F0837 F837: Establish a governing body that is legally responsible for establishing and implementing policies for managing and operating the facility and appoints a properly licensed administrator responsible for managing the facility.
D

Governing Body Failed to Ensure Oversight of Fire Alarm System and Fire Watch

Nans Pointe Rehabilitation And NursingSuffolk, Virginia Survey Completed on 04-25-2026

Summary

The deficiency involves the governing body’s failure to ensure effective leadership, policy implementation, and operational systems to maintain a safe, hazard‑free environment on all three units while the facility was on Fire Watch. Surveyors found that the facility had been on Fire Watch since 1/30/26 due to issues with the fire alarm system, yet the Administrator, who started on 3/30/26, could not clearly explain the exact problem with the fire panel or provide contemporaneous documentation of the malfunction or its monitoring. During an interview, the Administrator stated that Fire Watch consisted of someone making rounds every 15 minutes, primarily nursing staff, and acknowledged that the facility did not have a full‑time maintenance director. When surveyors requested evidence on 4/24/26 of the fire panel’s functionality, fire alarm system inspections, testing, or maintenance records, the Administrator was unable to produce any such documentation, including vendor service reports or audit records. He also could not initially provide documentation from the fire safety vendor verifying that the panel was functioning, and he did not present any evidence of communication from the local Fire Marshal or Fire and Rescue Department regarding Fire Watch. The fire alarm panel was observed in trouble mode for specific units, and the explanation given by regional leadership later was that the issue related to sensitivity and the age of the system, but this information and supporting documents were not available or presented at the time of the initial surveyor request. The governing body’s policies required it to be legally responsible for establishing and implementing policies for management and operation of the facility, including appointment and oversight of the Administrator and accountability for QAPI. However, there was no evidence that the governing body was involved in QAPI activities related to the ongoing fire panel and smoke detector issues or the prolonged Fire Watch status since January. The Administrator confirmed that the fire alarm and Fire Watch issues had not been brought to the QAPI committee, despite the QAPI agenda format including maintenance items such as fire drills, disaster drills, monthly fire alarm tests, and use of the TELS system. No evidence was provided to show a defined process of communication between the Administrator and the governing body regarding these life safety problems or that the Administrator was being held accountable for reporting and managing these operational issues.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0837 citations
Failure of Governing Body to Implement Effective QAPI, Oversight, and Reporting Systems
F
F0837 F837: Establish a governing body that is legally responsible for establishing and implementing policies for managing and operating the facility and appoints a properly licensed administrator responsible for managing the facility.
Short Summary

The governing body failed to ensure an effective QAPI program and overall management systems, resulting in multiple unresolved deficiencies in environmental services, sanitation, infection control, and medication storage and administration that affected all residents’ quality of life. Resident Council minutes and grievance logs documented ongoing complaints about inadequate linens and delayed laundering of personal clothing, while surveyors observed large amounts of unfolded clean laundry and other unsatisfactory conditions in the laundry area. Significant turnover in key leadership roles, including a new DON, Social Services Director, HR Director, and Maintenance Director, coincided with persistent maintenance and pest control issues. The facility also failed to notify the State agency when a fire watch was initiated after fire panel trouble alarms, and surveyors found the facility lacked an effective staff training program on required topics such as QAPI, effective communication, and behavioral health.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Controlled substance documentation policy lacked clear timing and sequence requirements
E
F0837 F837: Establish a governing body that is legally responsible for establishing and implementing policies for managing and operating the facility and appoints a properly licensed administrator responsible for managing the facility.
Short Summary

A facility failed to maintain a clear controlled substance policy because its P&P did not specify when to sign the CDR or complete the MAR. During review of a resident receiving PRN Tramadol for pain, the CDR and MAR showed multiple mismatched and delayed documentation times. Interviews with an LVN, another LVN, an RN, and the DON showed inconsistent understanding of the proper sequence for removing, administering, and documenting controlled meds.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Policies and Procedures for Low Air Loss Mattress Use
D
F0837 F837: Establish a governing body that is legally responsible for establishing and implementing policies for managing and operating the facility and appoints a properly licensed administrator responsible for managing the facility.
Short Summary

Surveyors found that multiple residents with orders for low air loss mattresses (LALM) for PU/PI prevention and wound healing were using these specialty beds without any facility policy or procedure in place to guide their use. The DON confirmed there was no written P&P for LALM, including no direction on linen use, and that staff relied on manufacturer guidelines, which did not address linen. The administrator acknowledged that a P&P for LALM should exist to guide care for the many residents using these mattresses, despite job descriptions assigning responsibility for developing and implementing such policies.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Governing Body Lacked Oversight of Key Facility Issues
F
F0837 F837: Establish a governing body that is legally responsible for establishing and implementing policies for managing and operating the facility and appoints a properly licensed administrator responsible for managing the facility.
Short Summary

Governing body oversight was ineffective because meeting minutes showed quality and safety issues were discussed, but staffing concerns and performance improvement progress for wound care compliance, updated care plans, unlabeled oxygen tubing, and pharmacy recommendations were not addressed. The Admin stated the GB was aware of staffing concerns but not these other issues, and confirmed there was a lack of transparency between the facility and the GB. The facility policy stated the GB has ultimate responsibility and legal authority for safety and quality of care.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Formally Appointed and Consistently Present Administrator
E
F0837 F837: Establish a governing body that is legally responsible for establishing and implementing policies for managing and operating the facility and appoints a properly licensed administrator responsible for managing the facility.
Short Summary

Surveyors found that the facility lacked a formally appointed, properly licensed Administrator (ADM) serving as the NHA and did not have consistent on-site administrative oversight. Staff reported that the prior ADM had left, the Department Head Directory did not list an ADM, and a regional ADM only visited a few hours several times per week without a formal appointment letter. The receptionist also noted that this temporary ADM had been absent for several days due to a corporate conference, leaving the DON identified only as the Abuse Coordinator and no clearly designated ADM present to manage operations.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Loss of Unencrypted PHI on USB Drive Due to Lack of Policy
D
F0837 F837: Establish a governing body that is legally responsible for establishing and implementing policies for managing and operating the facility and appoints a properly licensed administrator responsible for managing the facility.
Short Summary

The facility lacked a policy and procedure governing the use of USB drives for transmitting PHI, leading to an incident in which a resident’s complete medical record was saved to an unencrypted, non–password-protected USB drive and mailed to the resident’s authorized representative. After email transmission failed due to large file size, the MRD used a USB drive containing the resident’s medical records, medical record number, insurance details, residency dates, and share of cost, and sent it by certified mail. The envelope was later returned torn open with the USB drive missing. The ADM acknowledged that existing PHI policies were outdated and did not address USB drives or current technology.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Virginia

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Virginia — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