens before administration, and incorrect medication administration based on blood pressure readings without physician orders. The Director of Nursing acknowledged these errors, stating that the facility's policy requires accurate documentation and adherence to physician orders. The facility's policies on medication administration and blood glucose monitoring were not followed, contributing to the high medication error rate.
Failure to Assess and Obtain Orders for Self-Administration of Medications
Penalty
Summary
The facility failed to ensure that two residents were assessed for self-administration of medications and did not obtain physician orders for medications observed in one resident's room. Resident #49 was observed using a nebulizer without a physician order for self-administration. The resident's medical history included unspecified dementia and chronic obstructive pulmonary disease (COPD). The care plan for Resident #49 did not include any focus or intervention for self-administration of medication, and the facility did not provide a self-administration assessment for this resident. Resident #141 was observed with a bottle of throat spray and mentholated topical ointment on the over-bed table within reach, without a physician order for their use. The resident confirmed using the throat spray and ointment when feeling unwell. Staff were unaware of these items at the resident's bedside, and no physician order was found for self-administration of these medications. The facility reported that no residents were self-administering medications at the time. The facility's policy on self-administration of medications required an assessment by the interdisciplinary care team to determine if self-administration was safe and clinically appropriate. The policy also required documentation in the resident's care plan and medication administration record. However, these procedures were not followed for the residents involved, leading to the deficiency.
Failure to File Grievance for Missing Clothes
Penalty
Summary
The facility failed to file a grievance related to missing clothes for a resident, which was a violation of the resident's right to voice grievances without discrimination or reprisal. During observations, the resident was seen sitting on her bed and reported that she had complained about her missing clothes, but no action had been taken. The resident also stated that she was not informed about the grievance process. The resident had intact cognition, as indicated by a BIMS score of 15, and had been readmitted to the facility with diagnoses including fractures and hip pain. Interviews with staff revealed that the Director of Housekeeping was aware of the resident's complaint about missing clothes but did not assist in filing a grievance. The Nursing Home Administrator expected grievances to be filed when complaints were brought to staff attention, but this did not occur in this case. The facility's grievance policy, which was supposed to be provided to residents upon request, outlined the right to file grievances and the procedure for handling them, including follow-up with residents to ensure satisfaction. However, this policy was not followed, leading to the deficiency.
Failure to Provide Timely Transfer Notification
Penalty
Summary
The facility failed to provide written notification to a resident and their representative prior to an emergency transfer to a hospital. The resident, who was their own responsible party, was transferred due to a large abscess on the neck and swallowing issues. The transfer occurred without the required written notice being given to the resident or their representative, as confirmed by the Executive Director and the Social Service Director. The facility's policy requires that notice be provided as soon as practicable before a transfer, but in this case, the notice was not documented until after the transfer had already taken place. Interviews with staff, including a Licensed Practical Nurse and the Director of Nursing, revealed that the written notice was not provided to the resident prior to the transfer. The notice was signed by staff after the resident had left the facility, and the facility's policy was not followed. The Social Service Director later provided a transfer notice dated the day of the transfer, but it was signed the following day, indicating a failure to adhere to the policy of providing timely notification.
Inaccurate PASRR Documentation for Multiple Residents
Penalty
Summary
The facility failed to ensure that the Preadmission Screening and Resident Review (PASRR) was completed accurately for eleven residents. These residents had various diagnoses, including dementia, Alzheimer's disease, major depressive disorder, and anxiety disorder, which were not accurately reflected in their PASRR documentation. For instance, Resident #112 was admitted with diagnoses including major depressive disorder and dementia, but the PASRR did not reflect the dementia diagnosis. Similarly, Resident #144's PASRR did not include the diagnosis of Cognitive Communication Deficit, and questions related to dementia were incorrectly answered. The report highlights that several residents, such as Resident #21, had diagnoses of epilepsy and dementia that were not included in their PASRR documentation. Despite having active diagnoses of these conditions, the PASRR screenings were incomplete, and necessary Level II evaluations were not conducted. Staff Q, a social worker, was unaware of these omissions and acknowledged that the facility did not conduct dementia testing. This lack of awareness and incomplete documentation was a recurring issue for multiple residents, including Residents #12, #126, #140, #130, #23, #54, #18, and #49. The facility's policy on PASRR was not adhered to, as evidenced by the incomplete Level I screenings and the absence of required Level II evaluations for residents with qualifying diagnoses. The policy mandates that potential admissions be screened for serious mental disorders or intellectual disabilities, and any positive Level I screen should lead to a Level II evaluation by the state-designated authority. However, the facility failed to update PASRR documentation when new diagnoses were made, and there was a lack of communication with state authorities regarding significant changes in residents' conditions. This oversight resulted in the facility not meeting the regulatory requirements for PASRR screenings and evaluations.
