F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
D

Bathroom Ventilation Fans Not Operational

The Springs At St. Andrews VillageAurora, Colorado Survey Completed on 03-26-2026

Summary

The facility failed to ensure adequate outside ventilation by window or mechanical ventilation for three of 12 residents’ personal bathrooms because the ventilation fans were not kept operational. During observation, three resident personal bathrooms were found to have no air flow present at the bathroom vents. The bathrooms were in room [ROOM NUMBER], room [ROOM NUMBER], and room [ROOM NUMBER]. During interview and observation with the maintenance director, tissue paper placed at the vents in the three bathrooms was not pulled into the vents, indicating decreased or absent air flow. In one bathroom, the maintenance director removed the vent cover and had to place his hand up to the wrist into the vent opening to detect any air flow. He stated he was not aware of the decreased air flow and could not explain the reason for it. A work history report later provided showed an inspection of exhaust fans had been completed, but it did not identify which specific resident personal bathroom exhaust fans were inspected.

Penalty

Inspection fine: $14,220
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0923 citations
Nonfunctional Bathroom Ventilation in Multiple Resident Rooms
F
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Bathroom ventilation was not functioning in eight sampled resident rooms, including rooms 102, 105, 107, 114, 119, 121, 204, and 206. Surveyors verified the issue with a one-ply tissue during screening and the environmental tour, and the FM confirmed the problem. The facility also lacked an HVAC policy and a preventative maintenance program, and its HVAC checklist only addressed filter checks.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Functional Mechanical Ventilation in Soiled Utility Room and Resident Bathrooms
E
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Surveyors found that mechanical ventilation in a soiled utility room and in resident bathrooms on two halls was not functioning. A strong, pungent odor was present in the soiled utility room, and testing of the ceiling vents with tissue paper showed no suction. The maintenance supervisor confirmed the vents were non-functional and reported that a single unit controlled ventilation for the soiled utility room and both halls’ bathrooms, suggesting a possible belt issue. This failure had the potential to affect all residents on those halls.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Bathroom Ventilation Systems Not Operational
D
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Bathroom ventilation systems were not operational in several resident bathrooms, as the fans ran but did not draw a 1-ply square of toilet paper during observations. The Maintenance Director said the fans were only checked monthly by listening for operation, and the Maintenance Man was unaware the systems were not working. The Administrator confirmed the bathroom ventilation was not working and that there was no policy and procedures for the ventilation system.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Bathroom Ventilation Systems Not Functioning and Contaminated
E
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Bathroom vents in rooms 200, 201, 203, 205, 207, 209, 211, and 213 were not functioning and were found with whitish, brown debris. Observations showed the vents did not draw up a 1 ply sheet of toilet paper, and the ADM and Maintenance Director confirmed the vents were not working and had not been checked in a few months.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Nonfunctioning Bathroom Exhaust Vents in Resident Rooms
D
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Surveyors found that bathroom exhaust vents in two resident rooms were not functioning, as they did not pull air in, despite facility logs indicating that one of these rooms’ vents had previously been checked and recorded as working. Review of the exhaust fan inspection log showed that only a small number of rooms in each hall were checked monthly over several months, and during an on-site observation and interview, the MD confirmed that the vents in the identified rooms were not operating.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Inadequate Bathroom Ventilation and Odors
D
F0923 F923: Have enough outside ventilation via a window or mechanical ventilation, or both.
Short Summary

Inadequate bathroom ventilation and odors: The facility failed to maintain working ventilation in two shared resident bathrooms and two public bathrooms, with strong urine and feces odors noted on the 2nd floor. Several fan covers were dusty, multiple fans could not be heard or were not working, and one bathroom window was blocked by a bathtub setup that prevented it from being opened. The MTD confirmed the fans were not working properly and said the bathrooms needed functioning ventilation because they did not have usable windows.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Colorado

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Colorado — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