Hot Water Temperatures Exceeded Safe Range in Resident Rooms
Summary
The facility failed to keep resident areas as free from accident hazards as possible when multiple resident room sinks produced hot water temperatures above the facility’s stated range. The water management plan identified a central domestic hot water system with gas-fired water heaters set at 140 degrees F and a mixing valve reducing water to 125 degrees F for building distribution, as well as three steam-powered instant hot water heaters with no mixing valve providing 125 degrees F water. The facility’s policy stated resident room water temperatures should be between 105 degrees F and 120 degrees F, but survey observations found several resident room sinks measuring between 129 degrees F and 137 degrees F by facility testing and between 126 degrees F and 131 degrees F by the Engineering Supervisor’s multimeter. During observation, unoccupied and occupied resident rooms on the unit had sink water temperatures above 120 degrees F, including one resident room with both the main sink and bathroom sink measuring 131 to 132 degrees F by direct observation and 126 to 128 degrees F by multimeter testing. Another resident room had sink temperatures of 131 degrees F in both the main room and bathroom sinks, with multimeter readings of 126 to 127 degrees F. A third resident room had sink temperatures of 131 to 132 degrees F, with multimeter readings of 127 to 128 degrees F. The facility multimeter used for testing had an expired calibration date. Interviews showed staff did not know the required hot water temperature range, how often temperatures were monitored, or whether sink temperatures were checked routinely. The Regulatory Affairs Safety Coordinator, Engineering Supervisor, EVS staff, LPN, maintenance staff, RN, Environmental Safety Officer, Manager, and Administrator all described uncertainty about monitoring frequency or reporting processes. The Administrative Director of Engineering stated the facility had recent water temperature fluctuations related to repairs of the hot water mixing valve, including a weekend issue in which housekeeping staff reported hot water temperatures on 300 hall and 400 hall after cleaning equipment had been hung on the mixing valve lever, preventing proper function, and a recirculating pump had also required replacement.
Penalty
Resources
Below are regulatory guidelines relevant to this citation:
Trusted data from CMS and state health departments
Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release August 26, 2026) and official state health department websites — never guesswork.
In your survey window? See what surveyors are citing.
The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.