F0880 F880: Provide and implement an infection prevention and control program.
F

Incomplete Water Management Program for Legionella and OPPP Control

The Lakeland CenterSouthfield, Michigan Survey Completed on 02-11-2026

Summary

The facility failed to have an active and ongoing plan for reducing the risk of Legionella and other opportunistic pathogens of premise plumbing. During interview, the Maintenance Director stated that the Water Management Program was still being put together, identified only himself and one other maintenance staff member as the Water Management Team, and reported daily water temperature checks throughout the facility. He also stated there were no flushing protocols to prevent stagnant water, that hot water tanks were drained and refilled monthly, and that there was no monitoring of chlorine levels or other control measures at that time. During building tour, therapy tubs were observed in the Unit 2 and Unit 3 shower rooms, and the Housekeeping Director stated he had not seen them used. Soiled linen rooms on Units 1 through 4 had hoppers with spray arm attachments; three of the four hoppers worked when flushed, while the Unit 1 hopper had a sign indicating do not use and the water had been turned off because it did not flush. Record review showed monthly reports from 2023 through 2025 from a water treatment contractor indicating a corrosion control/secondary treatment service was in place, but the Nursing Home Administrator was not aware of a treatment system and believed the contractor was only providing testing. Later interview with the former Maintenance Director confirmed the corrosion control system had been in place since before 2021, and observation confirmed the treatment system was operating with sodium silicate injection into the cold water distribution piping. The Water Management Program binder also lacked several elements, including a text description of the water system, a comprehensive assessment of where Legionella and other opportunistic waterborne pathogens can grow and spread, measures based on nationally accepted standards, and documentation of visible inspections, disinfectant levels, or flushing protocols. The Legionella Water Management Program document in the binder was revised July 2017, did not contain the facility name or site-specific information, and did not show evidence of annual review and update.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0880 citations
Infection Control Practices Not Consistently Implemented for Resident Evaluated for C. difficile
D
F0880 F880: Provide and implement an infection prevention and control program.
Short Summary

A resident being evaluated for C. difficile was not consistently managed under the correct contact-enteric precautions. Staff gave care with incomplete understanding of the precautions, the room signage did not clearly identify the needed disinfectant or contact time, bleach wipes were not always available, and staff were observed missing hand hygiene and handling items under PPE during care.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Use EBP PPE During Wound Care
D
F0880 F880: Provide and implement an infection prevention and control program.
Short Summary

Failure to Use EBP PPE During Wound Care: A resident with a wound and severely impaired cognition was receiving ordered wound care when the DON and ADON entered the room, washed hands, and donned gloves but did not wear gowns before starting care. EBP signage and PPE were present at the bedside, and both leaders later stated they forgot to put on gowns even though the resident was on EBP for an open wound and the facility policy required gown and glove use for wound care.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Follow Enhanced Barrier Precautions and Hand Hygiene During Resident Care
D
F0880 F880: Provide and implement an infection prevention and control program.
Short Summary

Staff failed to consistently follow EBP and hand hygiene for two residents who required high-contact care. One resident with an indwelling catheter and cognitive impairment did not have EBP followed during transfers, clothing removal, and pericare, and another resident with a suprapubic catheter and multiple pressure ulcers had staff wear PPE incorrectly, remove PPE in the room without hand hygiene, and continue care after emptying the catheter bag without changing gloves or cleaning hands. Interviews confirmed staff were expected to use gowns, gloves, and hand hygiene for these tasks.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Use Required PPE for Resident on Contact Precautions
D
F0880 F880: Provide and implement an infection prevention and control program.
Short Summary

A resident on Contact Precautions for active C. difficile infection was not consistently protected by required PPE. Although signage outside the room directed all entrants to wear a gown and gloves, an RN entered the room with medications without either item and touched the bedside table and door surface. The resident stated staff did not always wear gowns, and the DON confirmed staff were expected to wear a gown and gloves when entering the room while precautions were in place.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Infection Control Lapses During Incontinence and Ostomy Care
E
F0880 F880: Provide and implement an infection prevention and control program.
Short Summary

A facility failed to maintain infection control during care for two residents. During incontinence care, a CNA removed gloves and applied clean gloves without hand hygiene before placing a clean brief on a resident who was dependent for toileting hygiene and always incontinent. During ostomy care, an LVN handled a resident’s colostomy, wiped stool from the stoma, and continued care without removing soiled gloves, sanitizing hands, or putting on clean gloves. The DON stated staff were expected to perform hand hygiene between glove changes.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Infection Control Failures During Incontinent Care
D
F0880 F880: Provide and implement an infection prevention and control program.
Short Summary

Infection Control Failures During Incontinent Care: Two residents were observed receiving incontinent care with multiple infection control lapses. A CNA did not perform hand hygiene between glove changes or after glove removal while caring for one resident, and another CNA did not wash hands before care, changed nothing between dirty and clean tasks, touched clean items with dirty gloves, placed soiled linens on the floor, and handled dirty linens with bare hands after glove removal. The DON stated hand hygiene, glove changes, and proper handling of soiled linens were required, and facility policies reflected those practices.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Michigan

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Michigan — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release October 8, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report