Failure to Provide Wound Care as Ordered
Penalty
Summary
The facility failed to provide wound care in accordance with professional standards of practice and as ordered by the physician for a resident. During an observation, a registered nurse found that the resident's left foot wounds were not covered with dressings as required. The nurse checked the resident's footwear for bandages but found none and stated that the dressings would be replaced immediately. The resident had been admitted with diagnoses including diabetes mellitus and a disorder of the skin and subcutaneous tissue, which required careful monitoring and treatment of skin integrity. The resident's care plan included interventions to check for skin breaks and treat them promptly as ordered by the doctor. Physician orders specified the cleansing and dressing of the resident's foot wounds, with instructions to verify the placement of wound dressings during specific shifts. However, it was noted that the resident often removed the dressings, and rolled gauze was used to help secure them. Despite these measures, the facility's policy on treatment orders, which required adherence to physician orders and product instructions, was not followed, leading to the deficiency.
Failure to Obtain Timely Laboratory Testing for Resident
Penalty
Summary
The facility failed to obtain physician-ordered laboratory testing for a resident diagnosed with unspecified hypothyroidism. The resident was receiving Levothyroxine sodium daily, and there was an order for Thyroid-Stimulating Hormone (TSH), Free T4, and Parathyroid Hormone (PTH) to be drawn every night shift from January 6 to January 21. However, the laboratory testing was not completed as ordered, with documentation indicating that the tests were only partially administered and that there were issues requiring clarification of the order. Despite staff documentation indicating the tests were completed, the facility could not provide any thyroid panel results for the specified period. The resident's progress notes revealed multiple entries indicating the need for order clarification, and a provider's note from January 6 confirmed the plan to check PTH. The laboratory results for the thyroid panel were only obtained on February 19, approximately 30 days after the order was discontinued. During an interview, the Director of Nursing stated that the expectation was to get labs as soon as possible and described the process for ordering tests through the lab portal, noting that the laboratory vendor visited the facility daily except Sundays.
Infection Control Breach During Medication Administration
Penalty
Summary
The facility failed to ensure proper infection prevention and control practices during the administration of medications to two residents. On the morning of February 19, 2025, a Licensed Practical Nurse (LPN) was observed administering medications to Resident #149. The LPN used a blood pressure wrist cuff from the medication cart to measure the resident's blood pressure, which initially registered an error. A second attempt yielded a reading of 101/48, leading the LPN to withhold the resident's Lisinopril. After administering other medications, the LPN returned the blood pressure cuff to the medication cart without cleaning it. Subsequently, the same LPN was observed administering medications to Resident #218. The LPN retrieved the same blood pressure cuff from the medication cart and used it to measure the resident's blood pressure, obtaining a reading of 120/57. The LPN then administered the resident's medications, withholding Losartan, and returned the cuff to the cart. During an interview, the LPN confirmed using the same cuff for both residents without cleaning it between uses, acknowledging that the cuff should have been cleaned between residents to prevent cross-contamination.
Latest citations in Florida
Surveyors found that the facility’s only commercial cooking hood was not maintained in accordance with NFPA 101 and NFPA 96 requirements. During a kitchen tour with the Maintenance Director, the hood was observed to be not grease tight due to missing fire-resistant caulk, and the Maintenance Director acknowledged this condition at the time of the survey.
Surveyors found that the facility failed to comply with NFPA 99, NFPA 70, and NFPA 1 requirements for electrical equipment when, during a tour with the Maintenance Director, a power strip in the electrical room was observed being used as a permanent power source instead of a dedicated receptacle. The report states that this improper use of a relocatable power tap could lead to electrical hazards for residents and staff, and notes that extension cords and power strips are not to be used as substitutes for fixed wiring under the cited codes.
Surveyors found that the facility did not have documentation showing completion of the required annual 90‑minute test of emergency lighting. During record review and interview, the Director of Facilities confirmed that records of this annual test, required under NFPA 101 sections 19.2.9.1 and 7.9, were not available. This deficiency was cited as affecting all occupants in the event of a fire or other emergency.
Surveyors found that the facility failed to perform and/or document the required annual Duct Detector Differential testing for the fire alarm system in accordance with NFPA 101, NFPA 70, and NFPA 72. During record review and interviews with the Director of Facilities, no documentation could be produced to show that this annual testing had been completed, and the Director acknowledged the lack of records. This deficiency was cited as potentially affecting all occupants in the event of a fire or other emergency.
Surveyors found that the facility failed to perform and/or document required annual testing and exercising of main and feeder circuit breakers in accordance with NFPA 99 and manufacturer recommendations. During record review, no documentation could be produced to show that the annual breaker exercises had been completed, and the Director of Facilities acknowledged this lack of records. This deficiency relates to the essential electrical system that supports life safety and critical branches during emergencies.
Surveyors observed that an adapter was used to power a refrigerator in the kitchen and a refrigerator in the dining room manager's office was plugged into a power strip. The Director of Facilities confirmed both uses, which did not comply with NFPA 99 and NFPA 70 requirements prohibiting adapters and power strips from being used as substitutes for permanent wiring.
Surveyors found that food service operations failed to meet professional food safety standards in both the main and satellite kitchens. In the main kitchen, a cook’s facial hair was not fully covered, the handwashing sink did not initially provide warm water, wet-nested pans and dirty plate domes were stored for use, ice buckets were stained with mold-like discoloration, and the high-temp dishwasher failed to reach the required sanitizing temperature. In the satellite pantry, the dishwasher did not reach required wash temperatures, vents and cabinets above serving dishes had mold-like buildup and residue, floors were damaged and soiled, the dishwasher chemical cabinet was rusted, the AC filter was heavily soiled, the juice dispenser had debris near clean cups, and tray carts contained dirty sheet trays. During tray line observation, salad items were held above 41°F, and a pureed vegetable listed on the menu extension was not available on the line.
