F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
C

Insufficient Resident Room Square Footage

Evercare Of CollinsvilleCollinsville, Illinois Survey Completed on 12-23-2025

Summary

The facility failed to provide at least 80 square feet of floor space per resident bed for 53 of 78 residents reviewed for room size. Surveyors found that the facility had 30 two-bed resident rooms that provided only 75 square feet per resident bed, with rooms measuring 12 feet by 12 feet 6 inches. These rooms were all certified for Medicare and Medicaid and included multiple numbered rooms, with one room now used as a family visiting room and telephone room for residents and another now used as a storage room. Surveyors also found 8 two-bed resident rooms that provided only 77.5 square feet per resident bed, measuring 12 feet 1 inch by 12 feet 6 inches with an additional 10-inch by 72-inch offset, and 3 two-bed resident rooms that provided only 76.5 square feet per resident bed, measuring 12 feet by 12 feet 6 inches with an additional 10-inch by 48-inch offset; one of these rooms was now the Break Room and another was now the Activity Room. In addition, 2 two-bed rooms provided only 78.5 square feet per resident bed and measured 15 feet by 10 feet 6 inches. During observation from 12/15/2025 through 12/17/2025, residents were observed in the rooms that did not meet the 80-square-foot requirement. Form CMS 671 dated 12/15/25 documented a census of 78, and on 12/15/2025 at 9:25 AM, the Regional Maintenance staff stated that the facility had multiple rooms with less than the required square footage.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0912 citations
Resident Rooms Did Not Meet Required Square Footage
B
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

Resident rooms failed to meet required square footage standards for 2 of 10 rooms reviewed. One room certified for 4 residents measured 74 sq ft per resident, and a private room measured 81 sq ft instead of 100 sq ft. Surveyors observed no residents in the rooms, and the ADM said she was unaware of current room waivers, noted one room was being used as a staff break room, and could not find paperwork showing a waiver had been filed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Insufficient Bedroom Square Footage for Double Occupancy
D
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

Insufficient bedroom square footage for double occupancy: The facility placed two residents in rooms that measured only 72.265 sq ft per resident, below the required 80 sq ft per resident. Record review showed multiple rooms below the required size, and several unoccupied rooms were available or being used for non-resident purposes. The ADM said the facility knew the rooms were licensed for 2 residents but chose to keep residents in the front halls and did not apply for a room-size waiver; the VCSP said there was no policy for room size requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Resident Room Size Deficiency
E
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

Resident Room Size Deficiency: An observation with the Maintenance Director found 4 of 17 sampled resident rooms did not meet the required square footage per resident. One room occupied by two residents measured 137.04 sq. ft. total, two rooms occupied by four residents each measured 260.6 sq. ft. usable space, and one room occupied by five residents measured 158.63 sq. ft. total. The Administrator stated prior inspections had not cited the issue and asked that the room size issues be grandfathered in.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Insufficient Resident Room Square Footage
C
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

Insufficient Resident Room Square Footage: The facility failed to provide the required 80 sq ft per resident in all 48 resident rooms. Surveyors reviewed the bed classification form, measured the rooms with a laser device, and found that the 2-bed rooms measured 151 to 160 sq ft and the 3-bed rooms measured 219 to 234 sq ft, which did not meet the required space per resident. The ADM provided a waiver request and stated there had been no changes to the rooms.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Resident Rooms Did Not Meet Required Square Footage
B
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

Resident rooms 107, 108, 110, 302, 305, 306, and 307 did not meet the required square footage standards for multiple-occupancy rooms. Census review showed each room had 2 beds, and repeated observations confirmed the rooms remained set up with 2 beds each. The Administrator stated an exemption had been requested from the state but had not yet been granted.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Bedroom Space Requirements Not Met in Multiple Occupancy Rooms
B
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

Bedroom Space Requirements Not Met in Multiple Occupancy Rooms: Multiple resident rooms were measured below the required 80 square feet per resident, with several rooms ranging from 61.9 to 79.3 square feet per resident. The Administrator stated a room waiver was in effect and that the room measurements had not changed. Record review showed the waiver criteria were met for the identified rooms, and 21 residents were living in most of those rooms during the annual survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Illinois

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Illinois — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release October 8, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.