K0161
F

Non-Compliance with Sprinkler System Requirements in Attic Space

Eastwood Nursing CenterNegaunee, Michigan Survey Completed on 04-03-2025

Summary

The facility failed to ensure that its building construction type and number of stories complied with the requirements outlined in Table 19.1.6.1, as required unless otherwise permitted by specific exceptions. During a record review and interview, it was found that the dry sprinkler system in the attic space did not pass inspection because the system was capped and only six sprinkler heads were operational. The annual dry sprinkler inspection report confirmed this deficiency, and the Maintenance Director verified that the attic sprinkler system was not functioning properly. This failure is in violation of the requirement that all LTC facilities be fully sprinklered and maintain their systems as mandated by 73 CFR 47075.

Plan Of Correction

1. The facility did not maintain the dry sprinkler system in proper working condition throughout the building. 2. A malfunctioning dry sprinkler system poses a risk to the safety of all residents, staff, and visitors in the event of a fire emergency. 3. Corrective actions have been completed as follows: - Excel Fire Protection replaced the 3-inch and 4-inch system piping. - Superiorland Electronics installed a second air compressor and replaced 12 feet of main sprinkler piping. - The sprinkler system was flooded and tested, revealing two leaks (located above a resident room and in the boiler room); both have been repaired. - Superiorland Electronics will conduct a trip test to confirm the system is functioning properly. - The Maintenance Director has been educated on the critical importance of maintaining the dry sprinkler system in working order. - Superiorland Electronics will complete the hydrostatic testing of the system by 5/23/25. 4. The Maintenance Director is responsible for ongoing monitoring of the dry sprinkler system to ensure it remains operational at all times and will report system status and maintenance updates to the Quality Assurance (QA) Committee.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0161 citations
Non-Compliance with Fire Resistance Rating Due to Excessive Building Height
C
K0161
Short Summary

Surveyors found that the facility, classified as a five-story Type II (000) unprotected non-combustible building with a basement, exceeded the maximum allowable number of stories for its construction type, despite being fully sprinklered. This non-compliance with NFPA 101 fire resistance requirements was confirmed by facility leadership and affects the entire building.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Follow Up on Building Structural Assessment
F
K0161
Short Summary

The facility did not follow up on a vendor-provided building structural assessment quote that was part of an ongoing plan of correction, as confirmed by document review and interview with the maintenance supervisor. This failure potentially affected the building's structural integrity.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Resistive Rating Due to Missing Ceiling Tiles
E
K0161
Short Summary

Surveyors found that the facility did not maintain the required fire resistive rating on one floor, as missing rated ceiling tiles were observed in the second floor IT/Conference Room and confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Noncompliance with Building Construction Type and Height Requirements
C
K0161
Short Summary

Surveyors found that the facility is a four-story, Type II (000) unprotected noncombustible structure that is fully sprinklered, which exceeds the maximum number of stories allowed by the 2012 Life Safety Code for this construction type. Facility leadership confirmed the building's structure does not meet code requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Noncompliance with Building Construction Type and Height Requirements
C
K0161
Short Summary

A survey found that the facility is a three-story, Type II (000) unprotected noncombustible building with a basement, which exceeds the maximum allowable story height for this construction type. The Director of Maintenance confirmed that the building's construction type and height are not permitted under current regulations.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Ceiling Penetration in Electrical Room
D
K0161
Short Summary

During a facility inspection, an unsealed four-inch penetration was found in the ceiling of the electrical room, with a conduit passing through. The Maintenance Consultant stated that this resulted from recent utility upgrades where the vendor did not seal the opening after completing their work. The deficiency affected one of two smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Michigan

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Michigan — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