Two residents on physician-ordered modified diets (pureed and mechanical soft with nectar-thick liquids) were given Regular Menus listing items such as fresh fruit, salad greens, and grilled cheese that were not compatible with their diet orders. Both residents selected items from these Regular Menus, but the facility either could not provide the chosen foods due to diet restrictions or substituted different items (e.g., canned peach halves instead of fresh fruit), despite the residents’ expressed preferences. The RD and dietetic technician confirmed that Regular Menus were routinely provided to all residents, including those on mechanically altered diets, leading to menu choices that did not align with ordered diet consistencies.
Surveyors found that the facility did not follow physician-ordered therapeutic diets or provide prescribed Magic Cup nutritional supplements for several cognitively impaired residents. A resident on a pureed diet with honey-thick liquids was served a lunch without the ordered pureed vegetable, and tray line review on another day showed no pureed vegetables available despite the menu specifying them. Multiple residents with orders for Magic Cup supplements had these listed on their meal tickets but were instead served other desserts or received no supplement at all, while documentation on the MAR indicated full consumption. Dietary staff acknowledged responsibility for providing Magic Cups but could not explain why residents in the dining room did not receive them.
A resident with intact cognition and multiple cardiac and pulmonary diagnoses had clearly documented DNR orders, including signed advance directive forms and care plan entries confirming her wish to avoid resuscitation. During a cardiac emergency, a CNA found the resident unresponsive and notified an RN, who initiated a code blue response. Several RNs and LPNs transferred the resident to bed and began CPR without first verifying code status, despite one LPN asking and then leaving the room to check the record. Staff interviews and video review showed that chest compressions and use of a bag-valve mask continued for about 12 minutes until EMS arrived, even after staff learned the resident was DNR, and the physician confirmed the resident was already listed as DNR in the system, leading to an Immediate Jeopardy finding for failure to honor advance directives.
Commercial Cooking Hood Not Maintained Grease Tight per NFPA Standards
Penalty
Summary
Surveyors identified a deficiency involving the facility’s commercial cooking facilities. During a tour of the kitchen between 1:00 p.m. and 3:00 p.m. with the Maintenance Director, surveyors observed that the one commercial cooking hood in use was not grease tight. Specifically, the hood was missing required fire-resistant caulk, which is necessary for maintaining a grease-tight seal in accordance with NFPA 96 and NFPA 101 standards. The Maintenance Director acknowledged these findings at the time of observation. The deficiency was cited under NFPA 101 and NFPA 96 requirements for commercial cooking operations, which mandate that cooking equipment and associated hoods be protected and maintained in compliance with these fire and life safety codes.
Plan Of Correction
Preparation and/or execution of this plan does not constitute admission or agreement by the provider of the truth of the facts alleged or conclusions set forth on the statement of deficiencies. This plan of correction is prepared and/or executed solely because required. What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice? No residents were affected by this deficient practice. How you will identify other residents having potential to be affected by the same practice and what corrective actions will be taken; Commercial cooking hood system inspected; no additional deficient areas were identified. What measures will be put into place or what systematic changes will you make to ensure that the practice does not recur:Maintenance staff and Dietary staff education on proper use and reporting of issues related to cooking hood system.Verification of scheduled inspections and cleaning of cooking hood system by licensed vendor.How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put in place:The maintenance director/designee will complete weekly audits of cooking hood system for 4 weeks, then monthly for 2 months to ensure compliance. The findings will be reported to the Quality Assurance Performance Improvement Committee for ongoing compliance. Preparation and/or execution of this plan does not constitute admission or agreement by the provider of the truth of the facts alleged or conclusions set forth on the statement of deficiencies. This plan of correction is prepared and/or executed solely because required. What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice? No residents were affected by this deficient practice. How you will identify other residents having potential to be affected by the same practice and what corrective actions will be taken; Commercial cooking hood system inspected; no additional deficient areas were identified. What measures will be put into place or what systematic changes will you make to ensure that the practice does not recur; Maintenance staff and Dietary staff education on proper use and reporting of issues related to cooking hood system. Verification of scheduled inspections and cleaning of cooking hood system by licensed vendor. How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put in place; The maintenance director/designee will complete weekly audits of cooking hood system for 4 weeks, then monthly for 2 months to ensure compliance. The findings will be reported to the Quality Assurance Performance Improvement Committee for ongoing compliance.
