Infection Control Failures in Water Management, Ice Scoop Storage, and Enhanced Barrier Precautions
Summary
The facility failed to maintain an active and ongoing plan for reducing the risk of legionella and other opportunistic pathogens of premise plumbing. On 7/7/26, surveyors observed a water line coming down from the ceiling in the kitchen and extending about 10 feet to the back of the cookline, with nothing hooked up to it or using it. The same day, in the South janitors' closet, hot water from a fixture initially discharged discolored water before running clear. Maintenance staff stated the South spa was not used often, that residents had private showers in their rooms, and that the spa and South personal showers were not regularly flushed. Surveyors also observed a hopper in the central soiled utility with the spray turned off and a mop sink in the central soiled linen room with the cold water turned off. Maintenance staff stated he was unaware of the unused water line on the cookline and that it was not currently flushed. Record review of the Water Management Team Meeting Minutes dated 6/11/26 showed the section for evaluating water cloudiness or turbidity was left blank, and the flushing documentation did not include a list or map of fixtures that were flushed. The facility also failed to maintain hydration carts' ice scoop holders in a sanitary condition. On multiple observations from 7/7/26 through 7/9/26, hydration carts in the 200s hallway and outside a resident room had cracked plastic ice scoop holders with white and brown debris inside, and later pink material was seen on the interior of the cracked holder. The Infection Preventionist stated that if an ice scoop holder was cracked it should be thrown out, that kitchen staff should clean the carts and scoops after nurse aides returned the carts each shift, and that cracked holders could harbor bacteria. The facility further failed to ensure staff used appropriate PPE and that enhanced barrier precautions were in place for two residents. One resident had a care plan for straight catheterization every 6 hours with enhanced barrier precautions during high-contact care. During observation, an RN entered the room, donned gloves, and performed a bladder scan and catheterization without putting on a gown; the RN later stated she should have worn one but forgot. A family member reported seeing staff not wearing proper PPE during care. Another resident had a history of MRSA and a care plan calling for enhanced barrier precautions, but no PPE cart or signage was present outside the room and two CNAs provided brief-change care without gowns. The Infection Preventionist stated residents with prior MDRO infection should remain on enhanced barrier precautions and confirmed the resident should have had new isolation orders after treatment ended, but this had been overlooked and not implemented.
Penalty
Resources
Below are regulatory guidelines relevant to this citation:
Trusted data from CMS and state health departments
Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release October 8, 2026) and official state health department websites — never guesswork.
In your survey window? See what surveyors are citing.
The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.