Failure to Maintain Safe Hot Water Temperatures Resulting in Immediate Jeopardy
Summary
The facility failed to maintain hot water temperatures at a safe level on one of its nursing units, specifically the C-Wing, resulting in water temperatures ranging from 137.1°F to 138.4°F in resident rooms and the shower room. These temperatures were significantly above the safe range of 95°F to 110°F, as acknowledged by both the Regional Licensed Nursing Home Administrator (RLNHA) and the Maintenance Director (MD). The C-Wing unit, which included cognitively impaired residents, was serviced by a separate boiler that lacked a temperature gauge and was found set to high. Multiple staff, including the RLNHA, confirmed the excessive temperatures and agreed that such conditions could cause burns. Residents on the C-Wing reported that the hot water was so hot it could be used to make tea or instant noodle soup, indicating prolonged exposure to unsafe water temperatures. One resident with fully intact cognition and another with moderately impaired cognition both confirmed the water had been excessively hot for some time. The surveyors directly measured the high temperatures in the presence of facility staff, who acknowledged the findings. Despite daily water temperature checks being claimed by the MD, the temperature logs for C-Wing were incomplete and did not show any recent entries, nor did they specify the locations where temperatures were taken. The facility did not have a written water temperature policy and relied on regulatory standards. The lack of documentation and monitoring, combined with the absence of a temperature gauge on the C-Wing boiler, contributed to the failure to detect and address the hazardous water temperatures. The issue was identified during a survey following a recent fire that had affected utilities, but the facility's staff denied any prior issues with high water temperatures. The deficiency was found to have placed residents, including those with cognitive impairments, at risk of serious injury from scalding.
Removal Plan
- The Maintenance Director lowered the hot water temperature on the boiler.
- Water temperatures were obtained throughout every residents' room in the facility.
- The facility initiated water temperatures to be taken every two hours for three days.
- All residents on C-Wing were assessed for skin damage.
- The facility conducted a resident council meeting to discuss safe water temperatures with the residents.
- The Director of Nursing/designee initiated a house-wide staff in-service on safe water temperatures, the process of taking water temperatures, and any staff not in-serviced would be prior to their next shift.
Penalty
Resources
Below are regulatory guidelines relevant to this citation:
Trusted data from CMS and state health departments
Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.
In your survey window? See what surveyors are citing.
The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.