Improper Use of Power Strip as Permanent Power Source in Electrical Room
Penalty
Summary
Surveyors identified a deficiency related to improper use of relocatable power taps (RPTs) and power strips in violation of NFPA 99, NFPA 70, and NFPA 1 requirements. During a facility tour conducted between 10:00 a.m. and 12:00 p.m. with the Maintenance Director, surveyors observed one power strip in the electrical room being used as a source of permanent power instead of being connected to a dedicated receptacle. The report notes that this use did not comply with standards that require extension cords and power strips not be used as a substitute for fixed wiring and that they be used only under specified conditions. The deficiency specifically concerns the facility’s failure to ensure that RPTs are maintained and used in accordance with NFPA 99 (2012 Edition) sections 10.2.3.6 and 10.2.4, and NFPA 70 (2011 and 2020 Editions) provisions governing flexible cords and temporary wiring, as well as NFPA 1 (2021 Edition) sections 11.1.2.2, 11.1.4.1, and 1.4.1. The report states that this condition could lead to electric hazards for residents and staff. No individual resident cases, medical histories, or specific clinical conditions are described in connection with this deficiency.
Plan Of Correction
What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice? No residents were affected by this deficient practice. How you will identify other residents having potential to be affected by the same practice and what corrective actions will be taken; Facility wide audit of electrical rooms was conducted to identify improper use of power strips. No additional concerns were identified. What measures will be put into place or what systematic changes you will make to ensure that the practice does not recur; The facility completed education reinforcing compliance with electrical safety requirements in accordance with National Fire Protection Association. How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put in place: The maintenance director/designee will complete random electrical safety audits 2 times per week for 4 weeks, then monthly to ensure compliance with electrical safety standards. The findings will be reported to the Quality Assurance Performance Improvement Committee for ongoing compliance. What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice? No residents were affected by this deficient practice. How you will identify other residents having potential to be affected by the same practice and what corrective actions will be taken; Facility wide audit of electrical rooms was conducted to identify improper use of power strips. No additional concerns were identified. What measures will be put into place or what systematic changes you will make to ensure that the practice does not recur; The facility completed education reinforcing compliance with electrical safety requirements in accordance with National Fire Protection Association. How the corrective action(s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put in place; The maintenance director/designee will complete random electrical safety audits 2 times per week for 4 weeks, then monthly to ensure compliance with electrical safety standards. The findings will be reported to the Quality Assurance Performance Improvement Committee for ongoing compliance.
Failure to Document Required Annual 90‑Minute Emergency Lighting Test
Penalty
Summary
Surveyors identified a deficiency related to emergency lighting when, during record review and staff interview between 11:30 AM and 3:00 PM with the Director of Facilities, the facility was unable to provide documentation that the required annual 90‑minute testing of emergency lighting had been performed. The Director of Facilities acknowledged that there was no documentation available to show completion of this annual 90‑minute emergency lighting test, as required by NFPA 101 (2012 and 2021 editions), sections 19.2.9.1 and 7.9. This failure to document the annual emergency lighting test was cited as a noncompliance that could affect all occupants of the facility in the event of a fire or other emergency. No specific residents, medical histories, or clinical conditions were mentioned in the report; the deficiency pertains to facility-wide life safety systems and their required testing and documentation.
Plan Of Correction
Emergency Lighting CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Emergency Lighting K0291 The facility immediately conducted a comprehensive inspection of all emergency lighting systems. On The Director of Facilities performed the required 90-minute annual testing of all emergency lighting units. Documentation of testing has been completed and is maintained on-site. 2. All areas of the facility were considered at risk due to lack of documented annual testing. A full facility-wide audit of all emergency lighting units was completed on by the Director of Facilities to ensure compliance. 3. The facility implemented a preventative maintenance schedule to ensure annual 90-minute emergency lighting testing is completed in accordance with NFPA 101 (2012), Section 7.9. A log tracking system has been developed to document all required testing. The Director of Facilities/designee will receive re-education on Life Safety Code requirements and documentation standards. 4. The Director of Facilities will review fire alarm testing records quarterly for 12 months, will present the findings for 12 months at Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the twelve months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required. Emergency Lighting CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Emergency Lighting K0291 The facility immediately conducted a comprehensive inspection of all emergency lighting systems. On The Director of Facilities performed the required 90-minute annual testing of all emergency lighting units. Documentation of testing has been completed and is maintained on-site. 2. All areas of the facility were considered at risk due to lack of documented annual testing. A full facility-wide audit of all emergency lighting units was completed on by the Director of Facilities to ensure compliance. 3. The facility implemented a preventative maintenance schedule to ensure annual 90-minute emergency lighting testing is completed in accordance with NFPA 101 (2012), Section 7.9. A log tracking system has been developed to document all required testing. The Director of Facilities/designee will receive re-education on Life Safety Code requirements and documentation standards. 4. The Director of Facilities will review fire alarm testing records quarterly for 12 months, will present the findings for 12 months at Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the twelve months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required.
Failure to Perform and Document Annual Duct Detector Differential Testing
Penalty
Summary
Surveyors identified a deficiency related to the facility’s fire alarm system testing and maintenance, specifically the required annual Duct Detector Differential testing. During record review conducted between 11:30 AM and 3:00 PM, surveyors requested documentation demonstrating that this annual testing had been completed in accordance with NFPA 101 (2012 and 2021 editions), NFPA 70, and NFPA 72. The facility was unable to produce records showing that the Duct Detector Differential testing had been performed as required. In an interview conducted during the same time frame, the Director of Facilities acknowledged that the facility failed to provide documentation of the annual Duct Detector Differential testing. The deficiency was cited under NFPA 101 2012 (19.2.9.1, 7.9) and NFPA 101 2021 (19.2.9.1, 7.9), indicating noncompliance with the standards that require fire alarm detection systems, including duct detectors, to be tested and maintained annually. The report notes that this deficiency could affect all occupants of the facility in the event of a fire or other emergency.
