F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
D

Bed Rail Inspection and Compatibility Deficiency

Lockport Rehab & Health Care CenterLockport, New York Survey Completed on 03-11-2026

Summary

The facility did not ensure regular inspections of bed frames, mattresses, and bed rails were conducted as part of a maintenance program to identify possible entrapment areas for two residents reviewed for side rail use. Surveyors found that the bed rails for both residents were checked with a bed system measurement device that lacked a required measurement component per the manufacturer's specifications, and the facility did not ensure the bed rails used with the beds were compatible with the bed frames. Resident #1 had diagnoses including dementia, osteoporosis, and muscle weakness. The resident's MDS documented moderately impaired cognition and need for substantial maximal assistance for lying to sitting at the side of the bed. The care plan documented limited physical mobility and use of bilateral bed assist bars. Observations showed the resident's bed was against the wall with bilateral assist rails, and the rails had no manufacturer's label and were affixed with screws to the underside of the bed springs and the surface of the bed springs with a wooden board above the pivot point of the head of the bed. Resident #71 was admitted with multiple sclerosis and sepsis. The MDS documented the resident was cognitively intact and required substantial assistance to move right to left in bed. The care plan documented limited physical mobility and use of bilateral bed assist bars. Observations showed the resident's bed was against the wall with bilateral assist rails that were slightly loose at the base, and the rails and bed frame had no manufacturer's label. The rails were also affixed with screws to the underside of the bed springs and the surface of the bed springs with a wooden board above the pivot point of the head of the bed. Staff interviews confirmed the facility used a bed system measurement device without the scale component, did not retain the test worksheets, and had not followed the bed manufacturer's specifications regarding authorized replacement parts.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0909 citations
Loose Bed Assist Bar Left in Place on Resident’s Bed
D
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

Loose Bed Assist Bar Left in Place on Resident’s Bed: A resident with anxiety, intact cognition, and moderate assistance needs for bed mobility had bed rail assessments that changed over time, with later documentation stating siderails/assist bars were not indicated. Despite this, two assist bars remained on the bed, and the left bar was observed to be loose and freely moving away from the bed. Staff reported the resident did not use the bars, maintenance did not perform monthly checks of bed positioning devices, and administrative staff were uncertain about inspection requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improperly Fitted Specialty Mattress Created Bed Gap
D
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

Improperly Fitted Specialty Mattress Created Bed Gap: A resident with severe cognitive impairment and extensive assistance needs was observed on a low air loss mattress that did not fit the bed frame well, leaving an approximately six-inch gap between the grab bar and the mattress. The QAN and MS both stated the mismatch created an entrapment risk, and the mattress supplier confirmed the mattress was 36 inches wide while the bed frame had width extensions from the original mattress. The resident reported difficulty getting up from the bed and discomfort while sleeping.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Loose Bed Rail Failed During Care
G
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

A resident reported that a circular bed rail was loose before the incident, and staff were aware of the problem but did not ensure it was repaired. During incontinence care, the rail bent flat instead of staying upright, causing the resident to fall to the floor and sustain a femur fracture with severe hip and knee pain.

Inspection fine: $17,155
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incompatible Bariatric Beds and Worn Mattress
D
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

Two bariatric residents had bed-related issues affecting comfort and safety. One resident had a mattress that was too large for the bariatric bedframe and said she felt unsafe and had asked for bedrails that were never provided. Another resident had a properly fitted mattress that was old, lumpy, and uneven, causing back pain and poor sleep. Staff were unaware of the concerns, and the DON and Administrator acknowledged the bed and mattress problems during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Loose Bed Grab Bars
D
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

Loose Bed Grab Bars: A resident’s bilateral bed grab bars were found to be loosely installed and moving sideways, backward, and forward while the resident used them daily to get out of bed and reposition. The Maintenance Director verified that the screws at the bases of both grab bars were loosely attached to the bed frame, and the facility’s maintenance policy required equipment to be kept safe, operable, and free from hazards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Torn Mattress Left in Resident Room
D
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

Torn Mattress Left in Resident Room: A resident’s bed mattress was observed with punctures exposing internal materials and with dips and lumps on the sleeping surface while the bed was unmade. The resident said staff had known about the mattress for over a year and that it was very uncomfortable. The HSKP supervisor said staff usually report worn mattresses, and the administrator said new mattresses had been ordered but was unsure how this one was missed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across New York

Get a heads-up on the newest immediate-jeopardy (J–L) citations in New York — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release October 8, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.