K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
F

Failure to Perform and Document Required Annual Receptacle Testing

Glades Health Care CenterPahokee, Florida Survey Completed on 04-29-2026

Summary

The deficiency involves the facility’s failure to comply with NFPA 99 requirements for electrical systems maintenance and testing, specifically related to receptacle testing for tension and polarity. During a record review conducted between 9:15 AM and 1:30 PM with the Maintenance Director, surveyors requested documentation showing that hospital‑grade and other required receptacles at patient care locations had been tested at the required intervals. The facility was unable to provide documentation that annual testing for receptacle tension and polarity had been performed as required by NFPA 99 (referenced as both the 2012 and 2021 editions in the report). The Maintenance Director acknowledged that the facility failed to provide documentation demonstrating that the required annual receptacle testing for tension and polarity had been completed. The report notes that this failure to maintain and document testing of electrical receptacles could affect all occupants in the facility in the event of a fire or other emergency. No specific residents, clinical conditions, or individual patient events are described in the report; the deficiency is based solely on the absence of required testing records and the associated noncompliance with NFPA 99 Section 6.3.4 for Class III electrical systems.

Plan Of Correction

The Tension and Polarity test was performed throughout the building and completed on .The facility has determined that all residents have the potential to be affected.An in-service education program will be conducted by the administrator.The administrator will conduct for a period of three months a random audit of completed documentation. The Tension and Polarity test was performed throughout the building and completed on [R] . The facility has determined that all residents have the potential to be affected. An in-service education program will be conducted by the administrator. The administrator will conduct for a period of three months a random audit of completed documentation.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0914 citations
Failure to Perform Required Polarity Testing of Electrical Receptacles
F
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

Surveyors identified that the facility did not fully comply with NFPA 99 requirements for electrical receptacle maintenance and testing. Review of the electrical receptacle testing log showed that only tension testing was documented, with no evidence of polarity testing being conducted. During interview, the Maintenance Director confirmed that staff had never tested receptacle polarity. This deficiency was cited as affecting the entire facility and was noted as potentially causing faulty electrical equipment which can result in fire.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Annual Electrical Receptacle Inspections
C
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

The facility did not provide documentation verifying that annual inspections and testing of electrical receptacles in resident care areas were completed, as required by NFPA 99. This deficiency was confirmed by both the Administrator and the Director of Maintenance, and affected all smoke zones within the component.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Test Electrical Receptacles at Resident Bed Locations
F
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

The facility did not perform required testing of electrical receptacles at resident bed locations, including both hospital-grade and non-hospital grade outlets, as mandated by regulations. Documentation and interviews confirmed that testing for physical integrity, polarity, and grounding blade retention force was not conducted throughout the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Test and Repair Hospital-Grade Electrical Receptacles
E
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

Multiple hospital-grade electrical outlets in resident rooms failed inspection, and there was no documentation showing that these outlets were repaired or replaced as required. This deficiency was confirmed by the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiencies in Electrical System Testing and Installation
D
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

The facility failed to accurately test electrical receptacles in resident care areas and lacked documented performance data. Additionally, improper installation of a power cord passing through the ceiling into interstitial space was observed, with a power strip used as permanent wiring above the fire sprinkler system, posing a potential fire hazard. These issues were confirmed by the Director of Maintenance and acknowledged by the Administrator.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Documentation for Electrical Receptacle Inspections
C
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

The facility failed to document the inspection and testing of electrical receptacles in Patient Care Areas. A review revealed missing documentation verifying that these inspections had been conducted, which was confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

65.1% of Ohio facilities received at least one citation during their inspection in the last 12 months.Will yours be survey-ready?

Surveyors issued 55 serious citations across Ohio in the last 12 months. See exactly what they're citing.

Get ready for your next survey

See what surveyors are citing in Ohio and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release May 27, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