Plan Of Correction
Fire Alarm System - Testing and Maintenance CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Fire Alarm System - Testing and Maintenance K0345 1. On The facility a certified fire alarm vendor to perform annual duct detector differential testing. All required testing has now been completed and documented. 2. All residents and staff were considered at risk due to lack of documented testing. A facility-wide review of all fire alarm components was conducted on 3. The facility established a service agreement to ensure all fire alarm testing (including duct detectors) is completed annually per NFPA 72 and NFPA 101 requirements. A compliance calendar has been implemented with alerts for required inspections and testing. The Director of Facilities/designee has been re-educated on required testing intervals and documentation. 4. The Director of Facilities or designee will audit for 3 months all documentation for the annual testing and inspection of the duct detector pressure differential test. The Director of Facilities will present the findings of site inspections for 3 months at Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required Fire Alarm System - Testing and Maintenance CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Fire Alarm System - Testing and Maintenance K0345 1. On The facility a certified fire alarm vendor to perform annual duct detector differential testing. All required testing has now been completed and documented. 2. All residents and staff were considered at risk due to lack of documented testing. A facility-wide review of all fire alarm components was conducted on. 3. The facility established a service agreement to ensure all fire alarm testing (including duct detectors) is completed annually per NFPA 72 and NFPA 101 requirements. A compliance calendar has been implemented with alerts for required inspections and testing. The Director of Facilities/designee has been re-educated on required testing intervals and documentation. 4. The Director of Facilities or designee will audit for 3 months all documentation for the annual testing and inspection of the duct detector pressure differential test. The Director of Facilities will present the findings of site inspections for 3 months at Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required
Failure to Perform and Document Annual Main and Feeder Breaker Testing
Penalty
Summary
The deficiency involves the facility’s failure to perform and document required annual maintenance and testing of the main and feeder circuit breakers in accordance with NFPA 99 and manufacturer recommendations. During a record review conducted between 11:30 AM and 3:00 PM, surveyors requested documentation of the annual main and feeder breaker exercise. The facility was unable to provide records demonstrating that this testing and exercising had been completed as required. In interviews conducted during the same time frame, the Director of Facilities acknowledged that the facility did not have documentation showing that the annual main and feeder breaker exercise was performed according to manufacturer recommendations. The report notes that this failure to comply with NFPA 99 (2012 and 2021 editions, Sections 6.4.4 and 6.5.4) could affect all occupants of the facility in the event of a fire or other emergency, and that written records of maintenance and testing are required to be maintained and readily available.
Plan Of Correction
Electrical Systems - Essential Electric System CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Electrical Systems - Essential Electric System Maintenance and Testing K0918 1. On A licensed electrical contractor performed the annual main and feeder breaker testing/exercising in accordance with manufacturer recommendations. Documentation has been completed and is maintained on-site. 2. All residents were considered at risk due to lack of documented testing. A full review of the essential electrical system was conducted on 3. A preventative maintenance program has been implemented to ensure that annual breaker testing is completed per NFPA 99 (2012). The facility has incorporated electrical system testing into its environmental compliance tracking system. The Director of Facilities/designee received re-education on NFPA requirements. 4. The Director of Facilities will audit electrical system maintenance logs quarterly for 12 months. Inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required. Electrical Systems - Essential Electric System CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Electrical Systems - Essential Electric System Maintenance and Testing K0918 1. On A licensed electrical contractor performed the annual main and feeder breaker testing/exercising in accordance with manufacturer recommendations. Documentation has been completed and is maintained on-site. 2. All residents were considered at risk due to lack of documented testing. A full review of the essential electrical system was conducted on . 3. A preventative maintenance program has been implemented to ensure that annual breaker testing is completed per NFPA 99 (2012). The facility has incorporated electrical system testing into its environmental compliance tracking system. The Director of Facilities/designee received re-education on NFPA requirements. 4. The Director of Facilities will audit electrical system maintenance logs quarterly for 12 months. Inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, , and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required.
Improper Use of Adapters and Power Strips for Refrigerators
Penalty
Summary
The deficiency involves improper use of electrical adapters and power strips as substitutes for permanent wiring, in violation of NFPA 99 and NFPA 70 requirements. During an observation with the Director of Facilities, surveyors found that an adapter was being used to power a refrigerator in the kitchen. The Director of Facilities acknowledged that an adapter was in use for this refrigerator, contrary to the standards that prohibit adapters from being used in place of fixed wiring. In a separate observation with the Director of Facilities, surveyors identified that a refrigerator in the dining room manager's office was plugged into a power strip. The Director of Facilities acknowledged that a power strip was being used for this refrigerator. These findings showed that the facility was not complying with NFPA 99 provisions that require power strips and adapters not be used as substitutes for permanent wiring for such equipment.
