F0906 F906: Provide enough power supply for lighting all entrances and exits; equipment for fire detection and alarm systems, and extinguishers.
D

Uninterrupted Power Supply for Life-Sustaining Equipment

Casa Coloma Health Care CenterRancho Cordova, California Survey Completed on 04-24-2026

Summary

The facility failed to ensure there was an uninterrupted power supply for life-sustaining equipment during a power outage for a census of 131. During an observation on 4/23/26 at 1:14 p.m., the facility experienced a power interruption, and staff were observed bringing out extension cords, flashlights, and power cords to plug oxygen concentrators into the red emergency outlets in Station 2. Staff stated the outlets were not working and that oxygen tanks were needed. During an interview at 1:35 p.m., the SSD stated the emergency outlets were not working, and at 1:38 p.m., 24 minutes later, the emergency power kicked in. The ADON stated at 1:43 p.m. that the emergency generator was on, and normal power was restored at 2:51 p.m. During a follow-up interview on 4/24/26, the DM stated the generator company installed the shutdown switch a year ago and that the generator should kick in within 6-9 seconds during a power outage. The DM stated the generator did not kick in within that time because the switch was pushed in, which shut the generator down, and that he had to pull the switch out when he checked it during the outage. He stated someone touched the switch, it was difficult to reset, and it took 10 minutes for the generator to kick in. The DM also stated this had happened in the past and that he had notified the AD and kitchen staff to be careful not to touch the switch. During observation, the generator switch was located to the right of the kitchen back door, and the DM demonstrated how easily the switch button could be pressed. The ADM later stated he had not been told the switch location was a bad spot and had not been notified of an incident related to the switch. The facility policy stated alternate energy sources would be used during a disruption in normal power, and that life-saving equipment and oxygen generating equipment were required to be restored to back-up power within 10 seconds of failure of the normal power source.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0906 citations
Generator Failure and Inadequate Emergency Response for Ventilator-Dependent Residents
F
F0906 F906: Provide enough power supply for lighting all entrances and exits; equipment for fire detection and alarm systems, and extinguishers.
Short Summary

A facility experienced a complete power loss when its emergency generator failed to activate, leaving all areas without electricity, including ventilators, tube feeding pumps, and other critical equipment. Fourteen ventilator-dependent residents were affected, and emergency (red) outlets remained without power until a portable generator was connected hours later. Maintenance records lacked evidence of required weekly inspections and monthly load-bank testing for the generator in the months before the outage. Nursing and respiratory staff did not initiate manual ventilation (ambu-bagging) as required by the facility’s Emergency Operations Plan, and an RN on duty reported not performing specialized respiratory interventions and focusing on only one ventilated patient. Two nurses on the ventilator unit did not know where backup ventilator batteries were stored, and the RN’s personnel file lacked documented competency in ventilator management and emergency respiratory procedures.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Ensure Critical Respiratory Equipment Connected to Emergency Power
D
F0906 F906: Provide enough power supply for lighting all entrances and exits; equipment for fire detection and alarm systems, and extinguishers.
Short Summary

A resident with a tracheostomy and chronic respiratory failure was found to have their oxygen concentrator and suction machine plugged into a standard wall outlet instead of a generator-powered outlet. Staff confirmed that only red faceplate outlets were connected to the backup generator, but these were already in use for other equipment. The facility's policy directed staff to move equipment after a power outage rather than ensuring critical devices were always connected to emergency power, and documentation of required safety checks was not provided.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Emergency Power System During Outage
F
F0906 F906: Provide enough power supply for lighting all entrances and exits; equipment for fire detection and alarm systems, and extinguishers.
Short Summary

The facility did not maintain an operable emergency power system during a prolonged outage, resulting in a complete loss of power. Staff were unable to access electronic medical records, emergency lighting was initially unavailable, and a resident requiring high-flow oxygen was transferred to the hospital due to the inability to provide necessary care. The facility did not follow its emergency procedures to obtain a backup generator, affecting all residents.

Inspection fine: $110,44829 days payment denial
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Generator Failure During Power Outage
E
F0906 F906: Provide enough power supply for lighting all entrances and exits; equipment for fire detection and alarm systems, and extinguishers.
Short Summary

A facility's generator failed during a planned power outage, leaving 13 residents who required oxygen concentrators without power for approximately 15 minutes. The generator malfunctioned due to a faulty oil pressure sensor, which was not detected during annual maintenance. This failure put residents at risk of respiratory distress.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Emergency Power System Delay During Outage
F
F0906 F906: Provide enough power supply for lighting all entrances and exits; equipment for fire detection and alarm systems, and extinguishers.
Short Summary

The facility experienced a delay in the activation of its emergency power system during a power outage, resulting in a two-minute period without power for emergency exit signs, lighting, and medical equipment. Staff had to manually switch residents requiring oxygen to portable tanks. The facility's policy requires immediate notification of the Administrator and Maintenance Director if the generator fails to activate within 10 seconds.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Emergency Power System Failure
E
F0906 F906: Provide enough power supply for lighting all entrances and exits; equipment for fire detection and alarm systems, and extinguishers.
Short Summary

The facility experienced a complete power outage due to a failure in the temporary generator, which had been in use since 2020. This outage affected medical equipment, elevators, and refrigeration units, and required manual intervention to restore power. Residents on oxygen concentrators were switched to O2 tanks, and staff faced challenges due to non-functional elevators and a lack of standard procedures for power outages. The deficiency was confirmed during an exit conference.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across California

Get a heads-up on the newest immediate-jeopardy (J–L) citations in California — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release August 26, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.