Obstructed Egress Corridors Due to Equipment and Chairs
Summary
The facility failed to maintain required clear egress widths in corridors in accordance with NFPA 101, 2012 Edition, sections 19.2.3.4 through 19.2.3.5 and 7.3.2 through 7.3.2.3, creating projections into the egress corridor that exceeded allowable limits. Surveyors observed that on one day in Station #3, a cart with a television and video equipment was plugged into an outlet in the corridor by room 38, and five activity room chairs were placed in the corridor near the secured unit dining room directly in front of a fire extinguisher. On the following day, surveyors again observed chairs in the Station #3 corridor, with four by room 35 and four by the activities room, and the same television cart still in the corridor; the chairs were not secured. The corridor was approximately eight feet wide, and the projections extended approximately 29 inches into the corridor in front of the handrail. These conditions had the potential to affect 28 residents in the facility and the staff’s ability to assist in an emergency, and the Maintenance Director confirmed the observations at the time of discovery. No specific resident medical histories or conditions were described in the report, only that 28 residents were potentially affected and the facility census was 59.
Plan Of Correction
This Plan of Correction is submitted as required under State and Federal law. This Plan of Correction does not constitute an admission on the part of the Facility that the findings cited are accurate, that the findings constitute a deficiency or that the scope and severity regarding the deficiency cited are correctly applied. Any changes to the Facility's policies and procedures should be subsequent remedial measures and should be inadmissible in any proceeding on that basis. Without admitting or denying the validity or the existence of the alleged noncompliance, the Facility submits this Plan of Correction with the intention that it be inadmissible by any third party in any civil or other action against the facility or any employee, agent, officer, director or shareholder of the Facility. The Facility is utilizing this Plan of Correction as an allegation of substantial compliance as of 05/29/2026 K-0232 Clear path of egress Corrective action for resident/s: 1. On 05/18/2026 station 3 had a cart with a television parked in the corridor by room 38 that exceeded allowable limits. Maintenance director/designee moved the TV cart into the activity room, out to the corridor on 05/18/2026 in accordance with applicable code. 2. On 5/18/2026 station 3 had 5 chairs in the corridor near the dining room directly in front of the fire extinguisher. Maintenance director/designee moved the chairs into the dining room, out of the corridor on 5/18/2026 in accordance with applicable code. 3. On 5/19/2026 station 3 had 4 chairs by the activity room and 4 by room 35. In addition, the TV cart was in the corridor. The maintenance director/designee moved the chairs and TV cart into the dining room, out of the corridor on 5/19/2026 in accordance with applicable code. Identification of other residents who may be affected: Maintenance director/designee completed a 100% facility audit for clear paths of egress on 5/26/26 with no findings or corrective action necessary. Measures for systemic change: Maintenance Director/designee educated staff on 5/26/2026 regarding NFPA 101-2012 section 19.2.3.4 and 19.2.3.5 specifically including maintaining a clear path of egress. How Corrective Action will be monitored Ongoing "Path of Egress Audit" to be completed weekly x 2 weeks, then monthly x 2 months. Corrective action will be initiated for any noted non-compliance. Audit findings will be reviewed as part of the monthly quality assurance process to determine the need for further monitoring. Date of Compliance 05/29/2026
Penalty
Trusted data from CMS and state health departments
Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release May 27, 2026) and official state health department websites — never guesswork.
Trusted by long-term care providers and associations.