Plan Of Correction
Formatted text (without <text> tags or quotes): Electrical Equipment - Power and Extension Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Electrical Equipment - Power and Extension K0920 1. On The adapter in the kitchen refrigerator and the power strip in the dining room manager's office were immediately removed. All equipment was plugged directly into approved wall outlets. 2. On A facility-wide inspection was conducted by The Director of Facilities to identify improper use of power strips and adapters. Any non-compliant items were removed immediately. 3. On Staff were educated on proper electrical safety practices, including prohibited use of extension and adapters. Routine environmental rounds now include electrical safety checks. 4. The Director of Facilities/designee will conduct monthly environmental rounds for 3 months, then quarterly thereafter. Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that Continued from page occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required. Electrical Equipment - Power and Extension CFR(s): NFPA 101 Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required Electrical Equipment - Power and Extension K0920 1. On The adapter in the kitchen refrigerator and the power strip in the dining room manager's office were immediately removed. All equipment was plugged directly into approved wall outlets. 2. On A facility-wide inspection was conducted by The Director of Facilities to identify improper use of power strips and adapters. Any non-compliant items were removed immediately. 3. On Staff were educated on proper electrical safety practices, including prohibited use of extension and adapters. Routine environmental rounds now include electrical safety checks. 4. The Director of Facilities/designee will conduct monthly environmental rounds for 3 months, then quarterly thereafter. Quality Assurance Performance Improvement (QAPI) meetings to confirm inspections have taken place. During and at the conclusion of the three months, the QAPI committee will re-evaluate and initiate necessary action or extend the review period. The Administrator is responsible for confirming implementation and ongoing compliance with the components of the Plan of Correction, and resolving variances that may occur. The Administrator is responsible for confirming the status of this Plan of Correction is reviewed and discussed at QAPI meetings and action initiated if required.
Food Safety and Sanitation Deficiencies in Main and Satellite Kitchens
Penalty
Summary
Surveyors identified multiple failures to store, prepare, distribute, and serve food in accordance with professional standards for food service safety in both the main kitchen and a satellite pantry kitchen. In the main kitchen, a cook’s beard cover did not fully cover all facial hair, and the handwashing sink initially did not provide warm water until the Executive Director manually adjusted a valve under the sink. In the pot washing area, full-sized steam table pans were stacked while still wet, and more than five plate domes with stuck-on food particles were found piled in the tray line area ready for use, indicating they had not been properly washed. Two large ice buckets were stained with black and grey mold-like discoloration and white wear marks. The high-temperature dishwashing machine in the main kitchen was run three times but failed to reach the required 180°F rinse temperature, only reaching 172°F, meaning dishes were not properly sanitized. In the second-floor satellite pantry kitchen, the high-temperature dishwashing machine was also run three times and failed to meet required wash temperatures, reaching only 139°F instead of the required 150–165°F, so dishes were not properly cleaned and sanitized. Additional sanitation and maintenance issues were observed, including a vent above serving dishes with a mold-like accumulation, broken and soiled cabinets above serving dishes with residue on the handles, and pantry floors with cracked, broken, and missing tiles with debris or residue buildup. The dishwasher chemical cabinet lock was rust-laden, the AC filter was covered with dark grey soot and dust, the juice dispenser with clean cups nearby had debris on top, and tray delivery carts contained large sheet trays with residue and stuck-on food debris. During a tray line observation, chopped tomatoes and sliced avocados on the salad line were held at 44°F and 45°F respectively, above the required 41°F or less, and the menu extension listed pureed peas for a pureed diet, but no pureed vegetable was present on the line.
Plan Of Correction
Food Procurement, Store/Prepare/Serve-Sanitary CFR(s): 483.60(i)(1)(2) §483.60(i) Food safety requirements. Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required F0812 1. All identified sanitation issues were corrected on Hot water valve was fixed immediately by maintenance team Steam table pan wet nesting was corrected The 5 plate domes that were dirty were taken to the dishwasher to be washed Stained ice buckets were replaced with new ones Dishwashing machine not reaching temperature for rinse cycle was fixed by Eco lab the same day Team member was provided education and in-service on proper use of beard guard. Corrected on [R] 2.Identified issues from satellite Kitchen were corrected on [R] Dishwashing machine not reaching temperature for rinse cycle was fixed by Eco lab the same day The vent located above the serving dishes was cleaned by maintenance team The cabinets were cleaned immediately The floors of the pantry area were observed with broken, cracked, missing tiles, with buildup residue and debris. Maintenance director made aware in the process of getting replaced. The locking mechanism of the dishwasher chemical cabinet is rust laden. Laden removed and in the process of being replaced. The AC filter was cleaned by maintenance team Th juice dispenser was cleaned by dietary aide The large delivery trays with residue and food debris were discarded 3. Issues identified during Tray line observation were corrected: The chopped tomatoes and sliced avocados were discarded Pureed vegetable was added to the line. Inservice on serving all food groups, starches, protein and vegetables to residents on texture modified diet order. Inservice provided to all dietary aides Inservice on maintaining and holding temperatures for ready to eat foods. Inservice provided to all cooks and dietary aides Daily sanitation rounds will be conducted by the Certified Dietary manager /designee for one week. Weekly for 2 months. 4. The Certified Dietary Manager/Executive Chef/designee will report the findings of the above observations and audits to the monthly QAPI Committee. The Administrator is responsible for confirming implementation and compliance of this POC and and resolving any variances that may occur.
