F0584 F584: Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
L

Failure to Maintain Safe and Comfortable Temperatures

Grand Manor Nursing & Rehabilitation CenterBronx, New York Survey Completed on 12-19-2024

Summary

The facility failed to maintain safe and comfortable temperature levels throughout the building, as required by federal and state regulations. Observations during the survey revealed that all sampled resident rooms, corridors, and stairwells on five resident floors had temperatures below the required range, with some areas as low as 40 to 53 degrees Fahrenheit. Multiple complaints and grievances were filed by residents regarding the loss of heat over a period of time, and maintenance logbooks documented ongoing heating issues in 23 resident rooms. Despite these reports, there was no documented evidence that the facility had identified or addressed unsafe room temperatures. The Administrator was unaware of the loss of heat or that room temperatures had dropped below regulatory standards, and stated that the PTAC units were not necessary because the boiler was supposed to provide heat. However, maintenance records and vendor invoices indicated that the boiler system was not functioning properly, with only 5 of 13 boilers operational at one point, and that the facility had not maintained an active service contract for preventive maintenance. Vendor communications documented repeated recommendations and proposals for repairs and maintenance that were not addressed by the facility. Staff interviews confirmed that the heating issues were discussed in meetings and that activities staff were called in to distribute hot drinks due to the cold conditions. The Medical Director was not aware of the heat-related issues, and temperature logs maintained by the facility were incomplete, lacking specific room or corridor information. The facility's failure to maintain adequate heating resulted in Immediate Jeopardy and Substandard Quality of Care, affecting all residents in the building.

Removal Plan

  • Packaged Terminal Air Conditioner units were deployed to all affected areas. Residents were relocated to warmer areas of the facility and temperature checks of all residents' rooms were conducted by the facility. A review of the temperature logs revealed temperatures within acceptable ranges.
  • Extra blankets and clothing were distributed to the residents by Housekeeping and Activities staff, hot beverages were provided, and residents had the option of staying in the warmer common areas.
  • The Administrator provided a vendor contract to provide annual maintenance to boilers, and for the maintenance of Packaged Terminal Air Conditioner units.
  • The facility completed staff training on identifying and addressing temperature related issues, procedures for reporting issues, deploying emergency measures, and ensuring resident comfort. All staff received the in-service.
  • Wall thermometers have been installed in residents' rooms and staff were given in-service education on reading the temperature.
  • The Emergency Preparedness plan for Loss of Heat was revised to include immediate deployment of portable units and proactive monitoring and escalation processes for heating issues.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0584 citations
Unclean Bed Linens
D
F0584 F584: Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
Short Summary

Unclean Bed Linens: A resident with hypothyroidism and chronic diastolic heart failure had a pillowcase with several dry dark brown/red areas and sheets that appeared gray and unclean. The resident could not remember the last time the linens were changed, and the DON confirmed the linens should have been changed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Dirty Resident Room and Respiratory Equipment
D
F0584 F584: Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
Short Summary

Dirty Resident Room and Respiratory Equipment: A resident with dysphagia, a feeding tube, and a tracheostomy had a room observed with a dirty fan, debris on the mattress, dust and dried debris on the O2 concentrator and trach machine, and a dirty towel on the bed. A family member reported the area by the bed was often dirty from tube feeding, and an LPN Resident Care Manager agreed the room was dirty and needed daily cleaning.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Baseboards on Second-Floor Hallway and Resident Room
D
F0584 F584: Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
Short Summary

A resident’s room and the second-floor hallway had missing baseboards, including under the window in the room and periodically along both sides of the hall. During interview, an Mnt. employee stated the machine must be hitting them and that they had been taken off.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Damaged Resident Room Wall Left in Disrepair
D
F0584 F584: Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
Short Summary

A resident room wall near the window was observed damaged and in disrepair, with a crack large enough for an ink pen to be inserted through it. The Maintenance Director said he knew about the damage after the resident reported it about 2 weeks earlier and believed it was caused by an AC leak. The damaged area covered about 6 square feet, while the Administrator said she was not aware of it and that the facility did not have a specific audit for wall or structural integrity checks.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsafe and Deteriorated Resident Room Conditions
D
F0584 F584: Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
Short Summary

Unsafe and Deteriorated Resident Room Conditions: Surveyors observed multiple resident rooms with broken, rusted, unsecured, and deteriorated conditions, including a hanging drawer front, scuffed and chipped walls, missing wall trim/chair rails, rust on a bedframe and AC shelf, a broken bathroom tile, and a gallon of Clorox stored in a bathroom. The Maintenance Director acknowledged the environmental conditions during the walkthrough, and photographic evidence was obtained.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Cleanliness, Safety, and Equipment Sanitation Deficiencies
E
F0584 F584: Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
Short Summary

The facility failed to maintain a clean, safe, and homelike environment. Surveyors observed dirty hallway vents, ceiling areas with residue, damaged walls, protruding door panel edges, missing tile and cracked flooring in shower areas, and multiple unsanitary conditions in resident rooms, including cracked light covers with bugs, uncovered soiled items, and substances on floors, mattresses, bed sheets, and bedside tables. Two residents’ wheelchairs also had dried substances and hair buildup, and staff acknowledged some areas needed repair or cleaning.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across New York

Get a heads-up on the newest immediate-jeopardy (J–L) citations in New York — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release October 8, 2026) and official state health department websites — never guesswork.