K0511 K511: Have properly installed electrical wiring and gas equipment.
E

Combustible Storage Blocking Access to Electrical Panels

Medilodge Of HollandHolland, Michigan Survey Completed on 05-08-2025

Summary

Observation on May 8, 2025, revealed that combustible storage was blocking access to the electrical panels and generator transfer switch in the mechanical, networking, and generator transfer switch room. This situation was identified during a walkthrough and confirmed by interview with the facility Maintenance Director at the time of observation. The report notes that this arrangement does not comply with NFPA 70, National Electric Code, which requires clear access to electrical equipment. The deficiency could potentially affect 20 occupants and staff within the smoke compartment if immediate access to the electrical panels is needed during an electrical or fire emergency.

Plan Of Correction

The items in front of the electrical panel in the mechanical/networking/transfer switch room were moved by the Maintenance Director on 5-21-25. A one-time audit was completed by the Maintenance Director on 5-21-25 to ensure all storage room areas and electrical panel locations were free from items which would prevent access to them. Education was provided to the Maintenance Staff on 5-20-25 as to the requirements of having a clear path and space in front of all electrical panels. A weekly audit x4 than monthly x3 will be completed by the Maintenance Director or designee to ensure all areas in front of electrical panels are free from items that would restrict access to them. Audit findings will be presented to the facility QAPI committee and will only be discontinued with substantial compliance and with approval of the facility QAPI. The Administrator is responsible for achieving and sustaining compliance.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0511 citations
Improper Fastening of Circuit Breaker Panel Cover with Sheet Metal Screws
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors found that a circuit breaker panel cover in one smoke compartment was improperly fastened with sheet metal screws instead of appropriate blunt-end fasteners, in violation of NFPA 70 requirements. The maintenance director acknowledged the use of sheet metal screws on the panel cover, and the report notes that this noncompliance could result in electric or fire hazards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improperly Labeled and Maintained Electrical Panels
F
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors identified that the facility’s electrical system was not maintained according to NFPA 101 and NFPA 70. In the kitchen electrical panel, breakers labeled for the dishwasher were in the off position while the dishwasher continued to run with power. In generator sub panel B, a breaker was labeled for a sprinkler pump even though no sprinkler pump existed, and there was an open breaker position without a blank cover. These issues were confirmed by the Maintenance Director and had the potential to affect all residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-GFCI Electrical Outlet Near Sink in Medication Room
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors observed that an electrical outlet in Nursing Station 1's med room was installed 18 inches from a sink and was not equipped with a required ground-fault circuit interrupter (GFCI), as mandated by NFPA 70, National Electrical Code. The DES confirmed during the survey that this outlet lacked GFCI protection, resulting in a cited deficiency related to utilities and electrical safety in one of the facility’s smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Exposed Electrical Wiring Due to Missing Junction Box Cover
E
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

An electrical junction box above the Zone 8 suspended ceiling, near the smoke barrier doors by the Unit Scheduler's Office, was found without a cover plate, leaving electrical wiring exposed. The Director of Maintenance confirmed the issue during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Noncompliance with Gas and Electrical Safety Standards
F
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors observed multiple deficiencies including broken light bulb bases left in ceiling sockets, combustible materials stored too close to electrical panels, and exposed wiring behind a boiler. These issues were confirmed by facility leadership during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Broken Electrical Outlet Faceplate at Nurse Station
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

An electrical outlet at Nurse Station #2 was found with a broken faceplate, exposing metal terminals. The CMO confirmed the damage had not been previously noticed. Facility policy assigns the Maintenance Director responsibility for maintaining safe equipment, but the exposed outlet was not addressed as required by NFPA 70.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Michigan

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Michigan — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