Failure to Honor Diet-Appropriate Menu Choices for Residents on Modified Diets
Penalty
Summary
The facility failed to provide residents with menu choices that matched their physician-ordered diet textures and liquid consistencies. One resident with severe cognitive impairment had a physician order for a controlled diet with pureed texture and honey-thick liquids. During a noon meal observation, this resident’s meal ticket was stapled to a Regular Menu listing items such as lettuce and tomato salad, stir-fried vegetables, and a grilled cheese sandwich, none of which were appropriate for the resident’s ordered diet. The Registered Dietitian and the Dietetic Technician confirmed that Daily Menu printouts with Regular Menu options were provided to all residents, including those on mechanically altered diets, resulting in residents being offered choices that could not be honored due to diet restrictions. Another resident with moderate cognitive impairment had a physician order for a mechanical soft diet with nectar-thick liquids. This resident’s lunch tray ticket was also stapled to a Regular Menu that included salad greens, which are not allowed on a mechanical soft diet. On a separate breakfast observation, the same resident’s Regular Menu included fresh fruit as a choice, which the resident circled, but the tray contained canned peach halves instead. The resident stated she wanted her chosen fresh fruit rather than the peaches and reiterated her food preferences during the interview. Photographic evidence was obtained to document these discrepancies between ordered diets, menu offerings, and the food actually provided.
Plan Of Correction
Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is requiredF05501. Resident #54 and Resident #56 were immediately assessed by the Registered Dietitian (RD) & CDM (Certified Dietary Manager) for food preferences on Residents #54 and #56 were offered meal choices consistent with the prescribed diet. No adverse outcomes were identified. 2. 100% audit of all residents with therapeutic diets was completed on [R] by CDM to ensure menus and meal selections consistent with physician-ordered diets.On [R] , CDM provided in-service provided to dietary aides, certified nursing assistants, nurses, managers on new selective menu processes. 3. The facility implemented a diet-specific menu system and pre-meal diet verification process by reviewing the diet in tray ticket program IMPAC and PCC. Copies of the menus to be provided as part of the audits.Diet Menu was revised to include a mechanically altered diet to be consistent with physician orders. Therapeutic diets menus are available and offered to each resident according to physician orders. The Dietary Manager or designee will conduct weekly audits of 4 residents on therapeutic diets x 4 weeks then monthly x 2months, to verify the correct menu is offered and served. 4. The Dietary Manager or designee will report findings at the monthly QAPI meeting. The Administrator is responsible for confirming implementation and compliance with this POC and [R] , and resolving any variances that occur.
Failure to Follow Therapeutic Diet Orders and Provide Prescribed Nutritional Supplements
Penalty
Summary
The deficiency involves the facility’s failure to follow physician-ordered therapeutic diets and prescribed nutritional supplements for multiple residents. One resident with severe cognitive impairment and a physician’s order for a controlled diet with pureed texture and honey-thick liquids was observed at lunch without the ordered pureed vegetable; her plate contained only pureed chicken, a pureed starch, and possibly a pureed bread, all covered in gravy. The pureed menu for that meal listed broccoli as the vegetable, and a subsequent tray line observation on another day showed no pureed vegetables available, despite the pureed menu specifying pureed peas. The dietary manager and registered dietitian were informed of the missing pureed vegetables, and photographic evidence was obtained. The facility also failed to provide ordered Magic Cup nutritional supplements as prescribed. One resident with severe cognitive impairment and a care plan addressing risk for compromised nutritional status had a physician’s order for a 4 oz Magic Cup on day and evening shifts with lunch and dinner; during a breakfast observation, the meal ticket listed Magic Cup, but none was provided. Another resident with moderate cognitive impairment had a physician’s order for a 4 oz Magic Cup with lunch; during lunch observation, the meal ticket indicated Magic Cup, but the resident was served chocolate ice cream and ate coconut cream pie for dessert instead. The MAR documented 100% consumption of a Magic Cup on two consecutive days, despite the observed failure to provide it. During interviews, the RD and dietary manager explained that Magic Cups were to be provided by dietary staff either on trays or via the dessert/ice cream cart, but they could not explain why residents in the dining room did not receive the ordered supplements. Photographic evidence was obtained of these occurrences.
Plan Of Correction
Preparation and/or execution of this plan does not constitute admission or agreement by the provider that a deficiency exists. This response is also not to be construed as an admission of fault by the facility, its employees, agents or other individuals who draft or may be discussed in this response and plan of correction. This plan of correction is submitted as the facility's credible allegation of compliance and Soley because it is required F0803 1. Upon identification, resident #54 was given pureed vegetables. Residents #23, #39, and #54 were given Magic Cup supplements as ordered. On [R] CDM re-educated team members on supplement delivery including proper documentation and confirming that pureed diet being served matches what is listed on spread sheet. Dietary aides' morning and evening shifts are accountable for serving all food groups including vegetables when serving puree meals to residents. 2. A 100% audit of all residents with therapeutic diets and/or supplements was completed on [R] by Certified Dietary Manager. 3. A tray line checklist and diet/supplement reconciliation process between dietary and nursing were implemented by [R]. RD oversight of menu compliance was initiated. The Certified Dietary Manager or designee will audit food tray weekly x 4 weeks then weekly x 2 months. 4. The Certified Dietary Manager/Designee will report on the findings at the monthly QAPI meeting. The Administrator is responsible for confirming implementation and compliance with this POC and [R], and resolving any variances that may occur.
