F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
D

Loose and Broken Bed Side Rails Not Properly Inspected

St Joe ManorBonne Terre, Missouri Survey Completed on 05-20-2026

Summary

Facility staff failed to conduct regular inspections of bed frames, mattresses, and side rails as part of the maintenance program for three residents who had side rails in use. The facility policy required the interdisciplinary team to evaluate the sleeping environment, check bed frames, mattresses, and bed rails for compatibility and size before use, and have maintenance routinely inspect beds and related equipment for risks and problems, including entrapment risks. The policy also stated that worn or malfunctioning bed system components were to be repaired or replaced and that bed rails were to be properly installed and used according to manufacturer instructions. Resident #52 had an order for bilateral quarter upper side rails for repositioning and transfers, along with a signed side rail consent, bed rail measurement assessment, side rail resident assessment, and care plan addressing side rail use. During observation, the resident used the right side rail to help stand, and the rail moved with minimal effort. The resident stated the right rail had been loose for a while and used the rails to help with transfers from the bed and chair. Resident #96 had an order for a right upper quarter side rail for repositioning and transfers, with consent, measurement assessment, resident assessment, and care plan documentation in place. Observations showed the rail up while the resident was in bed and later while the resident was out of the room, and the rail could be moved with minimal effort. Resident #154 had an order for bilateral upper quarter side rails for repositioning and transfers, with consent, measurement assessment, resident assessment, and care plan documentation. During observation, the resident grabbed the bed rail during peri-care, and the rail moved with minimal effort and tilted inward. The resident stated the right side rail was broken and said he/she used the bed rails to help turn in bed and during care. Staff interviews showed the QA Nurse and Housekeeping Supervisor handled side rail assessments and tightening, but some rails did not fit well and could become loose again.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0909 citations
Torn Mattress Left in Resident Room
D
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

Torn Mattress Left in Resident Room: A resident’s bed mattress was observed with punctures exposing internal materials and with dips and lumps on the sleeping surface while the bed was unmade. The resident said staff had known about the mattress for over a year and that it was very uncomfortable. The HSKP supervisor said staff usually report worn mattresses, and the administrator said new mattresses had been ordered but was unsure how this one was missed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Inspect Bed Systems for Entrapment Hazards
F
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

Failure to inspect bed systems for entrapment hazards: The facility did not maintain a regular program to inspect bed rails, mattresses, and frames or measure FDA entrapment zones. The ML stated annual bed checks focused on electrical components and function, but entrapment measurements were not being done, and the DON stated all residents had bed rails because they came on the bed. Multiple residents were observed with raised bed rails, including combinations of upper and lower rails, and the facility policy called for regular bed inspections and individual bed rail evaluations.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsafe Bed and Mattress Inspection and Attachment
D
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

A facility failed to ensure safe inspection and fit of resident beds and air mattresses. One resident with multiple chronic conditions had an air mattress with an approximately five-inch gap between the mattress and foot board on repeated observations, and staff were unclear who was responsible for correcting it. Another resident fell from bed when a broken clip securing the air mattress strap to the frame allowed the bed to lift; surveyors later observed the mattress was too wide for the bedframe, with about five inches hanging over the side and not fully supported.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Bed Rail Gap Measurements Exceeded Allowed Standards
E
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

Bed rail safety checks showed Zone 1 gaps of 7 inches for three residents, exceeding the FDA maximum of 4 3/4 inches. One resident had Bell’s palsy, falls history, reduced mobility, and cognitive impairment; another had Alzheimer’s disease, dementia, a tibia fracture, and needed max assist for bed mobility; and a third had quadriplegia and needed max assist for bed mobility. Observations found large square openings in the rails, a mattress separated from the frame, and staff interviews showed the Housekeeping Supervisor measured the rails while nursing leadership kept the forms and was responsible for compliance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Routine Bed Entrapment Inspections
F
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

The facility failed to maintain a routine process to inspect bed frames, mattresses, and bed rails for possible entrapment. Record review showed the bed inspection form addressed bed height and wheelchair cushion securement, but did not include checks of frames, mattresses, or rails. The ADMIN and MAINT both confirmed there was no checklist or routine maintenance program for these inspections unless a work order was submitted.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Bed Rail Inspection Documentation
E
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

Missing Bed Rail Inspection Documentation: The facility failed to complete and/or maintain routine bed rail inspection records for all residents with side rails. A resident with bilateral half rails used for repositioning and safety due to frequent falls out of bed was observed with upper quarter-length rails, and maintenance staff from a sister facility later checked the rails without prior facility documentation. An undated bed entrapment inspection form showed 10 beds passed, but it did not identify who completed the assessments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Missouri

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Missouri — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release August 26, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.