F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
B

Insufficient Bedroom Square Footage in Multiple Resident Rooms

Burbank Healthcare & RehabBurbank, California Survey Completed on 03-12-2026

Summary

The facility failed to provide at least 80 square feet per resident in 41 of 72 rooms, including Rooms 101, 103, 105, 106, 116, 119, 120, 121, 122, 123, 125, 126, 128, 130, 131, 133, 135, 201, 202, 203, 204, 205, 208, 209, 210, 211, 214, 216, 217, 218, 219, 220, 221, 222, 224, 225, 228, 229, 230, 231, and 232. The room sizes listed in the facility’s Room Waiver Request Letter showed multiple rooms measuring 209 sq ft for three-bed capacity, 220 sq ft for three-bed capacity, 154 sq ft for two-bed capacity, 154 sq ft for three-bed capacity, and 294 sq ft for four-bed capacity, with per-resident space below the stated minimum requirements. The facility policy stated that bedrooms must meet federal and state requirements, including at least 80 square feet per resident in double rooms and at least 100 square feet in single rooms. During observations from 3/9/2026 to 3/12/2026, surveyors observed a sufficient amount of space for residents to move freely inside the rooms with an application for room variance. The observations also noted adequate room for the operation and use of wheelchairs, walkers, or canes. The facility’s waiver request letter stated that the space in these multiple resident rooms was sufficient to provide access and freedom of movement, did not have adverse effects on residents’ health and safety, and did not impede residents’ ability to reach their highest practicable well-being. During interview, the DON stated that residents’ rooms should have enough space between beds to allow movement, and that the room waiver request was submitted to meet the required square footage for each resident. The DON also stated staff check for environmental hazards and clutter in rooms, especially those with room waivers, and stated that insufficient room size could leave residents without enough space to move around and create risk for falls and injury.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0912 citations
Insufficient Room Size in Multiple Resident Bedrooms
B
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

Insufficient Room Size in Multiple Resident Bedrooms: The facility failed to ensure four semi-private rooms met the required minimum of 80 sq. ft. per resident. The ADM stated the rooms were in an unused area awaiting renovation, but they remained listed on the bed classification form. The ADM also stated the facility had no policy for the room size waiver and confirmed the rooms were not planned to open in the near future.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Resident Rooms Did Not Meet Required Square Footage
B
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

Resident Rooms Did Not Meet Required Square Footage: Based on record review and interviews, 14 of 15 resident rooms inspected did not meet the required square footage per resident for privacy and comfort. The Bed Classification Form showed a 144-bed capacity, and the Administrator stated she was not aware of any room waivers. Measurements identified multiple rooms with less than 80 sq ft per bed, and the Administrator later confirmed the form was accurate and said she could not advise that a waiver request had been submitted previously.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Shared Rooms Did Not Provide Required Floor Space
B
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

Shared rooms did not provide the required 80 SF per resident in 23 rooms. A census report showed multiple rooms with three residents or capacity for three residents, and a tour confirmed the room arrangements. The DON stated bed management meetings did not address moving residents to meet the space requirement, and the administrator said current residents were not informed when a bed opened unless they requested a room change. One room measured 230 SF, providing 76.67 SF per resident when occupied by three residents, and a resident stated more space would be helpful for belongings and movement.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Insufficient Space in Multiple-Resident Rooms
B
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

A facility failed to ensure 14 of 33 resident rooms met the required 80 sq ft per resident for multiple-bed rooms. Although the ADM requested a room waiver and staff, residents, and the ADON, DON, DOR, and ADOR stated there was enough room for care, movement, ADLs, and therapy, the Client Accommodation Analysis showed several three-bed rooms measured only 72.1 to 79.8 sq ft per resident, below the required standard.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Insufficient Room Size in A-Wing Single Resident Rooms
B
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

The facility failed to ensure that 13 single resident rooms on the A-wing met the required 100 sq ft of usable floor space, and 6 occupied rooms were identified as noncompliant. The DON confirmed the rooms did not meet the standard, while an RN reported no resident complaints about room size and the Administrators stated they had no requests for room moves or complaints from current residents. One resident said staff care was not inhibited by the room size, and the facility reported it had previously moved a resident to a larger room for family visiting needs.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Provide Required Minimum Square Footage in Multi-Occupancy Rooms
D
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

The facility failed to meet regulatory and policy requirements for minimum usable living space in multi-occupancy resident rooms. Policy required at least 80 sq ft of usable floor space per resident in semi-private rooms, but surveyor measurements of multiple bed areas in two rooms, conducted with the maintenance director, DON, and later the administrator, showed bed spaces ranging from about 47 to 75.33 sq ft, even when adjacent common areas were included. The administrator confirmed that these room sizes were below the required minimum.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across California

Get a heads-up on the newest immediate-jeopardy (J–L) citations in California — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