Failure to Verify and Honor DNR Order Before Initiating CPR
Penalty
Summary
The deficiency involves the facility’s failure to honor a resident’s clearly established Do Not Resuscitate (DNR) status during a cardiac emergency. The resident had multiple medical diagnoses, including cerebral infarction, COPD, cardiomyopathy, atherosclerotic heart disease, a nonrheumatic mitral valve disorder, cognitive communication deficit, and immunodeficiency. The medical record contained DNR orders created on two separate dates with no end dates, a DNR document signed by the resident and a nurse practitioner, and a 3008 form listing the resident’s advance directive as DNR. The resident’s MDS showed a Brief Interview for Mental Status score of 15, indicating intact cognition, and progress notes documented that the difference between DNR/no CPR and full code had been explained over 30 minutes, after which the resident chose DNR and reiterated to social services that she did not want to be resuscitated or undergo chest compressions. On the day of the incident, a CNA assigned to the resident checked on her and found her sitting in a wheelchair and unresponsive despite multiple verbal attempts to rouse her. The CNA notified the RN, who obtained a blood pressure machine, entered the room, then ran out to the nurses’ station, after which a code blue was paged over the intercom. The RN returned with a crash cart, and additional nursing staff, including RNs and LPNs, entered the room. Staff described transferring the unresponsive resident from the wheelchair to the bed and beginning chest compressions. Multiple staff members reported that when one LPN asked about the resident’s code status, no one in the room knew it at that time, and that this LPN left the room to verify the code status while CPR was already in progress. Interviews and video review confirmed that CPR was initiated and continued for approximately 12 minutes before EMS arrived, despite the resident’s existing DNR orders. Several nurses, including those who arrived after CPR had started, acknowledged that they did not check the resident’s code status before assisting with chest compressions or using a bag-valve mask. Staff later reported that the LPN who checked the record returned and announced that the resident was a DNR, yet compressions continued until EMS arrived. The physician stated that the resident was already in the system as a DNR and that staff were expected to check code status before performing CPR. The DON and regional nurse consultant confirmed, based on interviews and camera review, that staff failed to confirm the resident’s code status prior to initiating CPR and that CPR was performed against the resident’s wishes, leading surveyors to determine that this failure resulted in Immediate Jeopardy.
Removal Plan
- Implemented a revised admission/readmission process requiring an Advance Directive discussion form to be completed by the licensed nurse upon admission or with change in advance directives, with follow-up by Social Services.
- Reviewed Advance Directive discussion forms in the daily clinical meeting with the Interdisciplinary Team.
- Conducted a huddle on units after the clinical meeting to discuss any changes in advance directives/code status.
- Placed signage on each crash cart stating: "Stop check physician order prior to starting Cardiopulmonary Resuscitation."
- Implemented the "It Takes Two" process requiring two licensed nurses to verify code status/advance directives prior to initiation of CPR.
- Initiated an internal investigation including resident record review, staff interviews, and notification to the physician and resident representative.
- Suspended and terminated the assigned nurse and reported the nurse’s license to the licensing board.
- Suspended and terminated an additional nurse who responded and participated in initiation of CPR and reported the nurse’s license to the licensing board.
- Suspended two additional nurses pending investigation and returned them to work with disciplinary action, education on ANE/honoring advance directives, and participation in a code blue drill.
- Conducted a 100% audit of all current residents’ code status and care plans.
- Conducted a 100% audit of crash carts to ensure all required items were present.
- Reviewed CPR cards for identified nurses to confirm validity and inclusion of in-person skills competencies.
- Held an ad hoc QAPI meeting with Administrator, DON, Medical Director, and department heads.
- Completed an audit of residents discharged, transferred to the hospital, or expired to verify advance directives were honored.
- Provided staff education for licensed/certified staff on medical emergency response and communication of advance directives and code status, following physician orders related to advance directives, the "It Takes Two" verification process, and CNA roles during code blue.
- Provided all-staff education on Abuse, Neglect and Exploitation/Resident Rights with focus on honoring advance directives.
- Completed honoring advance directives attestation with licensed nursing staff.
- Completed physician orders education for licensed nursing staff.
- Completed medical emergency response and communication of code status education for licensed nursing staff.
- Completed ANE/Resident Rights education for all staff.
- Completed advance directives posttest for licensed staff.
- Completed ANE/Resident Rights posttest for all staff.
- Completed code blue process/"It Takes Two" education for licensed nursing staff.
- Began code blue drills every shift and required licensed nurses to attend a mock code blue quality assurance drill prior to working.
- Completed CNA roles-in-code-blue training.
- Completed quality reviews validating staff competencies for completed education.
- Completed quality reviews of newly admitted residents to verify completion of the advance directive discussion form.
- Implemented Director of Clinical Services chart review of residents who expire at the facility or are transferred to the hospital after a cardiac event to verify advance directives were followed.