Failure of Corridor Fire Doors to Fully Close Due to Faulty Door Arranger
Penalty
Summary
Surveyors observed that the double rated fire corridor doors located outside of resident room 210 did not fully close due to a failing door arranger. This deficiency was identified during an inspection on June 24, 2025, at approximately 12:15 PM. The inability of the doors to close completely compromises their function to resist the passage of smoke, as required by NFPA 19.3.6.3. The observation was confirmed through an interview with the maintenance director at the time of the inspection. This issue affects the doors protecting corridor openings, which are critical for preventing the transfer of smoke, heat, and fire between compartments. The deficiency could potentially impact 50 occupants in the event of a fire, as the compromised doors would allow smoke and fire to move from one compartment to another. No specific details about individual residents' medical histories or conditions at the time of the deficiency were provided in the report.