F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
E

Incomplete Bed Inspections and Incorrect Entrapment Assessments

Terrace View Care CenterFullerton, California Survey Completed on 02-23-2026

Summary

The facility failed to ensure that bed inspections and entrapment assessments were completed and documented for residents using side rails or bariatric beds. The report identified deficiencies for three sampled residents and one non-sampled resident: one resident on a bariatric bed, two residents with bilateral half side rails, and another resident on a bariatric bed. The facility’s Bed Inspection and Maintenance Policy stated that all beds, rails, mattresses, wheels, and controls were to be inspected routinely, with nursing completing visual safety checks each shift and maintenance completing monthly and quarterly inspections that included entrapment risks. For one resident on a bariatric bed with bilateral side rails for bed mobility and repositioning, the medical record showed a side rail safety assessment, but it did not include the bedframe length, mattress type, mattress height, or mattress length. The resident was observed in bed with bilateral side rails elevated and stated the rails were used for turning and repositioning. Facility staff confirmed the resident had a bariatric bed, and the Maintenance Director stated he was responsible for the bed inspection and entrapment assessment, but the monthly preventive maintenance record did not document the required bedframe and mattress measurements or the applicable entrapment zone measurements. For another resident with padded bilateral half side rails, the physician’s order and care plan addressed the use of the rails for bed mobility and repositioning, but the safety assessment was inaccurate. The assessment identified the bed system zones for 1/4 side rails on both sides rather than 1/2 side rails, and zone 5 was checked even though staff stated zone 5 applies to split side rails and the resident did not have split rails. For a third resident with bilateral half side rails, the medical record did not show a physician’s order for the rails and did not show documented evidence that an entrapment assessment had been completed. For the additional resident on a bariatric bed with a low air loss mattress and bilateral half side rails, the record also did not show documentation of the bedframe length, mattress type, mattress height, mattress length, or entrapment zone measurements during the bed inspection.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0909 citations
Failure to Inspect and Assess Bed Rails and Bed Systems for Entrapment Risk
D
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

Surveyors found that the facility did not conduct or document regular inspections or entrapment assessments of bed frames, mattresses, and bed rails, despite FDA guidance and manufacturer instructions requiring ongoing evaluation of hospital bed systems. Three residents with CVA, hemiplegia, cognitive impairment, and significant ADL dependence had quarter or half side rails in use, but therapy notes, care plans, and MDS assessments did not consistently reflect side rail use or any entrapment evaluations. Staff interviews revealed that the maintenance engineer only addressed side rails when reported broken, a RN was unaware of any side rail safety or inspection procedures, and a PT described routine admission of brain-injured residents with side rails and lap belts while indicating that nursing was responsible for bed safety zoning. The facility’s restraint policy addressed assessment and consent for positioning and safety devices but did not include any schedule or process for device inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incompatible Mattress and Bedframe for Dependent Resident
D
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

A resident with severe cognitive impairment and multiple neurologic and vascular diagnoses was observed on multiple occasions lying on an air mattress that was too small for the bedframe, resulting in the resident’s feet and head extending beyond the mattress and a gap of about one foot between the mattress and the bedframe. A CNA, the ADON, and the DON each confirmed that the mattress did not properly fit the bedframe and did not accommodate the resident’s height.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Bed Entrapment Assessment and Incomplete Bed Inspection Logs
E
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

The facility failed to complete a bed entrapment assessment before a resident used bilateral upper bed rails and failed to document monthly inspections for all beds in use. A resident who had capacity to make decisions and needed partial/moderate assistance with mobility was observed using elevated side rails, and RN and Maintenance staff confirmed the rails were in use and that maintenance was responsible for the zone assessment. The February bed safety checklist did not show the required entrapment measurement for that resident, and the monthly bed maintenance log listed only a few rooms rather than all resident beds.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Loose Bed Rail Not Securely Attached
D
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

A resident with MS, seizures, generalized weakness, and impaired mobility had a loose right-hand mid-bed siderail that would not stay in place. Staff observed the rail drop to the floor when lifted, and a CMT confirmed it was loose and posed an injury risk. The Maintenance Director later found it attached with only one bolt near the head of the bed, and the facility could not provide documentation of weekly bed inspections.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Bed Rail Inspection and Compatibility Deficiency
D
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

Bed Rail Inspection and Compatibility Deficiency: The facility did not ensure regular entrapment inspections of bed systems for two residents using bilateral bed assist bars. Staff used a bed system measurement device that was missing a required scale component, did not retain test documentation, and were not following the bed manufacturer's specifications for compatible replacement rails. One resident had dementia, osteoporosis, and muscle weakness with impaired cognition, and another resident had MS and sepsis with substantial assistance needs for bed mobility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Bed rails were not inspected or documented as safe for two residents
D
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

Bed rails were not inspected and maintained per facility policy for two residents. One resident with a hx of stroke and dementia and another with frontotemporal neurocognitive disorder were observed in bed with raised side rails, but record review found no documentation that maintenance had assessed the beds or attached rails for safety. The MD stated beds were not specifically checked when rails were applied and that neither bed had been inspected for safety.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across California

Get a heads-up on the newest immediate-jeopardy (J–L) citations in California — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